4.3 Modbus BMS gateway: CCM-18A
CCM-18A support the Modbus protocol network, bridge the Midea central A/C system to the BMS, and support RTU or TCP/IP mode. Support the Modbus protocol network Built-in WEB server function Each gateway can be connected up to 64/16 indoor units and 4 outdoor units Transfer the information…
-
4.3.2 Ports instruction
WAN port: Connect to the router by 5 Ethernet cables to ensure that PC can access to the web page. A1B1E port:Connect to the XYE ports of the indoor unit and the K1K2E ports of the outdoor unit A2B2E port:Connect to the terminal serial port. POWER port: Offer DC 5V Reset button: Can reset to the…
-
4.3.4 Network example
1. One Modbus gateway can bridge one refrigerant system with a PC or the Modbus master 2. The PC system with the Modbus protocol port can communicate with CCM-18A through RTU or TCP/IP method to control and monitor units. There are two methods for your reference. 1) TCP/IP connection method: 2) RTU…
-
Notes:
If it doesn’t monitor the ODU’s states, it can directly connect to the XYE ports of the indoor/outdoor units in both ways above. If it connects to XYE ports of master ODU, ODU must be set to auto addressing mode. XYE and K1K2E must be connected hand by hand. It supports two kinds of baud…
-
Configure several IP
Before configuring several IP, it needs to configure a statistic IP address. Open the property dialog, select the "Advanced", and it will display the TCP/IP setting dialog. Click "Add" button in the IP address bar can add an IP address which is in the same segment as "192.168.1.200", for example…
-
Parameters Setting
Parameter Modbus address Modbus communication setting Description Modbus ID is used to distinguish multiple gateways which with Modbus protocol in the same subnet segment. The ID must not repeat and can be modified. Baud rate: suggest 9600; Check bit: no checking by default Stop bit: 1 Stop Bit by…
-
When click "input register", it will display as following dialog
Fig.4.5 Addresses Content Display value Addresses Content Display value The first column is the address, the second is the content and the third is displayed value, e.g. 17/0011, 17 is decimal display, 0011 is hexadecimal display. Explanation of part of the content: For example, 0~3 outdoor unit…
-
4.3.5.4 Air Conditioner Control
※ When click “Air Conditioner Control” on the web page, it will display as following dialog: Single control area Group control area Fig.4.6 Single control area: You can control a single air conditioner, set mode, fan speed, temperature setting and click "Apply" button to carry out a single…
-
4.3.5.5 Software installation and debug
※ PC access mode The PC system with Modbus protocol port can communicate with the Modbus gateway through TCP/IP protocol or Modbus RTU. For detailed information, please refer to 4.3.3 Network example. ※ Install Modbus Poll software Through Modbus Poll software to access debugging. When finish…
-
2) Connection through Modbus/RTU
Choose RTU to connect, it will display as following dialog and you can set the corresponding parameters. To PC port Parameter setting must be the same as WEB page, detailed refer to Fig.4.3 Fig.4.9 ※ Test Modbus Poll software can read/write the content of the corresponding address in mapping table.…
-
Take writing holding register for example
Choose button in Fig.3.7, as shown below: change the value Modbus address holding regi ster address After changed the value, click "send" button to finish the writing operation. ※ Software Reset Press "RESET" button on the gateway for 3 seconds and power on again, the software configuration will be…
-
4.3.8 Mapping table
4.3.8.1 Indoor unit variable mapping table Modbus description Coils(R) Indoor address number 0 Modbus register address 9-16 17-24 Control System Data name Fan mode Dry mode Heat mode Cool mode Auto mode Mode locking Reserve On/Off High fan speed Mid fan speed Low fan speed Low fan speed Reserve…
-
Modbus
description Indoor address number Modbus register address 25-32 33-40 41-48 Coils(R) 0 49-56 Data name ECO operation Electric auxiliary heating Swing Reserve Reserve Reserve Reserve Reserve Horizontal swing Add water Water drain pump Reserve Locking cool mode Locking heat mode Centralized controller…
-
Modbus
description Indoor address number Modbus register address 65-72 Data name P8 Compressor over current protection P9 PA PB PC PD PE Length 1 Octet Octet Order 9 PF Other protections 0 73-80 Coils(R) 81-128 137-144 145-152 Control System 0# Network connection module and mainboard communication error 1#…
-
Modbus
description Indoor address number Modbus register address 153-160 161-168 169-176 Coils(R) 1 177-184 Data name Eco operation Electric auxiliary heating Swing Reserve Reserve Reserve Reserve Reserve Horizontal swing Add water Water drain pump Reserve Locking cool mode Locking heat mode Centralized…
-
Modbus
description Indoor address number Modbus register address 193-200 Data name P8 Compressor over current protection P9 PA PB PC PD PE Length 1 Octet Octet Order Explanation 25 1:Protection; 0:Normal Reserve, stay 0 Reserve, stay 0 Reserve, stay 0 Reserve, stay 0 Reserve, stay 0 Reserve, stay 0…
-
таблицы и схемы — в просмотре
-
Modbus
