R 28 - B 28
ISTRUZIONI PER L’INSTALLATORE E IL MANUTENTORE INSTALLATION AND SERVICING MANUAL
-
http://www.unicalag.it/prodotti/domestico-50/condensazione-gas/1335/kutter-b
-
INFORMAZIONI GENERALI 1.1 - avvertenze generali Il libretto d’istruzioni costituisce parte integrante ed essenziale del prodotto e dovrà essere conservato dall’utente. Leggere attentamente le avvertenze contenute nel libretto in quanto forniscono importanti indicazioni riguardanti la sicurezza di…
-
1.2 - SIMBOLOGIA UTILIZZATA NEL MANUALE
Nella lettura di questo manuale, particolare attenzione deve essere posta alle parti contrassegnate dai simboli rappresentati: PERICOLO! Grave pericolo per l’incolumità e la vita ATTENZIONE! Possibile situazione pericolosa per il prodotto e l’ambiente NOTA! Suggerimenti per l’utenza NOTA! Per…
-
1.5 - AVVERTENZE PER LA SICUREZZA
Attenzione! L’apparecchio non puo’ essere utilizzato da bambini. L’apparecchio puo’ essere utilizzato da persone adulte e solo dopo avere letto attentamente il manuale di istruzione d’uso per l’utente. I bambini devono essere sorvegliati affinchè non giochino o manomettano l’apparecchio. Attenzione!…
-
La targhetta dati tecnici è posta all’interno della caldaia sullo schienale
nella parte inferiore. LEGENDA: 1 = Ente di sorveglianza CE 2 = Tipo di caldaia 3 = Modello caldaia 5 = (S.N°) Matricola 6 = P.I.N. Numero Identificativo del Prodotto 7 = Tipi di configurazioni scarico fumi approvati 8 = (NOx) Classe di NOx A = Caratteristiche circuito riscaldamento 9 = (Pn) Potenza…
-
1.7 - TRATTAMENTO DELL’ACQUA
Il trattamento delle acque di alimentazione consente di prevenire gli inconvenienti e mantenere funzionalità ed efficienza del generatore nel tempo. Il valore di pH ideale dell’acqua negli impianti di riscaldamento deve essere compreso: VALORE PH Durezza [°fr] MIN 6,5 9 MAX 8 15 Per minimizzare la…
-
nb
-
CARATTERISTICHE TECNICHE
E DIMENSIONI NOTA! 2.1 - CARATTERISTICHE TECNICHE Per maggiori informazioni consultare Info Tecniche dal sito 2.2 - VISTA CON L’INDICAZIONE DEI COMPONENTI PRINCIPALI E DIMENSIONI KUTter R 28 10
-
ONVIIVLI
-
Sb
-
N°
C.E. 3 4 S.E. Descrizione VG Fd 5 46 An Anodo Vaso di espansione riscaldamento Termostato di sicurezza C G Uscita acqua calda sanitaria Ingresso gas F Ingresso acqua fredda M Mandata impianto riscaldamento Ritorno impianto riscaldamento 10 HL TL 11 Hb SR 12 Ht P 13 Lp DK 18 Sensore di temperatura…
-
2.3 - DIAGRAMMA PORTATA/PRESSIONE DISPONIBILE PER L’INSTALLAZIONE
-
CIRCOLATORE MANDATA IMPIANTO - SOLO PER KUTter B
A valle del compensatore idraulico, le caldaie sono fornite di un circolatore di rilancio all’impianto di tipo elettronico a basso consumo, le cui caratteristiche di portata / prevalenza sono riportate nei grafici indicati a lato. Valore prevalenza Differenza di pressione variabile (Δp-v) Curva…
-
Prevalenza (mH2O)
