AHU Controller Specifications
1. Application This controller is used to set up a system by connecting a field-supplied Air Handling Unit (AHU) to Mitsubishi Electric City Multi outdoor unit. Applicable models: PAC-AH125, 140, and 250M-H 2. System restrictions and use of range (1) System configuration Connectable outdoor units…
-
Pipe length
-
(a)
Amount of refrigerant to be added Original charge of refrigerant and the maximum total charge. At factory shipment, refrigerant are charged in the outdoor unit as shown at following Table. When extending the piping in the field, additional charge of refrigerant is needed. Yet, the maximum total…
-
Controller components Name Controller Controller board Transformer Terminal block Connector Relay LEV-kit Thermistor Clip Insulation Tie band Tube Installation manual (3) Major specifications Power supply External dimension (mm) Usage For operation control For controller board For power source, for…
-
Temperature
-
Temperature
control by external thermostat Protection function Freezing prevention Sensor failure Communication error Other types of error Connect the field-installed external thermostat (ON/OFF) to the external input (ON/OFF) to start the operation when the external thermo is ON, and stop the operation when it…
-
Switch function
Thermostat control a) Change of discharge or suction air temperature control Dip switch SW7-2 OFF ON Thermostat control Remarks Suction / return Discharge - Initial setting b)TH21 Detection temperature of the thermistor TH21 is replaced to the value below by Dip switch on the control board. Dip…
-
d)Dip-switch for function
In a table shown below, the gray part shows “At delivery”. i) Discharge air temperature control SW1 No. Function 1 Thermistor< suction temperature> position Replace of TH21 Cooling: TH21-a Heating: TH21+a Operation by switch ON OFF Remote TH21 controller 2/3 OFF/OFF: a=0 ON / OFF: a=1 OFF/ ON: a=2…
-
4. Requirements on AHU design
(1) Design method of heat exchanger Model name Common part Unit capacity 3 PAC-AH125M-H PAC-AH140M-H PAC-AH250M-H Reference air flow rate (m /h) 2000 2500 3000 4000 5000 Min. volume inside 1500 1900 2150 3000 3750 2850 3550 4050 5700 7100 11.2 9.0 4~5 14.0 11.2 4~5 16.0 14.0 5~6 22.4 16.0 6~10 28.0…
-
HEX inlet temperature
Coose HEX inlet temperature from chart below depending on TC. Heating Hex inlet temperature( ℃) TC(℃) SC Condensor outlet temperature Condensor suction air temperature 15K TC-15 0℃DB / -2.9℃WB Calculate the capacity of connectable AHU units using the “Unit capacity” in the table above. (2) Heat…
-
Cautions for installing LEV-kit Installation environment Avoid locations in direct sunlight. Installation angle Install the motor above the horizontal. Pipe size Φ9.52 (Brazing) Use two LEVs when installing AH250. Connect two LEVs in parallel, and connect them to the appropriate refrigerant pipe…
-
- of AHU which is running heating operation using the heater for heating operation will temporarily drop. In controlling the suction/return air temperature, capacity control is affected by the outdoor temperature. When the outdoor temperature drops, the discharge temperature also drops. Take proper…
-
Operation signal
L1: Operation display lamp (field supply) Display power source: DC30V 1A, AC100V/200V 1A Error signal L2: Error display lamp (field supply) Display power source: DC30V 1A, AC100V/200V 1A If error resets (stop operation) and restart operations are repeatedly performed, the Compressor may be damaged…
-
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable CVV : PV insulated PVC sheathed control cable 6. Related cautions (1) Installation work Secure enough service space for replacement of the LEV and the thermistor. After an AHU controller is installed, address setting and unit capacity…
-
External Dimension
-
Electrical Wiring Diagram
WYN C0-8940 16/16