Инструкция на Чиллеры Clivet серии WSAT...
Чиллеры Clivet серии WSAT-SC 75C-90C-65D-70D-75D-80D-90D-100D-110D-120D-135F-150F-165F-180F с водяным охлаждением. Инструкция по монтажу и эксплуатации.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
AIR-COOLED WATER CHILLERS RATED FROM 190 TO 450 KW
-
- GENERAL - GENERAL WARNINGS MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether…
-
WSAT-SC 75C-180F TECHNICAL CHARACTERISTICS OF STANDARD UNITS COMPRESSOR Scroll compressor complete with: overload thermal protection, high refrigerant discharge temperature, rubber antivibration mounts, oil charge, acoustic and weather proof cabinet. A oil heater is automatically switched on at the…
-
ACCESSORIES - copper / aluminium condenser coils with acrylic lining - copper / aluminium condenser coils with Fin Guard (Silver) treatment - steel mesh strainer to be mounted at the exchanger inlet. (The manufacturer declines all liability with invalidation of the guarantee if it is not installed…
-
WSAT-SC 75C-180F - REGULATIONS AND CERTIFICATIONS - UNI EN ISO 9001 CERTIFICATION CERTIFIED QUALITY SYSTEM UNI EN ISO 9001:2000 Clivet S.p.A., in order to guarantee customer satisfaction, has chosen the ISO 9001 Quality System as the reference for all its business activities. This is demonstrated by…
-
- RESIDUAL RISKS - GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DEFINITION OF DANGER AREA - External danger zone, identified by a precise area around the unit (2 metres from the…
-
WSAT-SC 75C-180F MOVING PARTS - Contact with the fan rotors can cause injury. Before removing the protective grilles or the fans themselves, make certain the isolating switch on the power line to the unit is set to the OFF position and padlocked, and post a warning sign. - Contact with the fan…
-
08 Control of individual exposure/protection 09 Physical and chemical properties 10 Stability and reactivity 11 Toxicological information 12 Ecological information 13 Notes concerning disposal Information on shipping M01W45H6-06 Information on regulation 16 Other information Precautionary measures…
-
GENERAL SPECIFICATIONS ACOUSTIC CONFIGURATION: SC (STANDARD) SIZES 65D 70D 75C 75D 80D 90C 90D 100D 110D 120D 135F 150F 165F 180F 177.4 54 62.1 2.86 4.09 188.7 58.2 66.3 2.85 4.07 193.4 67.8 73.8 2.62 3.97 202.3 64.2 72.3 2.8 4 213 69.8 77.9 2.73 3.91 237.5 86.1 94 2.53 3.91 233.4 77.2 85.3 2.74…
-
ACOUSTIC CONFIGURATION: (EN) SIZES 65D 70D 75C 75D 80D 90C 90D 100D 110D 120D 135F 150F 165F 180F 173 55.7 61 2.84 4.26 185 60.8 66.1 2.8 4.2 187 71.9 75.8 2.47 3.83 196 67.7 73 2.68 4.02 206 73.8 79.1 2.6 3.9 233 88.7 93.8 2.49 3.86 225 81.9 87.2 2.58 3.87 253 92 97.3 2.6 3.89 30.5 30.5 30.5 30.5…
-
High pressure switch Low pressure switch Low pressure switch (Brine) Antifreeze protection High pressure safety valve Low pressure safety valve Max no. of compressor starts per hour High compressor discharge temperature safety thermostat Open 2700 kPa kPa bar °C kPa kPa Nr °C Closed 1940 360 240 6,5…
-
- RECEPTION -
WSAT-SC 75C-180F - RECEPTION - INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery…
-
- RECEPTION Insert safety pins ( 1 )
and split pins ( 2 ) 3 lifting points - use 3-arm uprights (3 slopes/chains/slings per each side of the unit) lifting points - use 4-arm uprights (4 slopes/chains/slings per each side of the unit) How to balance the charge Move the upper hook or the lower hooks, according to the spring equalizer…
-
- POSITIONING - POSITIONING -
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
- POSITIONING -
DIMENSIONS Sizes 75C 2030 9 8 OD 4-5 2990 4-5 148 59 3250 (15) 1600 977 1095 59 16 2990 (14) 1500 (13) 700 4-5 4-5 175 W2 P W1 977 "G" O 1 W4 (14) 1500 59 W3 M N (12) 700 M01W45H6-06 (1) COMPRESSOR (2) INTERNAL EXCHANGER (3) EXTERNAL EXCHANGER (4) HOLE TO HANG UNIT (5) LIFTING HOLES (6) LIFTING LUGS…