Portata (l/h) Caratteristiche Tecnhiche Prevalenza (mH2O) 2.3.1 - DIAGRAMMA PORTATA/PRESSIONE DISPONIBILE PER L’INSTALLAZIONE Portata (l/h) 17
-
2.3.2 - PRODUZIONE ACQUA CALDA SANITARIA KUTTER B 28 47 °C 15 °C 12 l/min. Tempo (sec) 2.4 - DATI DI FUNZIONAMENTO SECONDO UNI 10348 Per i dati di regolazione: UGELLI - PRESSIONI - DIAFRAMMI - PORTATE - CONSUMI, fare riferimento al paragrafo ADATTAMENTO ALL’UTILIZZO DI ALTRI GAS. Portata termica…
-
A
A - B KUTTER R 28 Categoria apparecchio II2H3P Portata minima del circuito di riscaldamento (∆t 20 °C) l/min 2,97 Pressione minima del circuito di riscaldamento bar 0,5 Pressione massima del circuito di riscaldamento bar 3 Contenuto circuito primario l 2,2 Temperatura massima funzionamento in…
-
ISTRUZIONI PER L’INSTALLAZIONE 3.1 - AVVERTENZE GENERALI ATTENZIONE! Questa caldaia deve essere destinata solo all’uso per il quale è stata espressamente prevista. Ogni altro uso è da considerarsi improprio e quindi pericoloso. Questa caldaia serve a riscaldare acqua ad una temperatura inferiore a…
-
3.4 - IMBALLO
Gli elementi dell’imballo (scatola di cartone, reggette, sacchetti di plastica, etc.) non devono essere lasciati alla portata dei bambini in quanto potenziali fonti di pericolo. Il costruttore declina ogni responsabilità nel caso di danni procurati a persone, animali o cose subentranti in seguito a…
-
3.5 - POSIZIONAMENTO DELLA CALDAIA
Nella scelta del luogo di installazione della caldaia attenersi alle seguenti indicazioni di sicurezza: - Collocare la caldaia in locali protetti dal gelo. - Evitare l’installazione in locali con atmosfera corrosiva o molto polverosa. - Tenere in considerazione il peso dell’apparecchio con il…
-
Scond = Scarico condensa
-
3.6 - ALLACCIAMENTO CONDOTTO SCARICO FUMI (per Caldaie a tiraggio forzato)
-
C63
Caldaia destinata ad essere collegata ad un sistema di adduzione di aria comburente ed evacuazione dei prodotti della combustione approvato e venduto separatamente. B23P I TA L I A N O C63x ATTENZIONE: La canna fumaria / camino deve essere conforme alle norme vigenti. C83x C83 LUNGHEZZA TOTALE (…
-
INFORMAZIONI GENERALI SUL SISTEMA DI SCARICO FUMI
Attenzione: Per configurazioni di scarico - COASSIALI Ø 60/100 montare il tappo di chiusura sul foro A aspirazione e utilizzare il foro S - SDOPPIATI Ø 80 utilizzare i fori A Aspirazione - S Scarico KUTter B KUTter R Tappo di ispezione corpo in alluminio per manutenzione. Si consiglia di utilizzare…
-
3.7 - ALLACCIAMENTO
Avvertendo odore di gas: a) Non azionare interruttori elettrici, il telefono o qualsiasi altro oggetto che possa provocare scintille; b) Aprire immediatamente porte e finestre per creare una corrente d’aria che purifichi il locale; c) Chiudere i rubinetti del gas. M R MANDATA RITORNO 3/4’’ 3/4’’ C F…
-
KUTter R
La pressione nella rete di alimentazione (acquedotto) deve essere compresa tra 1 e 3 bar (nel caso di pressioni superiori è necessario installare un riduttore di pressione). 28
-
NOTA!
