Инструкции на Чиллеры Clivet серии WSAT...
Чиллеры Clivet серии WSAT XEE 82-102-122-162-182-222-262-302 с водяным охлаждением для наружной установки. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
WSAT-XEE
82-102-122-162182-222-262-302 AIR COOLED WATER CHILLER FOR OUTDOOR INSTALLATION Installation and Use Manual M0G140F7-01 06/11/07
-
UNIT IDENTIFICATION
SERIAL NUMBER LABEL The units are identified by the serial number label shown here. The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer. The label is placed on the unit…
-
INSTRUCTIONS FOR THE USER
• This is a partial sintex of the information provided in the manual; carefully read this manual • Carefully read this manual. Keep it with the electrical diagram. Make it available to technicians for servicing. • Ask the installer for training on start-up, shutdown, changing set points, placing in…
-
ECO mode
-
M0G140F7-01
-
GENERAL WARNINGS
MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons…
-
RESIDUAL RISKS
GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DANGER AREA The figure below highlights the area in which only authorised personnel may operate. • External danger zone, identified by…
-
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by electrocution. When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign. MOVING PARTS Contact with the fan rotors can cause injury. Before…
-
Chemical -physical
properties. Relative density, gas (air=1) Heavier than air. Solubility in water (mg/l). Not known, but probably very low. Aspect. Colourless liquefied gas. Smell. Simile to ether. Point of ignition. Don’t ignite. Stability and reactivity. Stability and reactivity. No decomposition if used following…
-
RECEPTION
INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment…
-
POSITIONING
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
Tree Keep the coil clean. Avoid zones with leaves / dirt / corrosives. Consider clearances and direction of expelled air. Avoid snow build-up during winter operation ! 1. 2. floating floor 3. soundproofing Prevent the transmission of vibrations. Provide windbreaks in locations with strong winds.…
-
WATER CONNECTIONS
GENERAL Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield. INTERCEPTING…
-
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit. P 1. Charged system pressure switch 2. vent 3. pump 4. expansion tank 5. safety valve 6. flow switch 7. pressure switch / thermometer 9 8 F 10 8 P 8. filter 9. filling valve 10. antivibration…
-
ELECTRICAL CONNECTION
GENERAL The characteristics of the electrical lines and relevant components must be determined by SPECIALIZED PERSONNEL ABLE TO DESIGN ELECTRICAL INSTALLATIONS; moreover, the lines must be in conformity with professional procedures and the regulations in force. All electrical operations should be…
-
FUNCTIONAL CONNECTIONS
FOR ALL THE CONNECTIONS MAKE REFERENCE TO THE ELECTRICAL PANEL SUPPLIED WITH UNIT Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA) Few inputs must be activated by configuration parameters whose access is reserved to authorized assistance centres (in…
-
SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY
Optimises unit energy efficiency by automatically adjusting the set-point according to enthalpy or the outside temperature. Requires the external humidity probe or the outside temperature probe, which are optional for certain types of units and must be installed by the customer and enabled by…
-
- 12VAC
+5V gnd gnd + CN1 CN2 SERIALE TTL / RS485 SERIAL CONVERTER TTL/RS485 OPTIONAL - code PE2N0002 Plugged-in in the main module on the electric board (see lay in the wiring diagram). It is possible to connect up to 127 units with a single supervision system. The connection with a PC must use a RS485/232…
-
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS ELECTRICAL SYSTEM Before checking…
-
UNIT EQUIPPED WITH SCROLL COMPRESSORS The GENERAL TECHNICAL DATA table shows the type of compressor on the unit. The Scroll compressors have only one direction of rotation. In the event that the direction is reversed, the compressor will not be damaged, but its noisiness will increase and pumping…
-
CONTROL
M AT AR AL ST S ET In ONLY COOL units, the relative parameters are VISIBLE but NOT ACTIVE , for example the winter setpoint. U S The HEATING mode functions are active only on HEAT PUMP unit version . OPERING MODES Unit can be switched on and off by: remote or service keypad remote switch (see…
-
SET-POINT CORRECTIONS
The correction aim is to optimize the unit energetic efficiency. To do this the corrections modify the set point in a dynamic way in function of determined variables: for example in summer operating with low outside temperatures, so with a reduced charge, is possible to obtain the internal comfort…
-
AL AR M STB ST AT U S This way, the plant can be kept within the operating limits even when the unit is OFF or on STANDBY, for example during the weekend or the nighttime. Periodically the system activates the circulation pump, measures the water temperature and activates the compressor, if…
-
