Инструкции на Контроллер MicroTech II (для ALS, WHS, PFS).
Контроллер MicroTech II (для ALS, WHS, PFS). Сервисное руководство.
Загружаем документ…
Текст инструкции
-
MCQUAY MicroTech II Control
pLAN+Driver for Modular Chillers McQuay ALS / WHS / PFS With screw compressors, 1 to 4 circuits Release of the Manual: 1.0 - 01/05/2001
-
Applications and functions carried out by the system
Type of controlled units air / water only chiller air / water chiller + heat pump Compressor maximum number Max. 1 compressor for MicroTech II card, with max. 4 MicroTech II card capacity controls Compressor type Screw compressors Compressor call rotation Rotation of all the compressors with FIFO…
-
Master/slave system architecture
The system is composed of at least two up to four MicroTech IIs connected to the local network of which the first acts as master and the following act as slaves. Master function Temperature regulation All compressor call Manages the system alarms Management of a refrigeration circuit (start, stop…
-
Input/output list
Below the inputs and outputs are listed as a function of the unit type; a number has been associated to each type of machine. This number is the principal parameter of the program as it identifies the input and output configuration. In this way the configuration of the machine is made very easy…
-
WATER/WATER Unit with max. 2 screw compressors, McQuay PFS
Digital inputs Only Chiller unit MACHINE TYPE “3” N UNIT 1(Master) UNIT 2 (Slave) On/Off by Main Switch Evaporator flow controller (enabling) Remote On/Off Oil Level 1 Low pressure switch 1 Oil differential 1 Phase Monitor (enabling) Double Setpoint N.U. Failed trans. Y/∆ High pressure switch 1…
-
Regulation
Outlet temperature regulation CONTINUOUS UNLOADING Used Inputs: • Inlet Temperature • Outlet Temperature Used Parameters: • Regulation Setpoint • Outlet temperature Regulation Band • Continuous unloading Dead Band Dead-band • Pulse Period • Minimum Pulse Time for solenoid 1 • Maximum Pulse Time for…
-
Logic of the Continuous unloading through the points of the graphic
Compressors will start when temperature will be higher than the upper end of the neutral zone ( Setpoint + band). Consequently compressors will start after point E, and increasing pulses will have the maximal duration. At compressors start discharge is forced for a selectable time. Temperature…
-
In program masks will be selectable
• Output Setpoint of the regulation (User Menu) è Point B • Temperature Band for output regulation (User Menu) è between B and E • Neutral Band to control continuous unloading (User Menu) è between C and D • Solenoid Configuration for the phase of stand-by • Solenoid Configuration for the phase of…
-
Forced Unloading
Used inputs: • Outlet Temperature (B2) • High pressure (B7) Used Parameters: • Prevent Threshold of high temperature on discharge • High pressure Threshold • High pressure Differential • Antifreeze temperature Threshold • Antifreeze Differential Used Outputs • Unload Solenoids Principles of working…
-
Used inputs: • Thermostat (inlet temperature) Used Parameters: • Delay time to start. Used Outputs: • Fan group. • Liquid solenoid Valve. • Compressor. Description of the logic : Start phases are described in the following graphic : THERMOSTAT LIQUID SOLENOID FAN GROUP COMPRESSOR Delay to Start…
-
Start of the compressor motor
Used Inputs: • Inlet Temperature Used Parameters: • Time between star and line • Star pulse duration • Time between star and delta Outputs used : • Contactor Line • Contactor Star • Contactor Delta Description of the Logic: Motor star is described in the following diagram : Contactor Line Contactor…
-
PUMP-DOWN Management
Pump-down function is executed at compressor shutdown. It ends due to the low pressure switch or, in case this faults, for maximal time. Pumpdown Used Inputs: • Low pressure transducer Used Parameters: • Pump-down type • Pump-down enabling by switch with unit off • Pump-down Setpoint in fix mode…
-
Compressor Rotation
The compressor-call rotation causes the hour number and the start-stop number of different compressors to be equivalent. Rotation is carried out according to a FIFO-type logic; this means that the first compressor to start will be the first to stop. As a consequence of this behaviour, remarkable…
-
Condensation regulation
Condensation can be carried out as follows: • on/off bound to the compressor working ( without the pressure transducers) • on/off or modulating bound to the reading of the pressure transducer (if the high-pressure transducers have been enabled) • on/off or modulating bound to the reading of the…
-
