Electronic control for refrigeration applications USER MANUAL LEGGI E CONSERVA QUESTE ISTRUZIONI READ AND SAVE THESE INSTRUCTIONS NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! MPXone +0300086EN - ENG Up to date version available on www.carel.com
-
GENERAL WARNINGS
! CAREL bases the development of its products on decades of experience in HVAC/R, on continuous investments in technological innovations to products, procedures and strict quality processes with in-circuit and functional testing on 100% of its products, and on the most innovative production…
-
IMPORTANT
NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! Separate as much as possible the probe and digital input cables from cables to inductive loads and power cables, so as to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel cables) and…
-
Index
1. INTRODUCTION 1.1 Functions and main features 1.2 Models and accessories 2. INSTALLATION 2.1 Warnings 2.2 Panel version 2.3 DIN rail version 2.4 Description of the terminals 2.5 Probe connection 2.6 Connection diagrams 2.7 Positioning inside the panel 2.8 Electrical installation 2.9 Serial port…
-
1. Introduction
MPXone is an electronic controller for centralised commercial refrigeration applications in which a group of showcases needs to operate in a coordinated manner. The user terminal allows wireless connectivity with mobile devices and is built- in on the panel mounted models, or sold separately on DIN…
-
Models and accessories advanced superheat control with low superheat (LowSH), low/high evaporation temperature (LOP/MOP) and low suction temperature (LSA) protection. The single-pack versions come with connector kits, while the multiple pack versions are supplied without connectors. The table below…
-
P/N
Description AX3000PS2003(0/1)(*) User terminal, NFC+BLE, 4 buttons, buzzer AX3000PS20X1(0/1)(*) Remote display ACS00CB000020 User terminal cable - 1.5 m long ACS00CB000010 User terminal cable - 3 m long (0/1)(*): single/multiple pack (20 pcs.) Tab.1.b Cable and connector kit Controllers in multiple…
-
EEV
Electronic expansion valve (with external driver only) SV Solenoid valve Sm Outlet probe (air off) Sr Intake probe (air on) Sd Defrost probe E Evaporator Fig.1.d 1.2.2 Pressure sensors If using an external valve driver (EVDice/mini), to measure the saturated evaporation pressure/temperature…
-
Fig.1.f
P/N Description EVDM000N00 EVD MINI 24V without display EVDM010N00 EVD MINI 115/230V without display EVDM011R3* EVD ice 115/230 V, E2V stator, display EVDM011R1* EVD ice 115/230 V, E2V stator, display, Ultracap module connector EVDM011R4* EVD ice 115/230 V, E3V stator, display EVDM011R2* EVD ice…
-
2. Installation
2.1 Warnings 2.2 Panel version Important: avoid installing the controller in environments with the following characteristics: l temperature and humidity that do not comply with the ambient operating conditions (see "Technical specifications"); l strong vibrations or knocks; l exposure to water…
-
2.2.2 Assembly
Important: before carrying out any maintenance, disconnect the controller from the power supply by moving the main system switch to “off”. Fig.2.c 1. Place the controller in the opening, pressing lightly on the side anchoring tabs. 2. Then press on the front until fully inserted (the side tabs will…
-
DIN rail version 2.3.1 Dimensions – mm(in) Fig.2.e 2.3.2 Assembly Apply slight pressure to the controller resting on the DIN rail until the rear tab clicks into place. 2.3.3 Removal Use a screwdriver as a lever in the hole to lift and release the tab. The tab is held in the locked position by return…
-
Fig.2.h
Ref. J1 J2 J3 J4 J5 J6 J7 J8 Description L N 5V S3 S1 Y1 ID1 O S5 S2 Y2 ID2 ID3 ID5 +V S6 VL ID4 O S4 + O + O C NO1 NO2 NO3 C NO4 - Power supply Ratiometric probe power supply Analogue input 3 Analogue input 1 Analogue output 1 Digital input 1 GND: reference for probes, digital inputs and analogue…
-
Possible connections
Note: O = GND Fig.2.k 2.6 Connection diagrams 16 | 2. Installation Note: the “APPLICA” application can be used to change the configuration of the probes without needing to rewire or change the functions of the relays, thus taking advantage of different capacities when needed. MPXone +0300086EN rel.…
-
2.6.1 Panel model
-
2.6.2 DIN rail model
