1 BACnet Gateway---CCM08
Step1: Wiring with Central controller and indoor/outdoor units Refrigerant System: V3 V4 D3 D4 RS485 indoor units RS485 indoor units Max.64 IDUs CCM03 controller Max.8 refrigerant systems CCM02 controller
-
Refrigerant System: Full V4+
indoor units MAX:64 indoor units CCM03 MAX:8 systems CCM02 indoor units
-
Step2: Wiring with gateway and central controllers
Useful port, Connect to PC Port reserved, No useful Each gateway has a initial IP address, this one is:192.168.208.231,Pls keep it 4*Port RS485, each port connect one CCM(indoor or outdoor) and corresponding indoor or outdoor units
-
Power
Socket Power Switch
-
Ex. In this case, CCM08 connect one CCM03 and 8 IDUs
-
Modify the PC ip address to:192.168.208.232, under the same address range with CCM08.
-
Turn on IE,input 192.168.208.231 in the address bar
Initial user name:admin Initial PW: 12345
-
After that, the web control interface appeared
In the web control interface, we can control and monitor the A/C
-
Step4: Connect the gateway to LAN
-
Next, Change the ip address of CCM08
Cannot choose this item !!! No useful, Don’t care about it Change the ip address under the same address range. Pls ask the IT administrator which ip address is available. In this case, ip address of CCM08 have been changed to 10.46.1.2
-
After modified, Click “Rebot”botton
-
Connect CCM08 to LAN by Hub
-
into the web control interface, So CCM08 has been connected to LAN.
-
Additional: CCM08 cooperate with 3rd network software
Ex. In this case, IP address of PC is 10.46.1.253, ip address of CCM08 is 10.46.1.251. There are 10 IDUs(Network address range: (0054~0063), 1 ODU(Network address: 1800) Turn on ACServer
-
3.This is CCM08 ip address range. Max.256 CCM08 can be connected to LAN 6.All existed CCM08 will be found. In this case, only one. 2.In any case, here have to be 19781 4.In any case, here have to be 19780 5.Finish all setting above, Click Scan
-
After configuration, Searching the
devices After search, back to software main interface
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Контроллеры Gateway CCM08. Инструкция по установке.PDF · 345.52 Kb
- Шлюз Gateway CCM08 для систем управления. Инструкция по эксплуатации.PDF · 2.34 Mb
- Шлюз Gateway CE-CCM-18A/N. Инструкция по эксплуатации.PDF · 362.53 Kb
- Шлюз протокола LONWORKS MD-LonGW64/E для интеграции системы кондиционирования в системы BMS. Инструкция по эксплуатации.PDF · 2.65 Mb
- M-INTERFACE Gateway. Инструкция по установке и эксплуатации.PDF · 1.26 Mb
- Шлюз IMM441V4PA58. Инструкция подключения.PDF · 674.12 Kb
- BACnet шлюз CCM-08. Централизованное управление кондиционированием. Инструкция по эксплуатации.PDF · 473.81 Kb
- Шлюз MD-CCM08 для кондиционеров MDV07U-029BW. Инструкция по эксплуатации.PDF · 517.19 Kb
- Интеллектуальная система управления IMM. Инструкция по эксплуатации.PDF · 1.66 Mb
- Шлюз Gateway CCMO8. Технические характеристики.PDF · 1.20 Mb