-
- POSITIONING Sizes 90C
OD OD 2030 1095 3310 170 2650 1370 500 910 1370 3650 1400 (14) 700 (12) 15 500 2650 500 700 (11) 60 W1 W2 7 O G P 60 W3 W4 N (1) INTERNAL EXCHANGER (2) EXTERNAL EXCHANGER (3) HOLE TO HANG UNIT (4) LIFTING HOLES (5) LIFTING LUGS (6) ELECTRICAL PANEL (7) POWER INPUT (8) SOUNDPROOFED CABIN M N O P OD…
-
- POSITIONING -
-
WSAT-SC 75C-180F - WATER CONNECTIONS - GENERAL WARNINGS Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the…
-
SUGGESTED CONNECTION DIAGRAM An example of a plan is as follows: F = Impurity collector with filter GE = Flexible joint GRA = Automatic filling assembly with gate valve M = Pressure gauge P = Pump PD = Differential pressure switch R = Ball valve RS = Discharge cock SA = Storage tank (if necessary) T…
-
GENERAL The characteristics of the electrical lines and relevant components must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with professional procedures and the regulations in force. All electrical operations should be…
-
CONNECTION TO THE MAINS 1. 2. 3. 4. 5. 6. 7. 8. 9. Make sure that the sectioning device at the beginning of the unit’s power line is opened, locked and equipped with a signal Open the general line disconnecting switch (if present). Verify that the net is in conformity with the data shown in the…
-
WSAT-SC 75C-180F EXTERNAL AIR TEMPERATURE PROBE - Optional It allows the automatic correction of the set-point according to the external air temperature. For example, in summer operating with low external temperatures, is possible to obtain the internal comfort also with setpoint values higher than…
-
WATER RESET - Optional It allows the automatic correction of the set-point, according to an external signal of 4-20 mA or 0-10 vcc. The working process is similar to the above mentioned process. It is necessary the parameter configuration. MENU NUM Parameter name 11 MaxCWRC WR Summer correction max.…
-
CN2 STRIP J12 WSAT-SC 75C-180F gnd - E L E C T R I C AL C O N N E C T I O N S - JUMP2 PUMP MODULE code C5110701 It manages controls and safety devices relative to the circulation pumps 2 JUMP3 1 JUMP1 JUMP4 8 J17 H L gnd DIP1 OFF ON DIP2 ON 7 6 OFF CN1 DRIVER VCM ELECTRONIC THERMOSTATIC VALVE…
-
LED 1 : signalization of gateway working 8 LED 2 : signalization of gateway in programming 1 O N C5110770 jumper for activating the firmware rewriting of the gateway RS 485 serial port + RS 485 - 1 dip switch for the configuration of the CAN OPEN addresses CAN 0 LGH ON s Connection to the CAN…
-
cod PE1W0014 / 25 Refer to the wiring diagram and to the LONWORKS MANUAL. Information on cables for the Lonworks Network are available on www.echelon.com. The LONW ORKS technology is a complete platform to implement the net system control. These nets are intelligent control instruments or nodes that…
-
- START-UP ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS Before checking, please…
-
WSAT-SC 75C-180F VERIFY TENSIONS – ABSORPTIONS Check that the temperatures of the fluids are included in the WORKING LIMITS. If the controls of the previous paragraphs are positive, it is possible to restart the unit. For information on the control panel, refer to the paragraph SETTING. While the…
-
- CONTROL -
- CONTROL - CONTROL INTERFACE COOL cooling HEAT heating ON – ECO – OFF unit enabled timing bands status INLET temperature OUTLET temperature ; OK alarm Number of steps activated in comparison with the steps available ALARM menu access Current set point SET POINT, TIMING BANDS, CLOCK access HEAT /…
-
- CONTROL -
WSAT-SC 75C-180F SET-POINT CORRECTIONS The correction aim is to optimize the unit energetic efficiency. To do this the corrections modify the set point in a dynamic way in function of determined variables: for example in summer operating with low external temperatures, so with a reduced charge, is…
-
- CONTROL -
