WSAT-EE 82-102-122-142-162182-202-222-242-282
AIR COOLED WATER CHILLER FOR OUTDOOR INSTALLATION Installation and Use Manual M62N40B5-02 04/06/07
-
UNIT IDENTIFICATION
SERIAL NUMBER LABEL The units are identified by the serial number label shown here. The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer. The label is placed on the unit…
-
INSTRUCTIONS FOR THE USER
• This is a partial syntax of the information provided in the manual; carefully read this manual • Carefully read this manual. Keep it with the electrical diagram. Make it available to technicians for servicing. • Ask the installer for training on start-up, shutdown, changing set points, placing in…
-
ECO mode
-
See INPUT temp. to the unit
-
GENERAL WARNINGS
MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons…
-
RESIDUAL RISKS
GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DANGER AREA The figure below highlights the area in which only authorised personnel may operate. • External danger zone, identified by…
-
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by electrocution. When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign. MOVING PARTS Contact with the fan rotors can cause injury. Before…
-
Physical and
chemical properties Physical state (20°C): liquid gas Colour: colourless Smell: Slightly similar to ether; pH: not applicable. Boiling point/interval: -42,4 °C Melting point/interval: Not inflammable in test conditions Vapour pressure: (25°C): 1.13 Mpa (11,3 bar) a (50°C): 2.11 Mpa (21,1 bar) a…
-
RECEPTION
INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment…
-
Depending on the type of unit, the holes and/or the brackets for lifting may be located in different places 2 lifting points use 2-arm uprights (2 slopes/chains/slings per each side of the unit) REMOVING THE PACKING For removing the packaging, use specific personal protection for the operator…
-
POSITIONING
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
Tree Keep the coil clean. Avoid zones with leaves / dirt / corrosives. Consider clearances and direction of expelled air. Avoid snow build-up during winter operation ! 1. elastic joint 2. floating floor 3. soundproofing Prevent the transmission of vibrations. Provide windbreaks in locations with…
-
WATER CONNECTIONS
GENERAL Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield. INTERCEPTING…
-
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit. P 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. F 10 8 P Charged system pressure switch vent pump expansion tank safety valve flow switch pressure switch / thermometer filter filling valve…
-
ELECTRICAL CONNECTION
GENERAL The characteristics of the electrical lines and relevant components must be determined by SPECIALIZED PERSONNEL ABLE TO DESIGN ELECTRICAL INSTALLATIONS; moreover, the lines must be in conformity with professional procedures and the regulations in force. All electrical operations should be…
-
FUNCTIONAL CONNECTIONS
FOR ALL THE CONNECTIONS MAKE REFERENCE TO THE ELECTRICAL PANEL SUPPLIED WITH UNIT Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA) Few inputs must be activated by configuration parameters whose access is reserved to authorized assistance centres (in…
-
SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY
Optimises unit energy efficiency by automatically adjusting the set-point according to enthalpy or the outside temperature. Requires the external humidity probe or the outside temperature probe, which are optional for certain types of units and must be installed by the customer and enabled by…
-
- 12VAC
+5V gnd gnd + CN1 CN2 SERIALE TTL / RS485 SERIAL CONVERTER TTL/RS485 OPTIONAL - code PE2N0002 Plugged-in in the main module on the electric board (see lay in the wiring diagram). It is possible to connect up to 127 units with a single supervision system. The connection with a PC must use a RS485/232…
-
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS Before checking, please verify the…
-
REMOTE INPUT CONFIGURATIONS
Check used remote inputs are activated (ON-OFF etc.) as given in the instructions in the ELECTRIC WIRING chapter. SETTING THE SET-POINT Check if it is necessary to modify the set-points shown in the CONTROL chapter EVAPORATOR WATER FLOW RATE Check that the difference between the temperature of…
-
M
ST A AL AR SE T The HEATING mode functions are active only on HEAT PUMP unit version . In ONLY COOL units, the relative parameters are VISIBLE but NOT ACTIVE , for example the winter setpoint. TU S CONTROL OPERING MODES ON – OFF Unit can be switched on and off by: remote or service keypad remote…
-
SET-POINT COMPENSATIONS
The compensations are evolved functions to protect the compressors and to adapt, as far as possible, the unit operating to the installation and use characteristics. The compensations prolong the compressor operating time and limit the start number; to do this they delay the compressor insertion…