Per maggiori informazioni consultare Info Tecniche dal sito Vista di Fianco Istruzioni per l’installazione Vista di Fronte Il collegamento fra apparecchio e l’impianto smaltimento reflui domestici deve essere realizzato nel rispetto delle specifiche norme di riferimento. (*) Nel caso in cui il tubo…
-
3.8 - RIEMPIMENTO DELL’IMPIANTO
Attenzione! Non miscelare l’acqua del riscaldamento con sostanze antigelo o anticorrosione in errate concentrazioni! Può danneggiare le guarnizioni e provocare l’insorgere di rumori durante il funzionamento. Il costruttore declina ogni responsabilità nel caso danni procurati a persone, animali o…
-
3.9 - ALLACCIAMENTI ELETTRICI
I TA L I A N O Pericolo! L’installazione elettrica deve essere eseguita solo a cura di un tecnico abilitato. Prima di eseguire i collegamenti o qualsiasi operazione sulle parti elettriche, disinserire sempre l’alimentazione elettrica e assicurarsi che non possa essere accidentalmente reinserita.…
-
Collegamento termostato
ambiente ON/OFF (*) Collegamento termostato ambiente modulante RT/OT (*) - Rimuovere il ponticello e col- - Collegare il cavo del termostato modulante tra i morsetti TA1/OT legare i cavi del termostato dopo aver rimosso il ponticello ambiente tra i morsetti TA 2. da TA 2. Collegamento alimentazione…
-
3.10 - PRIMA ACCENSIONE
in seguito a mancata osservanza di quanto sopra esposto. I TA L I A N O La prima accensione deve essere effettuata da personale professionalmente qualificato. Il costruttore declina ogni responsabilità nel caso danni procurati a persone, animali o cose, subentranti Prima della messa in funzione…
-
3.11 - MISURA IN OPERA DEL RENDIMENTO DI COMBUSTIONE
3.11.1- ATTIVAZIONE DELLA funzione di taratura ATTENZIONE! Funzione riservata esclusivamente ai Centri di Assistenza Autorizzati. 1 L’utente NON è autorizzato all’attivazione della funzione di seguito descritta. 3 ATTIVAZIONE MINIMA POTENZA Premendo il pulsante (D) per 3 secondi, si attiva la…
-
Attenzione, durante queste operazioni
non effettuare prelievi in sanitario. Tutte le caldaie escono di fabbrica già tarate e collaudate, nel caso sia necessario eseguire la ritaratura della valvola gas: - Rimuovere il tappo ed inserire la sonda di analisi della CO2 nella presa fumi del terminale aspirazione/scarico, vedi cap. 3.11.2.…
-
TABELLA UGELLI - PRESSIONI - PORTATE
Controllare spesso i livelli di CO2 specialmente alle basse portate. sono riferiti con camera di combustione chiusa. KUTTER B 28 Tipo di Gas Potenza Utile [kW] Portata Termica [kW] risc. Press. Aliment. [mbar] Velocità ventilatore [rpm] min max Diaframma collettore [Ø/n.fori] Livelli CO2 Consumi…
-
L’utente NON è autorizzato all’attivazione della
funzione di seguito descritta. E’ possibile regolare la portata termica massima in riscaldamento, diminuendo il valore di Potenza percentuale del bruciatore. Agire sul parametro HP (par. 4.2 parametri modificabili da pannello comandi) per ottenere il valore corrispondente alla potenza desiderata.…
-
ISPEZIONI E
MANUTENZIONE Ispezioni e manutenzioni effettuate a regola d’arte ed ad intervalli regolari, nonché l’utilizzo esclusivo di pezzi di ricambio originali sono di primaria importanza per un funzionamento esente da anomalie ed una garanzia di lunga durata della caldaia. La manutenzione annuale…
-
OPERAZIONI DI VERIFICA ANNUALE ORDINARIA
COMPONENTE: VERIFICARE: VG (Valvola Gas) ( 3 ) SR (sensore riscaldamento)( 11 ) I sensori mantengono le SS (sensore sanitario) ( 1 ) caratteristiche d’origine? - KUTter B SSR (sensore ritorno) ( 22 ) I TA L I A N O An (Anodo in magnesio) - KUTter B - METODO DI CONTROLLO/INTERVENTO: L’anodo è in…
-
4.2 - PARAMETRI MODIFICABILI DA PANNELLO COMANDI
ATTENZIONE! Funzione riservata esclusivamente ai Centri di Assistenza Autorizzati. Alcuni parametri di servizio possono essere modifcati dal pannello comandi: 1 ATTIVAZIONE DA 0 PRERISCALDO VALORI A STANDARD 1 0 Premendo il pulsante (D) per 10 secondi, si attiva la funzione quando la chiave compare…
-
DISATTIVAZIONE
Per uscire dall’elenco parametri attendere 20” o ruotare rapidamente la manopola sanitaria ‘‘C’’. - Accedere alla scheda di modulazione contenuta nel quadro elettrico e posizionare il jumper nella posizione corrispondente al nuovo tipo di gas indicata in figura; 4.3 - ADATTAMENTO ALL’UTILIZZO DI…