Fig.2.m 2.7 Positioning inside the panel 18 | 2. Installation The position of the controller in the electrical cabinet must be chosen so as to guarantee correct physical separation from the power components (solenoids, contactors, actuators, inverters, ...) and the connected cables. Proximity to…
-
Electrical installation 2.9 Serial port connections Important: When laying the wiring, "physically" separate the power part from the control part. The proximity of these two sets of wires will, in most cases, cause problems of induced disturbance or, over time, malfunctions or damage to the…
-
Master/Slave Network
Fig.2.n Master/Slave network and valve driver Important: only the Medium models manage the external electronic valve driver. Fig.2.o 2.10 Functional diagrams MPXone can control multiple refrigeration units (for example, one or more multiplexed showcases). These systems are made up of stand- alone…
-
DIN
Fig.2.q Master/Slave network with user terminals, remote display and external driver. The Master controller, connected to the supervisor network, coordinates the operation of up to 9 Slave controllers connected to the network via RS485 Fieldbus. Each controller can be connected to a remote display…
-
DIN
Fig.2.s RS485 supervisor network Note: on the master, parameter H3 must be set based on the protocol used by the supervisory system (Modbus/Carel). On the slaves, parameter H3 should always be left at the default value (1=Modbus). Fig.2.t 22 | 2. Installation Fig.2.u MPXone +0300086EN rel. 2.0…
-
Installation For installation proceed as follows, with reference to the wiring diagrams: l before performing any operations on the control board, disconnect the main power supply by turning the main switch in the electrical panel OFF; l avoid touching the control board, as electrostatic discharges…
-
Procedure for setting the default parameters/loading the parameter set
Set 0, called the working set, contains the set of parameters used by MPXone during normal operation. This set is loaded whenever MPXone is started, and the parameters can be modified at any time from the terminal, supervisor, APPLICA app and configuration software. The other two sets of parameters…
-
3. User interface
3.1 Introduction The front panel of the user terminal includes the display and the keypad, featuring four buttons that, pressed alone or in combination, are used to program the controller. The remote display is only used to show the values of a selected system variable and any alarms. The user…
-
User terminal and remote display The display shows measurements in the range –50 and +150°C, according to the type of probe used. For 0 to 5 V ratiometric and active 0 to 10 V or 4 to 20 mA probes the unit of measure is defined by the type of probe used. The decimal point can be disabled by setting…
-
3.2.1 Keypad
Keypad Increase/decrease the value Scroll direct access functions l LED on: scroll menu, parameters, direct access functions UP DOWN l LED flashing: set parameter values Pressed briefly: l Enter direct access function menu (from main screen) and activate/deactivate functions l Save value and return…
-
Pressing PRG on the main screen for 3 s and entering the password 33 accesses programming mode; see
the menu descriptions for details of the available items. Note: (*) for possible optimisations, use the APPLICA app. Parameter categories visible on the user terminal VIS (Display) Sm Sd Sr SH Sa Sv Svt PPU tGS tEu PEu ESC CtL (Control)/ Analogue inputs On St rd /p1 /FA /Fb /Fc ESC DEF (Defrost) ALM…
-
categories
other parameters PRG; or b) press PRG for 3 s Note: if no button is pressed, after around 1 minute the terminal will automatically return to the standard display. Mobile device and PC The Applica app and SPARK software can be used to configure the controller from a mobile device (smartphone…
-
4. Initial configuration
Once the electrical connections have been completed (see “Installation”) and the power supply has been connected, the operations required for commissioning the controller depend on the type of interface used, however essentially involve setting the so-called initial configuration parameters. The…
-
Fig.4.a