ACCESSIBLE PARAMETERS PARAMETER MENU STRUCTURE PARAMETERS SCHEDULING CLOCK SETUP Set LIST Thermoreg. Antifreeze LIST Maintenance LIST Set - point LIST Enscheduling LIST Configure LIST Clock LIST Data LIST menu: PARAMETERS – THERMOREG. – SET POINT 90 / CEN SecondSetC 118 / CEN SetCool 272 / CEN…
-
- CONTROL SETUP – PARAMETERS
THERMOREG. Set the setpoint and the operating modes To enter in the SETUP menu button F3 SETUP I ? ESC H OME I ? ESC H OME ? ESC ? ESC ? ESC ? ESC buttons ▲▼ F2 – F3 To select the submenu SET (ATC ONLY) To access button F1 ENTER I To access the desired parameter buttons ▲▼ F1 – F2 I To modify the…
-
- CONTROL -
SETUP – CLOCK SETUP To enter in the SETUP menu CLOCK Set the clock DATA Set the dater To select the CLOCK SETUP submenu button F3 SETUP I ? ESC H OME I ? ESC H OME ? ESC ? ESC ? ESC ? ESC buttons ▲▼ F2 – F3 To access to CLOCK button F1 ENTER I To set HOURS MINUTES SECONDS HOME buttons F2 F3 F4 I H…
-
- CONTROL submenu
button F4 STATE To enter in the STATA menu GENERALS UNIT 1 I ? ESC HOME I ? ES C HOME I ? ES C HOME I ? ES C HOME I ? ESC HOME I ? ESC HOME buttons ▲▼ F2 – F3 To select the module mod_comp1 mod_comp2 To access mod_comp3 button F1 ENTER mod_evap buttons ▲▼ F2 - F3 To scroll the stata UNIT 2 mod_comp1…
-
- CONTROL Index
UNIT_1 – MOD COMP_1 Stata Valve 2 c3 status Valve 3 c3 status Liquid Solenoid Coil temperature Recovery temperature Condensation pressure Evaporation pressure Fan Status Defrost Status Defrost count time Compressor 1 operating time Comp. 1 starts Compressor 2 operating time Comp. 2 starts Compressor…
-
- CONTROL -
WSAT-SC 75C-180F An alarm list is associated with the inputs of each electronic module of the unit. According to the unit configuration, and then with electronic modules and options, some lists and/or ALARMS can not be used. ALARM STRUCTURE CENTRAL Unit_1 Mod_comp1 Mod_comp2 Mod_comp3 Mod_Evap…
-
- CONTROL -
M01W45H6-06 Str COMPRESSOR MODULE Name E101 Cond./ Evap. temp. probe fault E102 Condensing pressure probe fault E103 Evaporation pressure probe fault E104 Recovery temp. probe fault E105 High pressure alarm E106 Low pressure alarm E107 Fan/Pump thermal cut-out alarm E111 Cond. / Evap. H2O flow alarm…
-
WSAT-SC 75C-180F - ROUTINE MAINTENANCE - PREVENTIVE MAINTENANCE All equipment is subjected to wear out. The maintenance makes: 1. keeps their efficiency 2. limits breakdowns. 3. Gather information and data to understand the unit efficiency level and prevent possible faults Therefore, it is…
-
97/23 CE PED DIRECTIVE 97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well. Refer to local actuation norms. st In Italy, refer to the Ministerial Decree of 1 December 2004 no. 329 (and following modifications), which defines the st performances to be…
-
Pg
-
M01W45H6-06
-
- TROUBLESHOOTING -
WSAT-SC 75C-180F - TROUBLESHOOTING - TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE MUST CARRY OUT THE OPERATIONS. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE…
-
- TROUBLESHOOTING -
COMPRESSOR PROTECTIONS 1. Identify the part on the wiring diagram 2. Are the electric contacts / terminals loose? Are the wires broken or damaged? 3. Check electric coil continuity using a tester. 4. Is vacuum power voltage below the limits? 5. Check the power contactors and relative contacts. 6. Is…
-
- DECOMMISSIONING OF THE UNIT -
WSAT-SC 75C-180F - DECOMMISSIONING OF THE UNIT - DISCONNECTING THE UNIT Authorised personnel, who before proceeding must first read the Residual Risks section in this manual, must disconnect the units. Before disconnecting the unit, the following must be recovered, if present: o the refrigerant (if…
-
CLIVET SPA
Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it CLIVET ESPAÑA S.A. (Madrid) SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clivet-uk.co.uk CLIVET NEDERLAND B.V.…