CONTROL AND REGULATION
WITH CLIMATIC RTK RTK BASIS PROGRAM ROOFTOP Air conditioning unit Version anglaise
-
LIST OF CONTENTS
CLIMATIC control Page 2 Set points Page 5 Configuration Page 5 On-Off function Page 5 Stand by function Page 6 Regulation Page 7 Off loading autorisation Page 7 Compressor Page 8 Proportional load Page 9 Incident codes Page 9 Board links (J9) Page 12 RS-232 link to a (11) computer or B.M.S. Page 12…
-
CLIMATIC control
Characteristics. Outputs. Potential free all-or-nothing actuator Contact limits: AC: 10 A 25O V resistive load 4 A 250 V resistive load. With an inductive load, an RC (resistive capacitative) circuit must be installed on the terminals. Analogue output Supplies a voltage of 0 to 10 Volt dc. Inputs.…
-
Remark
A manual reset procedure requiring the user to press several keys simultaneously may be necessary to clear certain defaults. + - V To check the wiring to a board input, call up the address corresponding to the sensor or contact. Analysis of information : When the pointer points to an address between…
-
from variable nr 144 to variable nr 175 from variable nr 176 to variable nr 178 from variable nr 179 to variable nr 181 from variable nr 182 to variable nr 184 from variable nr 185 to variable nr 187 from variable nr 188 to variable nr 190 from variable nr 192 to variable nr 207 from variable nr 208…
-
SETPOINTS
Stpt. nr0 Stpt. nr1 Stpt. nr2 Stpt. nr3 Stpt. nr4 Stpt. nr5 Stpt. nr6 Stpt. nr7 Stpt. nr8 Stpt. nr9 Stpt. nr10 Stpt. nr11 Stpt. nr12 Stpt. nr13 Stpt. nr14 Stpt. nr15 CONSA MORTE T_VOLET T_CHAUD T_FROID MINIAIR DV_J FV_J DV_H FV_H P_ANTI FRIMAIR MA_AR_D INIT MODE_RT DING_A ENCL_F DIFET_F ENCL_C…
-
STANDBY (UNOCCUPIED) FUNCTION
CLIMATIC clock function If DV_J, setpoint n°08, has a value of 022 and FV_J, setpoint n°09, has a value of 006 then the daily unoccupied period will be activated every day at 22.00 hours until 6.00 hours the next morning. If DV_H, setpoint n°10, has a value of 207 and FV_H, setpoint n°11, has a…
-
Regulation
Setpoint for HEATING Setpoint for COOLING V3V 100% R2 R1 Damper G2 MINIAIR G1 ENCL_C G2 G1 DEADBAND ENCL_F DIFET_C CONSA T0/X0 T_AMB DIFET_F Offsetting the conditioned space temperature setpoint The required temperature for the conditioned space is adjustable with the CONSA setpoint (setpoint nr…
-
Full message display
If the ‘Local / Distance’ button [S5] is at ‘ON’ then If button [D2] is at ‘ON’ compressor operation is forced to 50%. If button [D3] is at ‘ON’ forces offloading of 100% of compressor operation. External contact Shunting terminals 216 (10 kΩ resistor in series with SP12 on CLIMATIC input X6) forces…
-
If the outdoor air temperature rises back above the +10°C and if the two conditions above were true for 1 minute, a forced defrost cycle is initiated. Proportional. The two proportional outputs are driven by all-or-nothing motors. The position of the outdoor air damper or the valve is transmitted to…
-
than 35°C
012 2nd safety level If the air discharge temperature is +60°C or greater, the safety thermostat is activated. This safety device resets itself automatically when the temperature drops back under 55°C. Incident code 012 is displayed, the general default contact is activated. Low air discharge…
-
The fire safety thermostat, the fan motor thermal protection device, and the electric heater
protection thermostats (Klixons) all act directly on the fan motor contactor. This information is transmitted to the CLIMATIC control by the contactors auxiliary contact. If the CLIMATIC control gives the command for fan operation and 5 seconds later, the auxiliary contact is still open, the fan…
-
Board links (J9)
Setpoint setback potentiometer If the inter-board link is used, a single control box with a potentiometer connected to the unit with CLIMATIC board nr 0 is sufficient, since the other units receive the setback value via the common information bus. Enthalpy function. If the inter-board link is used…
-
Table of J-BUS addresses
-
Write
CLIMATIC CONSA MORTE T_VOLET T_CHAUD T_FROID ENCL_F DIFET_F ENCL_C DIFET_C /C HE MN JS RAH /U DING MINIAIR DV_J FV_J DV_H FV_H P_ANTI ORDI /U /U GTC /U 220 MA_AR_D /U 206 /K /C /C /C /K /K /K /K /U /U /U /U /U /U /U /U /U CLIMATIC RTK – anglais J-BUS Required conditioned space temperature Deadband…
-
Read
-
Variables
-
246 IN22
247 IN23 MAXI_F MAXI_C U U Number of conditioned space cooling control stages Number of conditioned space heating control stages IN24 IN25 IN26 IN27 IN28 IN29 MODE_RT DING_A ENCL_F DIFET_F ENCL_C DIFET_C U U K K K K Configuration setpoint Integration time setpoint Cooling control cut-in threshold…
-
DISPLAY
LEGEND : 1 Green LED description leaflet, removable from the rear. 2 Keys D1 to D6, C1 to C5 & S1 to S5 description leaflet, removable from the rear. 3 Yellow « power on » LED 4 Eight green LEDs 5 Red default LED 6 Digital display CLIMATIC RTK – anglais Page 19
-
Alpha-digital display, describes the value displayed on the digital display. 8 CLIMATIC function keys, see page 2. 9 Buzzer clearing key, the buzzer is an option. 10 Language change, Two languages are available : French or English. 11 20 pin CLIMATIC connector on the rear. 12 Nine potential-free…
-
DEFINITION OF INCIDENT CODES
000 No defaults RT MA CAT ORD 001 Incorrect airflow RT MA ORD 004 Clogged filters RT MA ORD RT MA ORD RT MA ORD Airflow defaults PAN_DA Heating defaults PAN_C Electric heating coil default Discharge air overtemperature Return or room air under temperature Default on gas burner nr 1 Default on gas…
-
Temperature sensor default, return air or room air Humidity sensor default, return air RH Temperature sensor default, discharge air Temperature sensor default, outdoor air Temperature sensor default, chilled water Temperature sensor default, hot water RT MA ORD RT MA ORD RT MA ORD ORD ORD 089…
-