Commissioning parameters Par. In Sn H0 H3 /P1 P1 PH /P2 /P3 /Fd /FE /UE /LE End Desc. Type of unit Number of slaves in the local network (*) Serial or Master/Slave network address BMS serial port protocol Type of probe, group 1 (S1, S2, S3) Electronic valve Refrigerant (**) Type of probe, group 2…
-
Description
Def Min Max UOM User Sn No. of slaves in the local network 0 = no Slaves - S User terminal YES H0: Serial or Master/Slave network address On a Master controller this represents the address of the controller in the CAREL or Modbus supervisor network. The address of Slave controllers must comply with…
-
Fig.4.b
Note: MPXone is compatible with Carel and Modbus® supervisor networks. The type of protocol is set via parameter H3 H3: BMS serial protocol MPXone is compatible with Carel and Modbus supervisor networks, which can be selected using parameter H3. Note: on the master, parameter H3 must be set based on…
-
Description
-
This is used to assign the type of probe connected to input S6. Code Description Def Min Max UOM User /P3 Type of probe, group 3 (S6) 0 = PT1000 Standard Range –50T150 °C 1 = NTC Standard Range –50T90°C 2 = 0-5 V 3 = 4-20mA 4 = 0-10V - S User terminal NO /Fd: Assign tGS (superheated gas temperature…
-
4.4 Checks after
commissioning 36 | 4. Initial configuration Once having completed the installation, configuration and programming operations, after commissioning the controller check that: l the programming logic is suitable to control the unit and the system in question; l the time has been set on the controller…
-
5. Functions
If the settings made during commissioning are not sufficient to achieve the desired operation, further (detailed) configuration of the parameters can be performed, as described in the following paragraphs. The parameters described below can be configured via the configuration software or the…
-
Superheated gas temperature (tGS)
Saturated evaporation pressure/temperature (PEu/tEu) Defrost probe 2 (Sd2) /Fd /FE /FF Room humidity Glass temperature Dewpoint /FL /FM /Fn MPXone can adjust the values read by the probes. In particular /cA, /cb.../cn are used to increase or decrease the physical values read by the probes. Parameter…
-
Fig.5.a
MPXone, inside the showcase or cold room, can use temperature probes to measure: l the air outlet (off) temperature (at the evaporator outlet); l the defrost temperature (in contact with the coldest point of the evaporator); l the air return (on) temperature (at the evaporator inlet). The default…
-
Slave controller serving the Master, even in the continuous cycle, manages the user interface as if it were in normal control (solenoid/compressor icon on during cooling request and off when no request). Attempts to activate continuous cycle on a Slave serving the Master are ignored, both local and…
-
To associate a physical or virtual input to each available function, set parameters DIA, DIb, DIr parameters to the value relating to the physical or virtual digital input. See the parameter table. Digital input functions Digital input assignment for: immediate external alarm delayed external alarm…
-
message ‘IA’ shown on the display and ALARM flashing;
activation of the buzzer (see par. H8); activation of the alarm relay (see par. DOb); deactivation of the solenoid/compressor output (see par. A10). Nota: activation of the external alarm shuts down the evaporator fans only if these follow the status of the compressor output, as set for parameter…
-
Description
Def Min Max UOM User DId Assign start defrost digital input - see DIA Defrost delay on power-up or (for Slave) after control from Master 0 = delay disabled 0 -1 5 - S User terminal NO min S NO d5 Door switch with stopping control (par. DIE) Door open: l stop control (solenoid/compressor and…
-
when control resumes, the compressor times are observed (see the paragraph “Compressor”);
if the door remains open for longer than the value of par. Add, control resumes in any case. The light remains on, the measurement shown on the display flashes, the buzzer and the alarm relay are activated, and the temperature alarms are enabled with delay Ad. Remote ON/OFF (par. DIF) When the…
-
Description
Def Min Max UOM User DIG Assign curtain switch digital input - see DIA 0 -1 5 - S User terminal NO Digital input monitoring (par. DII) The supervisor is able to detect the status of the digital input. The value depends on the possible reversing the input logic using parameter rII. Code DII rII…
