CW-5000/5200 Series Industrial Chiller maintenance manual
-
目录
Ⅰ Chiller Alarm (red light on)--have water circulation P3-7 Ⅱ Chiller Alarm (red light on)--not water circulation P7-8 Ⅲ CW-5000 Series Temperature Controller T-503 alarm 3.1.Alarm code E1: ultrahigh room temperature P8-9 3.2.Alarm code E2: ultrahigh water temperature P9-12 3.3.Alarm code E3…
-
Ⅰ、Chiller Alarm (red light on)--have water circulation
Turn off the chiller power, use the water pipe of about 1 meters length to connect the outlet with the inlet short (pictured), turn on the chiller, and continue to observe the condition of the chiller. Observation effect I: water cycle normal, stop alarm (green light on) Cause analysis The external…
-
Baffle Flow Switch
2)Cut off the bezel flow switch two red power wire, and short connection, boot to observe whether continue to alarm 2.1)If the alarm stop(green light on),can determine the flow switch failure Recommendation: Replace the baffle flow switch 2.2)If the chiller continues to alarm (red light on), please…
-
3.2)If the chiller continues to alarm (red light on), please reconnect the flow switch power
wire, and do the step 4) detection 4)Measuring the relay coil Input voltage by measurement tool Remarks: Baffle Flow switch model relay coil AC220V; Hall flow switch model relay coil DC24V 4.1) If the relay (such as picture) coil does not enter the normal operating voltage, can be judged flow switch…
-
Recommendation: Clean the internal piping, replace the pipe that has been bent or
badly blocked. 2)Use the measuring tool to detect the switching power supply (picture) Output voltage: CW-5000 Series switching power supply operating voltage is DC24V. 2.1)If the switching power supply output is lower than DC18V, the low voltage is affecting the pump lift and flow, can determine…
-
Suggestion: disassemble the DC pump casing to observe whether the rotor is plugged or
worn, if unable to recover, need to replace DC pump Ⅱ Chiller Alarm (red light on)--not water circulation Cause analysis 1 Low water level 2 Switching power supply problem 3 DC Pump problem Detection method 1)Observe whether water tank is lower than pump inlet Recommendation: Add Pure water 2)Use…
-
2.1)If the switching power supply output is lower than DC18V, the low voltage is
affecting the pump lift and flow, can determine the switching power supply or pump failure. Suggestion: Change the switching power supply first to determine whether the pump is faulty too. 2.2)If the switching power supply has the output DC24V, may determine the water pump failure. Suggestion…
-
Cause analysis
1 More than 40 ℃ ambient temperature or machine placement is not ventilated Suggestion: The chiller is placed in the ventilated position, there must be at least 30cm from obstructions to the air inlet(The dust gauze), and should leave at least 50cm between obstruction and the air outlet(The fan). 2…
-
2)When the thermostat is in the refrigeration state
2.1)Using measuring tools to measure the output terminals of the compressor after the temperature control of the normal operating voltage output: if there is no voltage output, can determine the temperature controller failure, if the voltage output, can be used for next detection; 2.2)Using…
-
3.2)Use the measurement tool to detect the compressor input voltage is normal (depending
on the model: please refer to the manual technical parameters), such as the voltage below the compressor start-up voltage, the compressor does not run; 3.3)Use the measuring tool to detect whether the compressor overload protector output terminal has voltage, such as output voltage output, can…
-
5)Solenoid valve has been guided
6)Compressor Rotor not working (The above two points need to return to the factory for further testing) 3.3.Alarm code E3: ultralow room temperature Cause analysis 12
-
1、Low ambient temperature (such as autumn and winter season) when the first boot
appears E3 alarm is the normal status, can add a moderate amount of warm water to restore the temperature 3.4 Alarm code E4: room temperature sensor failure Cause analysis 1 Wiring Loose 2 Sensor failure Detection method 1) Find the terminal of the temperature sensor and the temperature transducer…
-
1.1)If the alarm stop can judge the terminal contact bad, reconnect the relative terminal
1.2)If there is a E5 alarm, can determine the temperature controller malfunction, such as the emergence of E4 alarm, can determine the temperature sensor failure; 1.3)If E4, E5 at the same time alarm, recommended to replace room temperature sensor and temperature sensor and temperature controller Ⅳ…
-
lines have AC220V voltage (depending on the model), such as detection of the power switch
only a group of lines have AC220V voltage, can be judged as power switch failure, need to replace the power switch 15