When this threshold is reached with compressor on, fans are forced on until the pressure falls down the setpoint - a selectable differential. Condensation Control with cut enabling This logic is applied to the units where the continuous speed control is requested to allow the unit to work with a…
-
Antifreeze regulation
Used inputs • Output temperature probe Used parameters: • output probe enabling • antifreeze heater Set-Point • antifreeze heater differential • antifreeze alarm Set-Point • antifreeze alarm differential Used outputs: • antifreeze heater Each MicroTech II unit can manage the antifreeze regulation…
-
Electro-valve Management
This software is configured to handle only the Electro-valve liquid-injection Used Inputs: Discharge Temperature B4 Used Parameters: Enabling threshold electro-valve differential electro-valve Inihibited Outputs: Economizer solenoid Valve, oil-cooler, liquid-injection Working Description…
-
Regulation on water/water units chiller only
Used inputs : • Evaporator Inlet Temperature • Evaporator Outlet Temperature • Condenser Inlet Temperature • Condenser Outlet Temperature Used Outputs • Compressors • Digital Output n°6 for solenoid 1 • Digital Output n°7 for solenoid 2 Used Parameters: • Unit type Special features of working: 1.…
-
Water pressure control for PFS units
Used Inputs: • • Used Parameters: • • Used Outputs: • • • condenser inlet water temperature evaporator inlet water temperature. Setpoint of First Opening in Cold Start Setpoint of High Discharge Superheat Driver EXV8 Valve Compressor Output Liquid injection solenoid Cold Start (WPC) Pre-Start Cold…
-
discharge temperature will keep in going up, controller will stop at 95°C in alarm the corresponding compressor. If otherwise temperature will go down, the controller will disable the liquid injection when that temperature will be lower than the setpoint minus the selected differential. On working…
-
Control Logic of the cooling tower for PFS
PFS with single compressor: Used Inputs • Used Parameters • • • Used Outputs • • • Condenser inlet water Temperature Setpoint Insertion Tower Steps Insertion Differential Number of Available Tower Steps First Step Cooling Tower OD12 Second Step Cooling Tower OD13 Third Step Cooling Tower OD08…
-
PFS with two Compressors
Used Inputs • Used Parameters • • • Used Outputs • • • Condenser inlet water Temperature Setpoint Insertion Tower Steps Insertion Differential Number of Available Tower Steps First Step Cooling Tower OD12 Second Step Cooling Tower OD13 Third Step Cooling Tower OD08 Units with two compressors install…
-
ALARMS
General description The alarms will be divided into three categories : • Only signalling alarms (only display and buzzer signalling, signalling on display, buzzer, alarm relay) • Circuit alarms (deactivate only the relative circuit, signalling on display, buzzer, alarm relay) • Serious alarm…
-
Alarm table
Code Alarm Description Compressor Off Fan Off Pump Off System Off Reset (auto/man) Delay Enabling AL01 CHILLER Severe alarm * * * * man no AL02 Antifreeze alarm * * * no AL03 AL04 AL05 Evaporator pump thermal Condenser pump thermal Evaporator flow control * * * * * * man or auto. (default is…
-
Driver alarms
The alarms coming from the driver cards also report the indication of the driver that has generated the alarm (in the example : “D:3”) Example: m_Drv_AL60 +--------------------+ ¦AL:066 D:3 U:2¦ ¦ Superheat alarm ¦ ¦ ¦ ¦ ¦ +--------------------+ When an alarm mask appears relative to the driver…
-
pLAN network
All the devices connected to the pLAN network are identified through their own address. If the same address is assigned to several units, the network can not operate. Since terminals and MicroTech II I/O cards utilise the same type of addressing, terminals and MicroTech II cards with the same…
-
Terminal address
Terminal card viewed from behind Microprocessore On Off Dip-switch Conn. Conn. stampante rete locale The address of the terminals is set up through the dipswitch bench found on the back . The address is selectable in the 1-16 range by utilising the 1-5 dipswitch. The address value is obtained via…
-
The number and type of terminals is established during the initial network configuration. The relevant data are stored in the EEPROM memory of each single I/O card. Terminal configuration procedure • The first operation to be performed, when for the fist time a pLAN network is to be started or an…
-
MicroTech II Control To leave the configuration procedure and store, select the 'Ok ? no' field and with the cursor buttons until 'Yes' appears and then press Enter. To get out without storing, it is necessary to wait for 30 sec without pressing any button. Display of the terminal connection state •…
-
Release 1.0 01/05/01
MicroTech II Control page 31/31