-
DIM
Stt Description Assign Standby mode switch digital input see DIA Maximum time for Standby status User terminal Def Min Max UOM User 0 -1 5 - S NO min S NO Switch to Clean status (par. DIn) Clean status is an intermediate state between ON and OFF: control is interrupted, the expansion valve is closed…
-
Start/stop defrost from digital input (par. DIr)
If configured in this new mode, a digital input can be used to start a defrost when closing and end the defrost when opening (independently of par. d0). If the defrost ends after the maximum time (par. dP1), alarm Ed1 is activated, if enabled (r3 = 1). Code DIr dP1 r3 Description Assign defrost…
-
Anti-sweat heater
DOQ - If the opposite logic to the default setting is required, or to correct a wiring error, the logic of the functions associated with the digital outputs using parameters rOA, rOb, rOp can be reversed. Code Description Digital output logic 0/1 = direct /reverse rOA, rOb, rOP Def Min Max 0 0 UOM…
-
Light (par. DOE)
The actuator can be activated/deactivated directly using the functions on the user terminal, using a command from the supervisor and based on the changeover in day/night status (linked to the curtain/door switch or the setting of the time bands); activation/deactivation of the actuator is signalled…
-
MPXone can manage defrosts with one or two outputs and one or two end defrost probes. The table
below summarises the possible cases: Defrost outputs 1 2 Evaporator probes Code /Fb /FF DOG DOH Control normal defrost managed on two outputs with reference to the same evaporator probe defrost managed on the same output with reference to the two evaporator probes (minimum evaporation temperature)…
-
Introduction
5.2 Control There are various modes for controlling air temperature for the preservation of foodstuffs in cold rooms and showcases. The following figure shows the position of the intake probe (air on) Sr and the outlet probe (air off) Sm. The virtual probe Sv is a weighted average of these two…
-
These values determine the control request and consequently, allowing for the protection times,
disabling functions or activation/deactivation delays, the opening/closing of the solenoid valve. Code Description Def Min Max UOM User St rd Set point Differential Operating mode 0/1 = Direct/Reverse 50 2 r1 0.1 r2 99.9 °C/°F °C/°F U U User terminal YES YES - U NO rC Note: HACCP: the set point and…
-
Description
Def Min Max UOM User r4 Automatic night set point variation Probe for night-time control 0/1 = virtual probe Sv/air on probe Sr Start time band 1 to 8 day: day - see (td1...8-d) Start time band 1 to 8 day: hours Start time band 1 to 8 day: minutes End time band 1 to 8 day: day - see (td1...8-d) End…
-
Fig.5.h
Ref. T t Sr Description temperature time intake probe (air on) Ref. Sv Sm Description Virtual probe Outlet probe (air off) Shared network solenoid If using solenoid valves, on Master controllers only the solenoid output (DOA) can be configured as a network solenoid output. The function is useful for…
-
Fig.5.i
Ref. E SV EEV Description Forced-air evaporator Solenoid valve Electronic expansion valve Ref. P T Description Evaporation pressure (PEu) Superheated gas temperature (tGS) ON/OFF (par. ON Parameter ON is used to switch the controller ON/OFF. If there is a digital input configured as remote ON/OFF…
-
St2
rd2 db1 Description Air on probe set point with double thermostat Set point St2 differential with double thermostat 0.0 = function disabled Double thermostat function logic 0/1: AND logic/OR logic User terminal Def Min Max UOM User 50 r1 r2 °C/°F S NO 0 0 99.9 °C/°F S NO M NO - The control request…
-
Fig.5.l
Ref. Sm Sr T Description outlet probe (air off) intake probe (air on) temperature Ref. Sv t Description Virtual probe time Daytime status: Sm = -21 to -23°C, St = -22°C Night-time status: Sm = -19 to -21°C, St = -22°C Sr = - 12 to -14°C, St = -16°C Sr = - 17 to -15°C, St = -16°C Fig.5.m Fig.5.n Ref.…
-
MPXone in standard mode uses the virtual probe Sv for control, that is, the weighted average of the
outlet and intake probe (see parameter /4). If one of the two probes making up the virtual probe is broken or has an error, parameter ro is used to continue normal control in controlled conditions, without the need for immediate intervention by maintenance personnel. The recommended value of ro is…
