Инструкция на Контроллеры секций охлаждения мультизональных VRF-систем CITY MULTI
Контроллеры секций охлаждения серии PAC-AH125, 140, 250M-H. Инструкция по монтажу.
Смотрите также: Технические характеристики →
Загружаем документ…
Текст инструкции
-
Air Handling Unit Controller
GB PAC-AH125, 140, 250M-H FOR INSTALLER INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the controller. WT04980X02-cover_GB 2 12/1/06, 11:57 AM
-
[Fig. 2.0.1] Controller 2 LEV-kit 3 Thermistor 4 Clip 5 Insulation 6 Tie band 7 Installation manual 8 Tube 3 [Fig. 3.0.1] C B D E A L K H I F G J A Air handling unit controller (PAC-AH · M-H) B Air handling unit (field supply) C Controller (field supply) D Outdoor unit E Heat exchanger (field…
-
• 1.3. Before getting installed • Caution: • • 1.4. Before getting installed (moved) - electrical work • 1.5. Before starting the test run Caution: • • • Caution: • • • Ground the unit. - Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper…
-
3. System component
[Fig. 3.0.1] (P.2) A 3.1.3 B Air handling unit (field supply) C Controller (field supply) D Outdoor unit E Heat exchanger (field supply) F Gas pipe G Liquid pipe H LEV-kit I Thermistor (gas pipe) J Thermistor (liquid pipe) K Thermistor (suction air) L Thermistor (discharge air) Select the heat…
-
4. Selecting an installation site and installing the controller
• Avoid locations in direct sunlight. • Avoid locations exposed to stream or oil vapour. • Avoid locations where combustible gas may leak, settle or be generated. • Avoid installation near machines emitting high-frequency waves. • Avoid places where acidic solutions are frequently handled. • Avoid…
-
Thermistor for gas pipe 6.3.2 Put the thermistor as close as possible to the branch pipe that is located the closest to the gas pipe (header) connection on the evaporator (field supply). Turn the lead wire of the thermistor downward, and wind the aluminum tape (field supply) around the header to fix…
-
Pull box
7.3.2 [Selecting non-fuse breaker (NF) or earth leakage breaker (NV)] To select NF or NV instead of a combination of Class B fuse with switch, use the following: • In the case of Class B fuse rated 15 A or 20 A, NF model name (MITSUBISHI): NF30-CS (15 A) (20 A) NV model name (MITSUBISHI): NV30-CA…
-
Defrost signal D31
X D32 X: Relay (field supply) AC208~240 V 1 A 7.5. External I/O specifications Caution: A defrost signal is output in defrosting. Be careful to miscarriage lines because over AC200 V is impressed in ON. Notes: • After connecting each wire to the terminal, tighten each nut tightly through which the…
-
8.3. Setting temperature control
8.4. Dip-switch function 1 Thermostat condition in controlling the discharge air temperature 1 Change of discharge or suction air temperature control 2 Thermostat condition in controlling the suction/return air temperature TH21: Suction/Return air temperature TH24: Suction air temperature To: The…
-
This product is designed and intended for use in the residential, commercial and light-industrial environment. The product at hand is based on the following EU regulations: • • Low Voltage Directive 73/23/EEC Electromagnetic Compatibility Directive 89/ 336/EEC Please be sure to put the contact…