AHU Controller Specifications
1. Application This controller is used to set up a system by connecting a field-supplied Air Handling Unit (AHU) to Mitsubishi Electric City Multi outdoor unit. This controller can be used to control the system only in cooling mode. Applicable models: PAC-AH63, 125, 140, and 250M-G 2. System…
-
Pipe length
Height difference (1) (2) (3) No further branching in the pipes is possible after the header branch. When cooling operation is performed when the outdoor temp. is 0ºC or lower:H’=4m or less Equivalent pipes length(m):Actual pipe length + A×number of bent. Table A Outdoor unit model P250 P300 P350 A…
-
Amount of
refrigerant to be added (1) Original charge of refrigerant and the maximum total charge. At factory shipment, refrigerant are charged in the outdoor unit as shown at following Table. When extending the piping in the field, additional charge of refrigerant is needed. Yet, the maximum total charge in…
-
Terminal block
Connector Relay LEV-kit Thermistor Clip Insulation Tie band Tube Installation manual (3) Major specifications Power supply External dimension (mm) Net weight (kg) External finish(Munsel No.) IP-class Remote controller temperature setting range Operation Operation by optional remote controller…
-
Protection function
Freeze prevention After 16-minute or more cooling operation, and when 1ºC or less of the thermistor detection temperature for liquid pipe is detected for 3 minutes in a row, the linear expansion valve will be closed to prevent freezing. The operation will be normal when either of the following…
-
leakage
Contamination control Wash the heat exchanger with detergent to make the allowable level of contamination per unit length of the heat exchanger tube the following values or less on the assumption that the heat exchanger tube size is Φ9.52. Do not use chlorinated detergent. Do not leave flux.…
-
- Do not strain the power supply wires
- Be careful with the plate edge not to damage to the wire from being damaged. - The wire can withstand only up to 105ºC. Keep the wire away from high-temperature part. - Bend the wire into "U" shape to prevent water from running down the wire and from dripping on the electrical components or the…
-
■Interlock operation with fan error and connection example of field-installed thermostat
Interlock the unit so that the unit stops when an error occurs on the fan (field supply). X: Relay(field supply) Minimum applicable load DC5V, 1mA SW2: Operation command (field supply) Error: Error of fan sections (field supply) Thermo: Thermistor (field supply) Operation signal L1: Operation…
-
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
6. (1) (2) (3) (4) 7. CPEVS : PE insulated PVC jacketed shielded communication cable CVV : PV insulated PVC sheathed control cable Related cautions Installation work Secure enough service space for replacement of the LEV and the thermistor. After an AHU controller is installed, address setting and…
-
EE
-
Electrical Wiring Diagram
WYN C0-8494 11/11
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Контроллеры секций охлаждения серии PAC-AH125/140/250/500M. Инструкция по проектированию, установке и настройке.PDF · 1.44 Mb
- Контроллеры секций охлаждения серии PAC-AH125, 140, 250M-H. Инструкция по монтажу.PDF · 722.61 Kb
- Контроллеры секций охлаждения серии PAC-AH63, 125, 140, 250M-G. Инструкция по монтажу.PDF · 450.26 Kb
- Контроллеры секций охлаждения серии PAC-AH125, 140, 250M-H для наружных блоков. Технические характеристики.PDF · 385.97 Kb