-
Fig.5.o
Ref. R c4 Description Control ON time Ref. t Description Time With duty setting active, during the ON time the solenoid/compressor icon remains on, while it flashes during the OFF time. The table below describes the possible fault situations relating to the control probes and the function that is…
-
The continuous cycle is activated using the direct continuous cycle function on the user terminal (see the paragraph "Direct functions"), from the supervisor or via digital input. When the continuous cycle is running: the + icons are displayed. the solenoid/compressor valve output (with icon) and…
-
Introduction
5.3 Defrost Parameters td1 to td8 can be used to set up to 8 defrost events based on the controller clock (RTC) and to activate the Power Defrost (see the end of the paragraph). To set parameters td1 to td8, use the supervisor or the "Applica" app. Code td1..8-d td1..8-hh td1..8-mm td1..8-P…
-
Fig.5.p
Ref. t dt1 dP1 Description Time End defrost temperature Maximum defrost duration Ref. Sd DEF Description Defrost probe Defrost The heater defrost by time with temperature control (d0=4) activates the defrost output only if the evaporator temperature (Sd) is less than the value of parameter dt1, and…
-
During the dripping phase the fan is always off, while during the post- dripping phase operation
depends on the setting of parameter Fpd. Code dd dH1 F2 F3 Fd cP1 Pdd dSb Description User terminal Def Min Max UOM User min S NO s M NO - S YES - S F3 min S NO % M NO min S NO % M NO Dripping time after defrost (fans off) 0 = no dripping Pump down phase duration 0 = pump down disabled Evaporator…
-
Description
td1…td3 Scheduled defrosts Staggered defrosts The function is used to perform a series of daily defrosts by setting just the first using parameter td1 and then indicating the number of defrosts per day using parameter d1S. The controller automatically schedules all the defrosts to be performed at…
-
Start/end defrost synchronised by Master (par. d2, d3)
Code d2 d3 Description End defrost synchronised by Master 0/1 = not synchronised/synchronised Send start network defrost signal (for Master) 0/1: yes/no Ignore start network defrost signal (for Slave) 0/1: no/yes User terminal Def Min Max UOM User - S NO - S NO These parameters determine whether or…
-
Dripping time after defrost (par. dd)
Code Description Def Min Max UOM User dd Dripping time after defrost (fans off) 0 = no dripping min S User terminal NO This parameter is used to stop the compressor and the evaporator fans following a defrost so as to allow the evaporator to drip. The value of the parameter indicates the off time in…
-
d10
d11 Description Defrost time in Running time mode 0 = function disabled Defrost temperature threshold in Running time mode User terminal Def Min Max UOM User min S NO -30 -50 50 °C/°F S NO Fig.5.s Ref. Sd DEF Description Defrost probe Defrost Ref. t Description time Pressure probe alarm management…
-
2. ONTIME is reset (instant A): OFFTIME iis reset with the default value and the natural defrost starts, lasting the entire time dS1. At the end of the defrost (instant B), OFFTIME and ONTIME are reset with the values dS1 and dS2 and control resumes. Fig.5.t Ref. CMP t Description Compressor time…
-
Power defrost (par. ddt, ddP)
Power defrost is used to increase the end defrost threshold dt1 (dt2 for the second evaporator) and/or the maximum defrost duration dP1 (dP2 for the second evaporator). These increases allow more effective defrosts. Power defrosts are performed on each defrost call during night status or when…
-
Description
Def Min Max UOM User FSb 9: Ambient (SA) 10: Ambient humidity (SU) 11: Glass temperature (Svt) 12: Dew point (SdP) 13: Virtual probe (Sv) 14: Saturated evaporation temperature (tEu) Second fan control probe - see FSa - M User terminal NO Fig.5.u Ref. Sa Sb F1 Description Probe set by parameter FSa…
-
If using the fan speed controller, F5 represents the temperature below which the fans are activated
There is a fixed hysteresis of 1°C for deactivation. Code Description Def Min Max UOM User F5 Evap. fan cut-off temperature (hyst. 1°C) 50 F1 50 °C/°F S User terminal NO Fig.5.v Ref. Sa Sb F5 F1 Description Probe set by parameter FSa Probe set by parameter FSb Fan cut-off temperature Fan activation…
