WSAT-EE
17-21-25-31-4151-61-71-81-91 AIR-COOLED WATER CHILLERS FOR OUTDOOR INSTALLATION Installation and Use Manual M22N40B5-03 10/10/07
-
UNIT IDENTIFICATION
SERIAL NUMBER LABEL The units are identified by the serial number label shown here. The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer. The label is placed on the unit…
-
INSTRUCTIONS FOR THE USER
• This is a partial sintex of the information provided in the manual; carefully read this manual • Carefully read this manual. Keep it with the electrical diagram. Make it available to technicians for servicing. • Ask the installer for training on start-up, shutdown, changing set points, placing in…
-
TO DO FOR
Some functions are active only if they are enabled during installation (remote ON-OFF, remote SUMMER WINTER change, remote ECO, sanitary hot water, set point compensation). Check with the installer about the configuration used. Start the unit LONG pressing of the ON/OFF button Choose the SUMMER mode…
-
TEST + ON/OFF contemporary for some
seconds Control parameter ametro 32 Modify the water temp. in ECO cooling Control parameter 29 Modify the water temp. in MAINTENANCE cooling Control parameter 42 Only by SERVICE keypad SE T A LA RM Modify the water temp. in COOLING S TA TU S To reset the current alarm ONLY AFTER THE CAUSE…
-
GENERAL WARNINGS
MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons…
-
RESIDUAL RISKS
GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DANGER AREA The figure below highlights the area in which only authorised personnel may operate. • External danger zone, identified by…
-
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by electrocution. When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign. MOVING PARTS Contact with the fan rotors can cause injury. Before…
-
Physical and
chemical properties Physical state (20°C): liquid gas Colour: colourless Smell: Slightly similar to ether; pH: not applicable. Boiling point/interval: -42,4 °C Melting point/interval: Not inflammable in test conditions Vapour pressure: (25°C): 1.13 Mpa (11,3 bar) a (50°C): 2.11 Mpa (21,1 bar) a…
-
RECEPTION
INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment…
-
POSITIONING
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
Install the unit raised off the ground and on a sturdy base
Consider the maximum depth that snowfall might reach. ! ! 2A ! Tree ! A Consider clearances and direction of expelled air. Keep the coil clean. Avoid zones with leaves / dirt / corrosives. 1. elastic joint 2. floating floor 3. soundproofing Prevent the transmission of vibrations. ! Provide…
-
WATER CONNECTIONS
GENERAL Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield. INTERCEPTING…
-
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit. P F 10 8 P 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Charged system pressure switch vent circulating pump / pump expansion tank safety valve flow switch pressure switch / thermometer filter…
-
ELECTRICAL CONNECTION
the unit; the electrical data shown in the technical chart refer to standard units. In the event of differences between the data of the registration plate and the data shown in this manual, as well as in the technical chart, please refer to the DATA SHOWN IN THE REGISTRATION PLATE. GENERAL The…
-
CONNECTION TO THE MAINS
1. Make sure that the sectioning device at the beginning of the unit’s power line is opened, locked and equipped with a signal. 2. Open the general line disconnecting switch (if present) 3. Verify that the net is in conformity with the data shown in the registration plate placed on the electrical…
-
FUNCTIONAL CONNECTIONS
FOR ALL THE CONNECTIONS MAKE REFERENCE TO THE ELECTRICAL PANEL SUPPLIED WITH UNIT Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA) Few inputs must be activated by configuration parameters whose access is reserved to authorized assistance centres (in…
-
DUAL CONTROLS FOR TEMPERATURE – RADIANT PANELS It is necessary the expansion plug-in module that must be fitted by the client (r refer to the kit instructions) and enabled by parameter 140 = 1. With the optional kit, the mixed elements can be controlled: fan coils + radiant panels: • Radiant panel…
-
SET POINT COMPENSATION WITH 4-20 mA SIGNAL (WATER RESET) It optimizes the energetic efficiency of the unit by automatically changing the set-point according to an external signal of 420 ma type. It requests the expansion plug-in module option that must be fitted by the client (refer to the kit…
-
8. UNIT INTERFACE VIA RS 485
Below the indications for the serial connection ; refer anyway to the CLIVET “RS 485 NETWORKS – GUIDELINES” document and ask for the COMMUNICATION PROTOCOL about the COMPACT electronics - - The total length of each single serial line, don’t have to be over 1000 metres The potential difference…
-
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. When using antifreeze solutions, make sure the glycol…
-
VERIFY TENSIONS – ABSORPTIONS
Check that the temperatures of the fluids are included in the WORKING LIMITS. If the controls of the previous paragraphs are positive, it is possible to restart the unit. For information on the control panel, refer to the paragraph CONTROL. While the unit is working (ATTENTION ELECTRIC RISK: WORK…
-
CONTROL
The HEATING mode functions are active only on HEAT PUMP unit version . In ONLY COOL units, the relative parameters are VISIBLE but NOT ACTIVE , for example the winter setpoint. OPERING MODES ON – OFF Unit can be switched on and off by: • keypad • remote switch (see ELECTRICAL CONNECTIONS paragraph)…
-
SET-POINT COMPENSATIONS
The compensations are evolved functions to protect the compressors and to adapt, as far as possible, the unit operating to the installation and use characteristics. The compensations prolong the compressor operating time and limit the start number; to do this they delay the compressor insertion…