-
4.4 - NOTE IMPORTANTI
NOTA Il pressostato di sicurezza contro la mancanza d’acqua non dà il consenso elettrico per la partenza del bruciatore quando la pressione è inferiore a 0,4 bar. La pressione dell’acqua nell’impianto di riscaldamento non deve essere inferiore a 0,8/1 bar; in difetto, agire sul rubinetto di carico…
-
VIOLA
LEGENDA A1 A9 CMP DK E. ACC./RIL MVD PDC PR SR Connettori servizi Controllo pompa modulante Pressostato sicurezza mancanza acqua Elettrodo accensione/rilevazione Motore valvola deviatrice (solo B) Pompa di caldaia Pompa riscaldamento (impianto) Sensore riscaldamento mandata SRR SS TL TLC VG VM SE…
-
4.6 - CODICI DI ERRORE
ll simbolo lampeggia sul video display quando la caldaia rileva una anomalia. service 1) In caso di anomalia che non provoca il fermo della caldaia, per visualizzare il codice di errore è necessario premere il tasto di sblocco; nel caso la caldaia sia in stand-by il codice di errore compare in modo…
-
VELOCITA’ FUORI
Verificare il funzionamento del CONTROLLO ventilatore (18) e le connesAlterazione della velocità ven- sioni tilatore la velocità non viene raggiunta. VELOCITA’ FUORI Verificare il funzionamento del CONTROLLO ventilatore (18) e le connesAlterazione della velocità ven- sioni tilatore la velocità e’…
-
14 PARAMETRI DI FABBRICA Premere il tasto di sblocco se Alterazione dei parametri di l’anomalia non scompare, sofabbrica a causa di eventuali stituire la scheda interferenze elettromagnetiche BLOCCO Verificare l’alimentazione gas Mancanza gas o mancata ac- oppure il buon funzionamento censione…
-
http://www.unicalag.it/prodotti/domestico-50/condensazione-gas/1335/kutter-b
-
GENERAL INFORMATION 1.1 - general warnings The instruction booklet is an integral and essential part of the product and must be kept by the user. Read the warnings contained in this instruction booklet carefully as they provide important guidelines regarding installation, use and maintenance safety.…
-
1.2 - SYMBOLS USED IN THE MANUAL
Pay special attention when reading this manual to the parts marked by the symbols: DANGER! Serious danger to safety and health ATTENTION! Possible dangerous situation for the product and the environment NOTE! Tips for the user NOTE! For more information See Technical Info…
-
1.5 - SAFETY WARNINGS
Attention! The boiler cannot be used by children. The boiler can be used by adults and only after having carefully read the user’s manual. Children should be supervised to ensure that they do not play or tamper with the device. Attention! The appliance must be installed, adjusted and maintained by…
-
The technical data plate is located
inside the boiler on the back at the bottom KEY: 1 = CE monitoring body 2 = Type of boiler 3 = Boiler model 4 = Number of stars (directive 92/42 EEC) 5 = (S.N°) Serial Number 6 = P.I.N. Product Identification Number 7 = Types of approved flue gas exhaust configurations 8 = (NOx) NOx Class A =…
-
The technical data plate is located
inside the boiler on the back at the bottom KEY: 1 = CE monitoring body 2 = Type of boiler 3 = Boiler model 4 = Number of stars (directive 92/42 EEC) 5 = (S.N°) Serial Number 6 = P.I.N. Product Identification Number 7 = Types of approved flue gas exhaust configurations 8 = (NOx) NOx Class A =…
-
1.7 - WATER TREATMENT
The treatment of the supply water allows to prevent inconveniences and maintain the functionality and efficiency of the generator over time. The ideal water pH in heating systems must be within: VALUE PH Hardness [°fr] MIN 6.5 9 MAX 8 15 To minimise corrosion, it is crucial to use a corrosion…
-
a
-
TECHNICAL FEATURES
AND DIMENSIONS 2.1 - TECHNICAL FEATURES NOTE! For more information See Technical Info from site indicated at pag. 2 2.2 - VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS KUTter R 28 10
-
НМЗ
-
Sb
-
ВА 590 ~
-
N°
C.E. An Anode C G Domestic hot water outlet Gas inlet 5 E. Ignition/detection electrode ACC /RIL Burner 8 Expansion vessel F Cold water inlet M Heating system flow R Heating system return Rc Filling valve ReF Tap cold water inlet Ri Recirculation (Optional) Scond Condensation drain DN 32 Simp Boiler…