-
T
F1 Frd 5.5 Anti-sweat heater or fan modulation Description temperature Fan activation threshold Differential Ref. F5 F6 F7 Description Fan cut-off temperature Maximum speed Minimum speed The control of anti- sweat heaters is performed by comparing the dew point calculated based on the ambient…
-
Description
Def Min Max UOM User rHo rHd Offset for anti-sweat modulation Differential for anti-sweat heater modulation 2 0 -20 20 °C/°F 0 20 °C/°F S S User terminal NO NO If one of the probes is not available (SA or either Sm or Sr), only fixed activation control will be possible, according to parameters rHu…
-
Fig.5.y
Ref. A B rHu 5.6 Electronic valve Description Relay output 0-10 Vdc output Manual anti- sweat percentage heater activation Ref. rHt t Description Manual anti-sweat heater activation period Time Introduction MPXone manages an electronic expansion valve using an external driver connected to the…
-
SH = tGS - tEu
MPXone Medium manages the proportional opening of the electronic expansion valve, adjusting the flow of refrigerant in the evaporator, so as to maintain the superheat around the value set for advanced parameter P3 (superheat set point). The opening of the valve is controlled independently of normal…
-
The parameter that electronic valve control is based on is superheat, which effectively tells whether or not there is liquid at the evaporator outlet. Superheat is calculated as the difference between: superheated gas temperature (measured by a temperature sensor located at the end of the outlet…
-
Initial valve position when control starts (parameter cP1)
This is used to set the position of the valve as a percentage when control starts. High values ensure intense and immediate cooling of the evaporator when each request is sent, however may cause problems if the valve is oversized with reference to the unit’s cooling capacity. Low values, on the…
-
the other control factors, and is valid in both normal control and with all emergency control functions. High values ==> fast and reactive valve (e.g. 20 for CO2 - carbon dioxide applications). Low values ==> slow and less reactive valve. P5: this represents the time required by the controller to…
-
5.6.1 Protection functions
LowSH: low superheat threshold (par. P7) To prevent too low superheat values that may cause the return of liquid to the compressor or system instability (swings), a low superheat threshold can be defined, below which a special protection function is activated. The LowSH threshold must be lower than…
-
critical conditions have ended, the controller temporarily operates with a higher superheat set point until the function is automatically reset. Important: if this action causes the complete closing of the electronic valve, the solenoid valve is also closed, even if this is a network solenoid valve…
-
LSA - Low suction temperature
When the suction temperature falls below the threshold, the alarm is activated after the set delay, closing the electronic valve and the local or network solenoid valve (if parameter P10 = 1). The alarm is reset when the suction temperature exceeds the set threshold plus the hysteresis. Code P10 P11…
-
LOP Minimum evaporation pressure
This function is useful above all for stand- alone refrigeration units, used to prevent the evaporation pressure from remaining excessively low for too long. When the evaporation pressure, expressed in degrees (saturated), falls below the threshold, the LOP protection is activated, which adds an…
-
PMP
PMu Description Enable manual expansion valve positioning 0/1 = disabled/enabled Manual valve position Def Min Max UOM User - 0 600 steps - User terminal S NO S NO PMP is used to enable/disable manual positioning of the valve. l PMP = 0: manual positioning disabled; l PMP = 1: manual positioning…
-
d9 disables the compressor protection times when defrosting
l d9 = 0: protection times are observed; l d9 = 1: protection times are ignored, defrosting has higher priority. Fig.5.af Ref. t 5.8 Generic functions Description Time Ref. CMP Description Compressor MPXone can exploit unused inputs and outputs to configure a "generic function". Each generic…