-
SECONDARY SET POINT – ECO
A secondary set point can be used with different levels to the “normal” set point. It is normally set to give lower energy consumption with respect to the comfort setting: • The SECONDARY SUMMER set point is higher than the SUMMER setting. It can be set according to individual requirements. •…
-
ON - OFF
The ON-OFF control from the keyboard allows activating or deactivating the normal functioning of the unit. SETTING THE OPERATING MODE key for a few moments. COOLING: to set the SUMMER operating mode, press the When the mode has been activated, the corresponding green led lights up. When the mode has…
-
FUNCTIONING TEST
The “Test” key allows the verification of the proper functioning of the all six signalisation LEDs. When it is pressed, all leds are ON until the key is released. REMOTE OR SERVICE KEYPAD (OPTIONALS) Menu and “historical log “of alarms flashes during an alarm Led signalling the necessity to multiply…
-
M
ST AT US Select another parameter ST AT U S SE T AL AR M AL AR Select the parameter SET to esc SE T AL AR M 5 M 4 ST AT U S Modify the value SE T ST AT U S 3 AL AR 2 SE T Push SET button SE T AL AR M 1 ST AT U S PARAMETER MODIFICATION VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD INDEX…
-
M
SE T S M TU R AL A Select status STATUS to esc SE T ST A 3 ST AT U S 2 AL AR U AT ST push STATUS button SE T AL AR M 1 S STATUS DISPLAY ALARMS BEFORE RESETTING THE ALARM, IDENTIFY AND ELIMINATE THE CAUSE OF ITS ACTIVATION. REPEATED RESETS CAN CAUSE IRREVERSIBLE DAMAGES. The ALARMS show a potentially…
-
The complete list of alarms is provided below; depending on the machine type and its configuration, some of the codes shown may not be used. E 00 Serial faulty - comunicazione tastiera / scheda base E 1 Faulty or disconnected water inlet probe Auto E 2 Faulty or disconnected water outlet probe Auto.…
-
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT . cleaning activities; otherwise, controls have to be performed by specialized technicians (INSPECTIONS). All equipment is subjected to wear…
-
MAINTENANCE INSPECTIONS
Foresee inspection assistance carried out by authorized centers or by qualified personnel. The inspections should be carried out at least: • - Every year for only the cooling units • - Every six months for the cooling and warming units The frequency, however, depends on the use: in the event of…
-
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING: • THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION • THE MODES OF DETECTING TEMPERATURE AND PRESSURE • THE RISKS RELEVANT TO THESE OPERATIONS The data of the tables allow the testing of the refrigerating…
-
Pg
-
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING AN ALARM, IDENTIFY…
-
COMPRESSOR PROTECTION
1. Identify the part on the wiring diagram 2. Loose electric contacts/terminals, leads broken 3. electrical windings interrupted 4. Vacuum power voltage below the limits 5. power contactors / contacts defective 6. start-up power voltage lower than the limits 7. electrical absorption high /…
-
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT DISMANTLING AND DISPOSAL The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL. Before disconnecting the unit, the…
-
TECHNICAL DATA
SIZE COOLING Cooling capacity Compressor power input Total power input EER COMPRESSOR Type of compressors No. of Compressors Std Capacity control steps Refrigerant charge (C1) Refrigerant circuits INTERNAL EXCHANGER Type of internal exchanger No. of internal exchangers Water flow rate Useful pump…
-
OPERATING LIMITS (COOLING)
SIZE EXTERNAL EXCHANGER Max air intake temperature Min. air intake temperature Min. air intake temperature INTERNAL EXCHANGER Max water inlet temperature Max water inlet temperature Min. water outlet temperature 1 °C 2 °C 3 °C 4 °C 5 °C 47.5 12 48 11.5 10.5 48.5 12.5 46.5 10.5 47 11.5 47.5 11.5 45…
-
EVAPORATOR PRESSURE DROP LIMIT. CAUTION
DO NOT USE OVER THIS LIMIT 81-91 61-71 41-51 17-21 25-31 INTERNAL EXCHANGER PRESSURE DROP DP (kPa) 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 Q (l/s) 1,0 1,1 1,2 1,3 1,4 UNIT WITHOUT HYDRAULIC CIRCUIT COMPONENTS DP = PRESSURE DROP Q = WATER FLOW 1,5 1,6 EVAPORATOR PRESSURE DROP LIMIT. CAUTION: DO NOT USE…
-
DIMENSIONS
Size 17-21 23,5 (15) W2 2 W1 P "G" 5 10 (15) 500 2 (15) 100 1 O W4 23,5 12 13 W3 M N 6 The units require minimum clearances for operation and maintenance. The following sketch describes the minimum clearances to be considered. In the event of multiple units, the functional clearances must be…
-
Size 25-31
1095 23,5 (15) W2 2 W1 P "G" 5 10 (15) 500 2 (15) W4 23,5 12 13 O W3 M N 6 The units require minimum clearances for operation and maintenance. The following sketch describes the minimum clearances to be considered. In the event of multiple units, the functional clearances must be doubled. Size M N O…
-
Size 41-51
3 1040 1175 1057 15 (16) 150 15 23,5 W2 5 W1 1 "G" 2 (16) 100 10 P O 1087 (16) 500 23,5 W4 W3 M N 14 The units require minimum clearances for operation and maintenance. The following sketch describes the minimum clearances to be considered. In the event of multiple units, the functional clearances…
-
Size 61-71-81-91
1325 1225 1110 116 1373 1343 15 23,5 (16) W2 W1 2 508 (16) 100 2 "G" 23,5 P W4 W3 M 13 1 (16) 500 O 4 4 N The units require minimum clearances for operation and maintenance. The following sketch describes the minimum clearances to be considered. In the event of multiple units, the functional…
-
CLIVET SPA
Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it CLIVET ESPAÑA S.A. (Madrid) SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clivet-uk.co.uk CLIVET NEDERLAND B.V.…