description Input Register (R) Control System Indoor address number 0 Modbus register address Data name Length Explanation bit0: the running state of the system 1:running, 0:stop; bit1: the error state of the system, 1:error,0:normal; bit2: local/remote, 1:remote, 0:local 30001 System state 2 Octet…
-
Modbus
description Input Register (R) Indoor address number 0 Modbus register address Length 30020 16~31# indoor unit online state 2 Octet 30021 32~47# indoor unit online state 2 Octet 30022 48~63# indoor unit online state 2 Octet 30023 0~3 #outdoor unit error state 2 Octet 30024 30025 225 Data name 0~3#…
-
Modbus
description Input Register (R) Control System Indoor address number 0 Modbus register address Data name Length 30026 16~31# indoor unit error state 2 Octet 30027 32~47# indoor unit error state 2 Octet 30028 48~63# indoor unit error state 2 Octet 30029 0~15# indoor unit running state 2 Octet 30030…
-
Modbus
description Input Register (R) Indoor address number 1 Modbus register address 30033 30034 30035 Reserve Model message 1 Model message 2 2 Octet 2 Octet 30036 Setting temp. Ts 2 Octet 30037 Indoor temp T1 2 Octet 30038 Evaporator pipe temp. T2A 2 Octet 30039 Evaporator medium pipe temp. T2B 2 Octet…
-
Modbus
description Indoor address number n Modbus register address 30000+n*32+1 30000+n*32+2 30000+n*32+3 30000+n*32+4 30000+n*32+5 30000+n*32+6 30000+n*32+7 Input Register (R) 63 30000+n*32+8 30000+n*32+9 30000+n*32+10 30000+n*32+11 30000+n*32+12 30000+n*32+13 (30000+n*32+14) ~(30000+n*32+32 32017 32018…
-
Modbus
description Indoor address number Modbus register address Data name Length Refrigerant 40001 system on/off 2 Octet Holding register (W) 0 40002 Setting mode 2 Octet Setting fan 40003 2 Octet 0:All-off the system 1:All-on the system – The summer mode 1: cooling,17℃,Low speed, no timer and auxiliary…
-
Modbus
description Indoor address number 0 Modbus register address Auxiliary function state 2 Octet 40008-40032 Reserve 50 Octet 40033 Reserve 2 Octet 40034 Setting mode Setting fan speed Setting temperature Time on 2 Octet 2 Octet 40040~40064 Time off Auxiliary function state Reserve 40000+n*32+1 Reserve…
-
Modbus
description Indoor address number Modbus register address Data name Length Explanation 64 / / / Can group control the 0-7# indoor units and the format is the same as the above each indoor unit. 65 / / / Can group control the 8-15# indoor units and the format is the same as the above each indoor…
-
4.3.8.2 Outdoor unit variable mapping table
Modbus description Coils(R) Indoor address number 0 Modbus register address 8192+1 8194 8195 8196 8197 8198 8199 8200 8201 8202 8203 8204 8205 8206 8207 8208 8209 8210 8211 8212 8213 8214 8215 8216 8217 8218 8219 8220 8221 8222 8223 8224 8225 8226 8227 8228 8229 8230 8231 8232 8233 8234 8235 8236…
-
Modbus
description Indoor address number 0 Modbus register address 8239 8240 8241 8242 8243 8244 8245 8246 8247 8248 8249 8250 Coils(R) 1 233 8251 8252 8253 8254 8255 8256 8257~8320 8320+1 8322 8323 8324 8325 8326 8327 8328 8329 8330 8331 8332 8333 8334 8335 8336 8337 8338 8339 8340 8341 8342 8343 8344…
-
Modbus
description Indoor address number Modbus register address 8353 8354 8355 8356 8357 8358 8359 8360 8361 8362 8363 8364 8365 8366 Coils(R) 1 8367 8368 8369 8370 8371 8372 8373 8374 8375 8376 8377 8378 8379 8380 8381 8382 8383 8384 8385~8448 Control System Data name E0 Outdoor unit communication error…
-
Modbus
description Coils(R) Indoor address number n Modbus register address Data name Explanation 8192+n*128+1 8192+n*128+2 8192+n*128+3 8192+n*128+4 8192+n*128+5 8192+n*128+6 8192+n*128+7 8192+n*128+8 8192+n*128+9 8192+n*128+10 8192+n*128+11 8192+n*128+12 8192+n*128+13 8192+n*128+14 8192+n*128+15…
-
Modbus
description Indoor address number n Coils(R) 3 Control System Modbus register address Data name Explanation 8192+n*128+49 8192+n*128+50 8192+n*128+51 8192+n*128+52 8192+n*128+53 8192+n*128+54 8192+n*128+55 8192+n*128+56 8192+n*128+57 P0 Compressor top temp. protection P1 Discharge high pressure…
-
Modbus
description Indoor address number Modbus register address 8609 8610 8611 8612 8613 8614 8615 8616 8617 8618 8619 8620 8621 8622 Coils(R) 3 8623 8624 8625 8626 8627 8628 8629 8630 8631 8632 8633 8634 8635 8636 8637 8638 8639 8640 8641~8704 237 Data name E0 Outdoor unit communication error E1 Phase…
-
Modbus
description Indoor address number Modbus register address 32048+1 32050 32051 0 Input register (R ) Data name Reserve Ambient temperature T4 32053 Condenser outlet temperature T3 32054 Condenser inlet temperature T6 32056 The discharge temperature of compressor 2 32057 The discharge temperature of…
-
Modbus
description Indoor address number 1 Modbus register address Current of compressor 3 32090 32091 Inverter compressor frequency Opening degree of EXV 1 32092 Opening degree of EXV 2 32093 Capacity of outdoor unit 32094 Reserve 0~200 means the current range from 0A to 200A 0~250 means 0~250Hz 00h~07Dh…
-
Modbus
description Indoor address number Modbus register address 32145 32146 32147 Input register (R ) Data name Reserve Reserve, stay 0 The first byte of models message The second byte of model message 32148 Ambient temperature T4 32149 Condenser outlet temperature T3 32150 Condenser inlet temperature T6…