-
2.3 - FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION
Avaible Head (mH2O) meters of water 2.3.1 - FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION By-pass closed By-pass open Installation Instructions ENGLISH Pump - KUTter R Flow rate (l/h) 15
-
Flow system Pump - Only for KUTter B
Downstream of the hydraulic compensator, the boilers is provided of a flow system pump (relaunch), of electronic type with low consumption, the characteristics of which flow rate / head are shown in the graphs shown below. Pressure Head Value Differenza di pressione variabile (Δp-v) Variable…
-
Technical Features ENGLISH Avaible Head (mH2O) meters of water 2.3.1 - FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION Flow rate (l/h) Flow rate (l/h) 17
-
Withdrawal Temperature (°C)
2.3.2 - Production of Domestic Hot Water KUTTER B 28 47 °C 15 °C 12 l/min. Time (sec) 2.4 - OPERATING DATA ACCORDING TO UNI 10348 For the adjustment data: NOZZLES - PRESSURE - DIAGRAMS - FLOW RATES - CONSUMPTION refer to the paragraph ADAPTATION TO OTHER TYPES OF GAS. Nominal heat input in CH / DHW…
-
Symbol
Pnominale Nominal Heat Output Seasonal space heating energy ƞs efficiency Seasonal efficiency class in heating mode For CH only and combination boilers: useful heat output Useful Heat Output in high-temperature regime P4 (Tr 60 °C / Tm 80 °C) Useful efficiency at nom. heat output 4 in…
-
INSTALLATION INSTRUCTIONS 3.1 - GENERAL WARNINGS ATTENTION! This boiler is intended solely for the use for which it was expressly designed. Any other use is to be considered improper and therefore dangerous. This boiler heats water at a temperature lower than the atmospheric pressure boiling…
-
3.4 - PACKAGING
The packaging elements (cardboard box, straps, plastic bags, etc.) must be kept out of the reach of children as they are potential sources of danger. Unical AG S.p.A. will not be held liable for damage to persons, animals or objects due to failure to comply with the instruction above. A…
-
3.5 - POSITIONING THE BOILER
When choosing the place of the installation of the boiler, follow the safety instructions below: - Place the boiler in rooms protected from frost. - Avoid installation in rooms with a corrosive or very dusty atmosphere. - Consider the weight of the boiler with it’s water content. - Avoid placement…
-
Caution
Scond = Condensate drain Check the drainage natural or forced depending of the heigh of drainage outlet (see par.3.7) Installation Instructions ENGLISH KUTter R 23
-
3.6 - FLUE GAS EXHAUST PIPE CONNECTION FOR BOILERS WITH FORCED DRAUGHT
To connect the flue gas exhaust pipe, local and national standards must be observed In the event the boiler is replaced, ALWAYS re- place the flue gas pipe as well. The boiler is type approved for the exhaust configurations listed below: C13x C43x C13 % Slope towards inlet = 3% TOTAL LENGTH (LA…
-
C63x
C63 B23P Boiler intended for connection to a combustion air intake and combustion products evacuation system, approved and sold separately C83x ENGLISH ATTENTION: The flue must comply with standards in force. C83 TOTAL LENGTH (LS) DOUBLE Ø80 FROM [m] TO [m] 1 30 Connection to a combustion products…
-
Caution
Flow configurations - Coaxial Ø 60/100 mount the cap on the hole A suction and use the S hole - Twin Ø 80 use holes A suction - S Exhaust KUTter B KUTter R Rubber cap for inspection to aluminium exchanger NOTE! For further details relating to pressure drops of the individual components, for…
-
3.7 - CONNECTION
3/4’’ Danger! The gas connection must be carried out only by a qualified installer who must respect and apply that foreseen by relevant laws in force in the local prescriptions of the supply company. Incorrect installation can cause damage to persons, animals and objects for which the manufacturer…
-
KUTter R
The mains pressure (acqueduct) must be within 1 and 3 bar (in the event of greater pressure is necessary to install a pressure reducer). 28
-
The connection between the appliance