ACCESSIBLE PARAMETERS FROM REMOTE OR SERVICE KEYBOARD
num. Par. description 29 32 Value UM Summer secondary Set Point 10 °C Summer Set Point 5.7 °C 42 Summer Set Point Maintenance 20 °C 44 Enables Summer Maintenance 0 num 77 Antifreeze resistanceset point 4 °C 80 Antifreeze alarm 4 °C 4.5 °C 84 Limit of deactivation before reaching the antifreeze steps…
-
Visible status from remote keyboard or service keyboard
INDEX DESCRIPTION VALUE Outdoor Humidity Machine Clock - fed unit hours Working hours C1 Pickups C1 Working hours C2 Pickups C2 0-100% Num Num Num Num Num AS – t 2007 03 04 AS – b 2007 1 11 Keypad software Year of certification of the keyboard SW Month of certification of the keyboard SW Day of…
-
M The most recent alarm is visualized Use the arrow keys to visualize other alarms LA R 2 A flashing Alarm code Alarm unit hours opened alarm log short pressure ALARM M LA R A ST A TU S S ET To esc Short pressure ALARM To RESET LONG pressure ALARM S ET A LA R M 5 ST A TU S S E T A LA R M 3 S TA TU S…
-
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT . cleaning activities; otherwise, controls have to be performed by specialized technicians (INSPECTIONS). All equipment is subjected to wear…
-
MAINTENANCE INSPECTIONS
Foresee inspection assistance carried out by authorized centers or by qualified personnel. The inspections should be carried out at least: • - Every year for only the cooling units • - Every six months for the cooling and warming units The frequency, however, depends on the use: in the event of…
-
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING: • THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION • THE MODES OF DETECTING TEMPERATURE AND PRESSURE • THE RISKS RELEVANT TO THESE OPERATIONS The data of the tables allow the testing of the refrigerating…
-
Pg
-
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING AN ALARM, IDENTIFY…
-
COMPRESSOR PROTECTION
1. Identify the part on the wiring diagram 2. Loose electric contacts/terminals, leads broken 3. electrical windings interrupted 4. Vacuum power voltage below the limits 5. power contactors / contacts defective 6. start-up power voltage lower than the limits 7. electrical absorption high /…
-
CONVERSION TABLE FOR RESISTANCETEMPERATURE FOR TEMPERATURE PROBES NTC
To check the reliability of the probes in the event of alarm signals, the table below shows the relationship between the temperature and the resistancevalue in Ohms. Temperature °C -20,0 -19,5 -19,0 -18,5 -18,0 -17,5 -17,0 -16,5 -16,0 -15,5 -15,0 -14,5 -14,0 -13,5 -13,0 -12,5 -12,0 -11,5 -11,0 -10,5…
-
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT DISMANTLING AND DISPOSAL The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL. Before disconnecting the unit, the…
-
TECHNICAL DATA
SIZE Cooling Cooling capacity Comp. input power Total input power EER ESEER COMPRESSORS Compressor type No. of compressors Capacity control steps Std Refrigerant circuits Refrigerant charge (C1) INTERNAL EXCHANGER Type of exchanger No. Of exchangers Water flow-rate Pressure drop Useful pump…
-
OPERATING LIMITS (COOLING)
SIZE EXTERNAL EXCHANGER Max air intake temperature Max air intake temperature Min air intake temperature INTERNAL EXCHANGER Max air intake temperature Min. water supply temperature Min. water supply temperature °C °C °C °C °C °C 48,5 50,5 47 49 48,5 50,5 49 51 48,5 50,5 48,5 50,5 47,5 49,5 -10 23 5…
-
DIMENSIONS
Sizes 82-102-122 1209 - 13 151.5 9 - 14 9 - 13 1225 326.5 22.5 1703 1225 W1 W2 7 "G" P O 7 2 W4 W3 700 (14) 1 21.5 326.5 (15) 1 700 M (15) N (1) COMPRESSOR (2) FINNED EXCHANGER (3) HELICAL FANS (4) PLATE EXCHANGER (5) EXCHANGER WATER RETURN (6) EXCHANGER WATER SUPPLY (7) PUMP (8) POWER INPUT (9)…
-
Sizes 162-182-222
-
Sizes 262-302
-
CLIVET SPA
Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it CLIVET ESPAÑA S.A. Madrid - SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clivet-uk.co.uk CLIVET NEDERLAND B.V.…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Чиллеры Clivet серии WSAT-XSC 352-402-432-452-502-552-602 с водяным охлаждением. Инструкция по монтажу и эксплуатации.PDF · 1.04 Mb
- Чиллеры Clivet серии WSAT-SC 75C-90C-65D-70D-75D-80D-90D-100D-110D-120D-135F-150F-165F-180F с водяным охлаждением. Инструкция по монтажу и эксплуата…PDF · 1.58 Mb
- Чиллеры Clivet серии WSAT-ЕЕ 82-102-122-142-162-182-202-222-242-282 с водяным охлаждением для внешней установки. Инструкция по монтажу и эксплуатации.PDF · 1.13 Mb
- Чиллеры Clivet серии WSAT-ЕЕ 17-21-25-31-41-51-61-71-81-91 с водяным охлаждением для наружной установки. Инструкция по монтажу и эксплуатации.PDF · 1.14 Mb
- Чиллеры Clivet серии WSAT-ЕЕ 17-21-25-31-41-51-61-71-81-91-101-121-131-151 с водяным охлаждением для наружной установки. Инструкция по монтажу и экс…PDF · 787.18 Kb
- Чиллеры Clivet серии WSAT-XSC 65D-70D-75D-80D-85D-90D-100D-110D-115D-120D-135E-150F-165F-180 с водяным охлаждением. Инструкция по монтажу и эксплуат…PDF · 1.02 Mb
- Чиллеры Clivet серии WSAT XSC 200H-220H-230H-240H-270J-300L-315L-330L-345L-360L с водяным охлаждением. Инструкция по монтажу и эксплуатации.PDF · 1.01 Mb