Инструкция на Rooftops (крышные кондиционеры) Lennox серии GS..., WS...
Rooftops (крышные кондиционеры) Lennox серии GS 16 Е. Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
NX
LENNOX instructions NOTE: To comply with current regulations Gas Fired Warm Air Heaters must be installed and serviced by CORGI registered personnel. и PART No. P - 8 - 67392
-
DIMENSIONS (тт) Recommended flashing for
-
1.0 Shipping and packing list
Package contains 1. Assembled unit 1. Vent cap package shipped in vestibule area. 2.0 Shipping damage Check unit for shipping damage. The receiving party should contact the last carrier immediately if shipping damage is found. 3.0 General These instructions are intended as a general guide and do not…
-
Horizontal discharge applications
Specified installation clearances must be maintained when mounting GS16E units. Refer to Fig 1. Top of the support slab should be at least 100 mm above the finished ground level and located so no run-off water from higher ground can collect around the unit. Horizontal discharge kit LB.55756BA for…
-
9.0 Connecting gas piping
Before connecting gas piping, check with gas region or authorities having jurisdiction for local code requirements. When installing gas supply piping, the length of run from the gas meter must be considered in determining pipe size for 1.25 mbar (0.5 in wg) maximum pressure drop. Do not use a supply…
-
11.0 Electrical connections - power
supply Do not apply power or close isolator switch until installation is complete refer to start-up directions. Refer closely to unit wiring diagram. Refer to unit nameplate for minimum circuit amperage. All units are factory wired for 380/420V 3-phase, 50 Hz supply. See Fig.8 (Wiring Diagrams). The…
-
Fan operation and adjustments
Fan operation Fan operation is manually set at the thermostat sub-base fan switch. With fan switch in ON position, fans will operate continuously. With fan switch in AUTO position, the fan will cycle with demand. Fans and the entire unit, will be off when the system switch is in the OFF position.…
-
TO INCREASE AIR FLOW
LOOSEN ALLEN SCREW & TURN PULLEY CLOCKWISE DO DECREASE AIR FLOW TURN PULLEY COUNTER- CLOCKWISE PLATE MOTOR & PULLEY ae LOCKING BOLT, MOTOR MOUNTING TO INCREASE BELT TENSION 1- LOOSEN LOCKING BOLT. 2-PULL MOTOR MOUNTING PLATE, 3. TIGHTEN MOTOR MOUNTING PLATE $0 PLATE iS VERTI- CAL. BLOWER WHEEL Fig…
-
РАМ РЕКРОВМАМСЕ
-
Lubrication
Note Always lubricate motors according to manufacturers lubrication instructions on each motor. If no instructions are provided, use the following as a guide. Supply air fan in motor bearings Bearings are prelubricated. No further lubrication is required for 10 years of normal operation. Thereafter…
-
Flue passageway and flue box
Remove induced draught fan assembly as described in previous section. Remove flue collector cover and flue collector baffle. Clean with a wire brush as required. Pull tube baffles from heat exchanger and clean tubes with a wire brush. Reinsert tube baffles by gently bending them to lock tab against…
-
aseyd aad y р — peo} jin) ajOd с зшеш - 42014. ела Wal
-
16.0 GSI6E repair parts listing
When ordering parts, include the complete model number listed. eg. GSIGE-70-1M. Heat Section Heat exchanger Combustion air fan motor (B6) Combustion air fan wheel Burner assembly Combustion ат fan housing Burner manifold assembly Main burner orifices Ignition electrode assembly Ignition lead Sensor…
-
17. Parts descriptions 5. Supply air fan. А single beit
driven fan provides air supply through 1. Control Transformer M10 located the unit. An adjustable sheave is uged inside the control box is used to step оп the fan motor so that the m%/s down line voltage to 24 VAC to provide (cfm) rating can be adjusted. (see Fig. power to all the units controls and…
-
Burners are controlled by the spark
electrode, flame sensing electrode, gas valve СУ! and combustion air fan B6. The spark electrode, flame sensing electrode and gas valve СУ! are directly controlled by ignition control A3. Ignition control A3 and combustion air fan B6 are controlled by heating demand from the thermostat or control…
-
А "Fenwall" electronic direct spark
ignition with flame rectification sensing is used on all GSIG6E units. The "Fenwall" control is illustrated in figure 10. The 4 wire harness, plugged directly into the jack at the lower corner of the control, is used to connect the control to the unit. Each of the four jack terminals are identified…
-
SECONDS
END OF THERMOSTAT DEMAND 0 110 THERMOSTAT DEMAND INOUCED DRAFT BLOWER GAS VALVE & K25 IGNITION SPARK BLOWER B3 KZ Lies IGNITION TRIAL (ZA ом с NORMAL IGNITION SEQUENCE OFF TIMINGS NOMINAL FIGURE 11 SECONDS 6570 — 100105 135140 170175 THERMOSTAT DEMAND A, INDUCED DRAFT BLOWER ГА GAS VALVE & К25…
-
Gas valve (GV1) (Figures 14 & 15)
GSI16Es may have ваз valves manufactured by either 'Honeywell' or 'White-Rodgers'. The gas valve is twostage and internally redundant. Initial heat demand (WI) from the ignition control (АЗ} opens both operators of the gas valve. Both operators respond to stage 1 demand quickly. Increased heat…
-
Оп а temperature rise terminals 1-3
open to de-energise the ignition circuit and terminals 1-2 close to energise the fan. The limit is factory preset to “erip" at 65.5°C 3°C (150°F — 69Е) on a temperature rise and reset at 43°C 4°C (110°F 7°F) on a temperature fall. This is a safety shut-down function of the unit. Primary (lower)…
-
If flame is not sensed after first trial
for ignition, controller A3 repeats steps 6 through 10 up to two more times before locking out delay relay K25 waits 60 seconds. If the control locks out, it can be reset by breaking and remaking thermostat demand. 11. After 60 seconds delay, relay K25 normally open contacts close. 24 VAC power is…