-
Assign control probe
Select the control probes for the generic function. Code GFS_1 GFS_2 GFM_1 GFM_2 GFA_1 GFA_2 Description User terminal Def Min Max UOM User - S NO - S NO - S NO - S NO - S NO - S NO On/Off generic function: control probe 1 0: Not configured 1: Outlet temperature (Sm) 2: Defrost temperature (Sd) 3…
-
Fig.5.ag
Fig.5.ah Ref. Description Set Set point Diff Differential Sreg1 - Sreg2 Control probe1 - Control probe 2 OUT Digital output 5.8.3 Modulating output Assign the modulating output for the generic function and the type (direct/reverse). It is possible to use proportional control only or PID, as well as…
-
Fig.5.ai
Ref. Description Set Set point Diff Differential H Hysteresis Sreg1 - Sreg2 Control probe1 - Control probe 2 OUT Digital output CutOff_Diff Cut-off differential 5.8.4 Alarm signal The alarm can be signalled for two reasons: 1. switching of the digital input, assigned by parameter DIs: the display…
-
Fig.5.aj
Ref. Lth HTh diff Del t Sreg1 - Sreg2 GHI GLO Description Low temperature threshold High temperature threshold Differential Delay Time Control probe1 - Control probe 2 High temperature alarm message Low temperature alarm message Example Display of the generic alarm when exceeding the thresholds. 88…
-
6. Parameter table
Below is the table of the parameters that can be displayed on the terminal or can be modified using the commissioning software or APPLICA app. The APPLICA app and commissioning tools for MPXone feature three predefined parameter access levels: User (U), Service (S) and Manufacturer (M). The default…
-
Description
/LL Minimum value for ambient humidity probe (SU) /2 Analogue probe measurement stability Digital inputs Assign immediate external alarm digital input DIA 0 = Function disabled 1 = digital input 1 (ID1) 2 = digital input 2 (ID2) 3 = digital input 3 (ID3) 4 = digital input 4 (ID4) 5 = digital input 5…
-
Description
UOM User User terminal 4 - S NO - S S S S S S S M M M S NO NO NO NO NO NO NO NO NO NO NO - M NO - M M M S S S S S M M NO NO NO NO NO NO NO NO NO NO - S NO - M NO - M M M NO NO NO - S YES % S NO -50 50 0 -50 r1 -50 r2 200 50 °C/°F °C/°F °C/°F M M S NO NO NO - S NO °C/°F S NO - S YES 50 50 r1 r1 r2 r2…
-
Description
Def Min Max UOM User rd Differential Operating mode 0/1 = Direct/Reverse Set point St2 differential with double thermostat 0.0 = function disabled Virtual probe composition for glass temp. probe estimate 0 = Air off probe Sm 100 = Air on probe Sr Coeff. A for glass temp. probe estimate Coeff. B for…
-
d10
d11 d12 Description Defrost time in Running time mode 0 = function disabled Defrost temperature threshold in Running time mode Pressure probe alarm management during defrost probe error disabled enabled disabled enabled supervisor update enabled enabled disabled disabled Pump down phase duration 0 =…
-
Description
F6 F7 Max evaporator fan speed Min evaporator fan speed Evaporator fan peak time F8 0 = Function disabled Evaporator fan forcing time at max speed F10 0 = Function disabled First fan control probe 0: Not configured 1: Air off (Sm) 2: Defrost (Sd) 3: Air on (Sr) 4: Superheated gas (tGS) 5: Saturated…
-
таблицы и схемы — в просмотре
-
Description
8 = -1 to 12.8 barg 9 = 0 to 20.7 barg 10 = 1.86 to 43.0 barg 11 = Reserved Solenoid/compressor c0 Delay to enable solenoid/comp. and evap. fans on power-up c1 Min time between consecutive compressor starts c2 Min compressor OFF time c3 Min compressor ON time ON time for duty setting operation (Toff…
-
Description
UOM User User terminal 1 - S YES 0 199 - S YES - S YES - S YES - S YES - S YES - S NO - S YES - S NO - S NO - S NO - S NO - U NO - U NO Def Min Max = monitoring disabled Connectivity In H0 H1 H2 H3 Type of unit 0/1 = Slave/Master Serial or Master Slave network address BMS serial port config. (stop…
-
Description
Day/Night tS1..8-d Start time band 1 to 8 day: day - see (td1...8-d) tS1..8-hh Start time band 1 to 8 day: hours tS1..8-mm Start time band 1 to 8 day: minutes tE1..8-d End time band 1 to 8 day: day - see (td1...8-d) tE1..8-hh End time band 1 to 8 day: hours tE1..8-mm End time band 1 to 8 day…
-
GFM_2