-
VENTILATION
Fans are controlled with a variable speed: • in SUMMER, the speed increases according to the increase of fresh air temperature • in WINTER the speed increases according to the decrease of the outside temperature SET POINT SUMMER - WINTER The thermoregulator manages two set points: • SUMMER set-point…
-
KEYPAD
Menu and “historical log “of alarms flashes during an alarm Led signalling the necessity to multiply by 100 the value VALUE display Opened active defrost Opened active compressor INDEX display. U S STATUS menu AT ST AL AR M COOLING open in COOL HEATING open in HEAT Opened ACTIV PUMP ON –OFF S ET…
-
AT
US SE T M AT U S SE T ST AT US AT US SE T AL AR M Select another parameter SET to esc SE T AL AR M Select the parameter ST 5 AL AR M 4 ST Modify the value ST 3 AL AR M 2 SE T AL AR Push SET button ST 1 AT U S PARAMETER MODIFICATION VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD According to…
-
SE
T S M TU R AL A Select status STATUS to esc SE T ST A 3 AT US AL AR M 2 ST U AT ST push STATUS button SE T AL AR M 1 S STATUS DISPLAY ALARMS BEFORE RESETTING THE ALARM, IDENTIFY AND ELIMINATE THE CAUSE OF ITS ACTIVATION. REPEATED RESETS CAN CAUSE IRREVERSIBLE DAMAGES. The ALARMS show a potentially…
-
According to the unit configuration and to the current options, some status can not be
used. INDEX ALARM RESET E 1 Faulty or disconnected water return probe Auto. E 2 Faulty or disconnected water supply probe 1 Auto. E 3 Faulty or disconnected water supply probe 2 Auto. E 4 Faulty or disconnected coil probe 1 Auto. E 5 Faulty or disconnected coil probe 2 Auto. E 6 Faulty or…
-
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT . cleaning activities; otherwise, controls have to be performed by specialized technicians (INSPECTIONS). All equipment is subjected to wear…
-
• check the operating parameters of the refrigerating
circuit (see the following REFRIGERANT TABLES and the START-UP section) For units equipped with safety valves, follow the Manufacturer’s instructions. Verify periodically the cleaning of the safety valves and that oxidative / corrosive phenomena are not present, in particular for installations near…
-
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING: • THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION • THE MODES OF DETECTING TEMPERATURE AND PRESSURE • THE RISKS RELEVANT TO THESE OPERATIONS • • • • The data of the tables allow the testing of the…
-
Pg
-
таблицы и схемы — в просмотре
-
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING AN ALARM, IDENTIFY…
-
FAN PROTECTION
1. Identify the part on the wiring diagram 2. fan mechanically jammed, bearings / drive belt (if present) 3. Loose electric contacts/terminals, leads broken 4. electrical windings of fan interrupted 5. power supply voltage below limits 6. electrical absorption high / unbalanced COMPRESSOR PROTECTION…
-
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. Awaiting dismantling and disposal, the unit can also be stored outdoors, as bad weather and rapid changes in temperature will not cause…
-
TECHNICAL DATA SIZE Cooling Cooling capacity Comp. input power Total input power EER EER EER COMPRESSORS Compressor type No. of compressors Capacity control steps Std Refrigerant circuits Refrigerant charge (C1) INTERNAL EXCHANGER Type of exchanger No. Of exchangers Water flow-rate Useful pump…
-
OPERATING LIMITS (COOLING)
SIZE EXTERNAL EXCHANGER Max air intake temperature Max air intake temperature Min air intake temperature INTERNAL EXCHANGER Max water return temperature Min. water supply temperature °C °C °C 4 5 °C °C 48.5 44.5 50 46.5 50.5 45 43 49.5 48 -10 46.5 43.5 48 44.5 49.5 24 4 Water thermal head (min /…
-
DIMENSIONS
Sizes 82-102-122 (1) COMPRESSOR (2) WATER RETURN (STANDARD UNIT) Ø 1 1/4"F GAS (3) WATER RETURN (UNIT WITHOUT HYDRONIC GROUP KIT) Ø 1 1/4"F GAS (4) EXCHANGER WATER SUPPLY Ø 1 1/4"F GAS (5) ELECTRICAL PANEL (6) PLATE EXCHANGER (7) POWER INPUT (8) FINNED EXCHANGER (9) ACCESS TO THE COMPONENTS (10)…
-
Sizes 142-162-182
(1) COMPRESSOR (2) WATER RETURN (STANDARD UNIT) Ø 2" F GAS (3) INTERNAL EXCHANGER WATER SUPPLY Ø2" F GAS (4) ELECTRICAL PANEL (5) FINNED EXCHANGER (6) PLATE EXCHANGER (7) ACCESS TO THE COMPONENTS (8) DESUPERRESISTANCE (OPTIONAL) (9) CENTRIFUGAL PUMP (10) POWER INPUT Sizes W1 W2 W3 W4 Operating…
-
Sizes 202-222-242-282
(1) COMPRESSOR (2) WATER RETURN (STANDARD UNIT) Ø 2" F GAS (3) INTERNAL EXCHANGER WATER SUPPLY Ø2" F GAS (4) ELECTRICAL PANEL (5) FINNED EXCHANGER (6) PLATE EXCHANGER (7) ACCESS TO THE COMPONENTS (8) DESUPERRESISTANCE (OPTIONAL) (9) CENTRIFUGAL PUMP (10) POWER INPUT Sizes W1 W2 W3 W4 Operating…
-