Air Handling Unit Controller
FOR INSTALLER INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the controller. GB PAC-AH63, 125, 140, 250M-G
-
[Fig. 2.0.1] Controller 2 LEV-kit 3 Thermistor 4 Clip 5 Insulation 6 Tie band 7 Installation manual 8 Tube 3 [Fig. 3.0.1] C D B F A L I J G H E 2 K A Air handling unit controller (PAC-AH · M-G) B Air handling unit (field supply) C Controller (field supply) D Outdoor unit E Indoor unit (City Multi) F…
-
• 1.3. Before getting installed • Caution: • • • • Do not install the unit where combustible gas may leak. - If the gas leaks and accumulates around the unit, an explosion may result. Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept. - The quality…
-
3. System component
[Fig. 3.0.1] (P.2) 3.1.3 Specifications of the evaporator A Air handling unit controller (PAC-AH · M-G) B Air handling unit (field supply) C Controller (field supply) D Outdoor unit E Indoor unit (City Multi) F Evaporator (field supply) G Gas pipe H Liquid pipe I LEV-kit J Thermistor (gas pipe) K…
-
6. Connecting refrigerant pipes
6.1. Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit and BC controller (simultaneous cooling and heating series R2). For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.…
-
8. Put the unit to the ground on the outdoor unit side
Connecting wiring 9. Select control cables from the conditions given in page 10. [Fig. 7.0.1] (P.4) Caution: A Outer cover K Operation signal Be sure to put the unit to the ground on the outdoor unit side. Do not connect the earth cable to any gas pipe, water pipe, lightening rod, or telephone earth…
-
7.3.1 Connecting LEV-kit cables
Connect the lead wire of the linear expansion valve to the controller. Pull the end of wire (ring terminal) through the bunch of wires (LEV-kit) at the bottom of the controller. Connect the lead wire of the expansion valve to the same colored terminal. When the lead wire is too long, cut it to the…
-
8. Setting switches
8.1. Setting addresses 8.2. Setting unit size (Be sure to operate with the main power turned OFF.) Set the unit size according to the evaporator type (field supply). Set the dip switch (SW2) on the control board in accordance with the chart below. Type Unit size Allowed evaporator Setting switches…
-
This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is based on the following EU regulations: • • Low Voltage Directive 73/23/EEC Electromagnetic Compatibility Directive 89/ 336/EEC Please be sure to put the contact…