GFM_T GFM_S GFM_D GFM_Kp GFM_Td GFM_Ti GFM_CD GFM_H GFM_Max GFM_Min /Ad GFA_E GFA_1 GFA_2 GFA_De GFA_D GFA_Hth GFA_Lth Description Modulating generic function: control probe 2 See GFS_1 Modulating generic function: type 0/1 = Direct/Reverse Modulating generic function: set point Generic modulating…
-
Fig.6.at
Note: during the first connection, the Applica app aligns itself with the software version on the MPXone controller via a cloud connection; this means a mobile data connection is needed at least for this first connection. If the data connection is not available, the required packet can be retrieved…
-
3. Select “Profiling”';
4. Select the variables to assign to the profile. These will only be the variables that are visible via the configuration/commissioning software and the Applica app to any M-level user who has the password for profile MyProfile1. 5. Now, selecting profile MyProfile1, the variables to assign to the…
-
7. Technical specifications
Panel Physical specifications Dimensions Case Assembly Ball pressure test temperature Ingress protection Front cleaning Environmental conditions Operating temperature Storage temperature Rated power supply panel IP20 rear IP00 IP65 front Use soft, non-abrasive cloth and neutral detergent or water…
-
Analogue
outputs Digital outputs Probes and terminal power supply Cable lengths Conformity Y1, Y2 NO1 (16A), NO2 (8A), NO3 (5A), NO4 (5A) Note: NO1+NO2+NO3 cannot exceed 15 A max Panel closing current, 6 mA typical open contact voltage 13 V contact resistance max 50 Ω. 0-10 V: 10 mA max PWM 100 Hz: max…
-
Connector/cable table Ref. Description J1 J2 J3 J4 J5 J6 J7 J8 Wiring terminals Wire crosssection (mm2) Lmax (m) Panel model: plug- in terminal, screw, 2- pin, 0.5-1.5 10 pitch 5.08 Controller power supply DIN rail model: plug-in terminal, screw, 2-pin, 1.5 10 pitch 5.08 Inputs S1, S2, S3, S5, ID1…
-
8. Alarms and signals
8.1 Signals The signals are messages shown on the display to notify the user of the control procedures in progress (e.g. defrost) or to confirm keypad input. P/N dEF Ed1 Ed2 OFF Act Stb CLn MSS Description Defrost running Defrost on evaporator 1 ended by timeout Defrost on evaporator 2 ended by…
-
A single alarm can be reset by pressing ALARM for more than 3 s. If the condition that generated the
alarm is still present, the alarm will be reactivated. The alarm log can be deleted via APPLICA on a smartphone, with BLE connection, using the specific function on the alarm page ("Service" level access is required). Note: deletion of the alarm log is irreversible. 8.3 Display alarm log The alarm…
-
Display
Description code dor Etc LSH LSA MOP LOP bLo Edc dA1 dA2 Display Alarm icon Buzzer Reset relay flashing from external contact Door open for too long Real time clock not updated Low superheat Low suction temperature Maximum evaporation pressure Low evaporation temperature Valve blocked Communication…
-
Assign probe for high and low temperature alarms (parameters AA, AA2)
8.5 Alarm parameters AA selects the probe to be used for measuring the high and low temperature alarms with reference to thresholds AL and AH. AA2 is the same as AA for thresholds AL2 and AH2. Code AA AA2 Description Assign probe for high (AH) and low (AL) temperature alarms 0: Not configured 1: Air…
-
A11
AL AH AL2 AH2 Ad Ad2 Description 100 = always ON Delay time for delayed external alarm 0 = Signal-only alarm Low temp. alarm threshold High temp. alarm threshold Low temp. alarm 2 threshold High temp. alarm 2 threshold Delay time for high and low temp. alarms (AH, AL) Delay time for high and low…
-
Slave with the alarm (x=1 to 9). If parameter DOb is set on the Master (value other than zero), then the master alarm relay is also activated. 8.6 HACCP alarms Code Description Def Min Max UOM User Ar Signal alarms from Slave to Master 0/1 = not enabled/enabled - S User terminal NO (HACCP = Hazard…
-
S
St AH ALARM Ref. Description Measurement probe Set point High temperature alarm threshold Type HA HACCP alarm Ad Htd t Description Delay time for high and low temperature alarms HACCP alarm delay - 0 = monitoring disabled Time Code Description Def Min Max UOM Ht0 (*) HAn (*) HACCP alarms present…
-
9. Release notes
Software version 1.1 23/08/2018 ≥ 1,2 31/10/2018 Manual version 1.0 04/09/2018 2.0 15/10/2019 Description First release Second release: generic functions Tab.9.a MPXone +0300086EN rel. 2.0 – 15.10.2019 9. Release notes | 113
-