and the domestic waste system must be made in compliance with the specific reference standards. NOTE! For more information See Technical Info from site indicated at pag. 2 Danger! Before commissioning the appliance: - check that the trap is assembled properly (H = 190 mm) - fill the trap and check…
-
3.8 - FILLING THE SYSTEM
Attention! Do not mix the heating water with incorrect concentrations of antifreeze or anti-corrosion substances! This could damage the gaskets and cause noise during operation. The manufacturer will not be held liable for damage to persons, animals or objects due to failure to comply with the above…
-
3.9 - ELECTRICAL CONNECTIONS
ENGLISH Danger! Only a qualified technician may perform the electrical installation. Before performing connections or any type of operation on electrical parts, always disconnect electrical power and make sure that it cannot be reconnected accidentally. Back view Outputs electrical connections…
-
External probe
connection (*) ON/OFF room thermostat connection (*) ON/OFF room thermostat connection RT/OT (*) - Remove the jumper and connect the room thermostat wires between terminals TA 2. - Connect the modulating thermostat - Predisposed on the terminal wire between terminals TA1/OT board, terminals SE after…
-
3.10 - COMMISSIONING
Commissioning must be done by professionally qualified personnel. The manufacturer will not be held liable for damage to persons, animals or objects due to failure to comply with the above instruction. Before commissioning the boiler, check that: does the installation meet the specific standards and…
-
3.11 - MEASUREMENT OF COMBUSTION EFFICIENCY DURING INSTALLATION
3.11.1- ACTIVATION OF THE calibration function ATTENTION! Function reserved for Authorised Assistance Centres only. 1 ACTIVATION The user is NOT authorised to activate the function described below. 3 MINIMUM OUTPUT By pressing the button (D) for 3 seconds, the calibration function is activated.…
-
Attention, during these operations do not take
any samples in domestic hot water mode. All boilers leave the factory already calibrated and tested, however in the event the gas valve recalibration is required: 1) Maximum output adjustment - Operate the boiler in “calibration” mode at MAXIMUM OUTPUT (see 3.11.1) - Once the burner is on check that…
-
NOZZLES - PRESSURE - FLOW RATES TABLE
Check the levels of CO2 often, especially with low flow rates. They refer to the boiler with a closed combustion chamber. KUTTER B 28 Type of Gas Effective Output [kW] Heating Thermal [kW] Capacity Supply Press. [mbar] Fan speed [rpm] min max Collector diaphragm [Ø/n. holes] CO2 levels [%]…
-
3.12.1 - ADAPTATION OF THE POWER TO THE HEATING SYSTEM
The user is NOT authorised to activate the function described below. It is possible to adjust the maximum thermal capacity in heating mode, by decreasing the burner output value. Act on parameter HP (par. 4.2 parameters that can be edited from control panel) to achieve the value corresponding to the…
-
INSPECTION AND
MAINTENANCE Inspections and maintenance performed professionally and according to a regular schedule, as well as the use of original spare parts, are of the utmost importance for fault-free operation of the boiler and to guarantee its long life. Yearly maintenance of the appliance is mandatory in…
-
ROUTINE YEARLY VERIFICATION OPERATIONS
COMPONENT: VERIFY: VG (Gas valve) ( 3 ) SR (heating sensor) ( 11 ) Do the sensors maintain the origiSS (domestic hot water sensor) nal characteristics? ( 1 ) - KUTter B SSR (heating sensor return) ( 22 ) 12571 ohm at 20° C / 1762 ohm at 70° C. Measurement to be taken with the wires disconnected (see…
-
4.2 - PARAMETERS THAT CAN BE EDITED FROM THE CONTROL PANEL
ATTENTION! Function reserved to. Authorised Assistance Centres only. Some service parameters can be edited from the control panel: 1 ACTIVATION FROM 0 PREHEATING VALUES TO 1 DEFAULT 0 By pressing the button (D) for 10 seconds, the function is activated when the key flashes on the display 2 SELECTION…
-
DISABLING
To exit the parameters list wait for 20” or quickly turn the domestic hot water knob ‘‘C’’. - Access the modulation board contained in the electric panel and position the jumper in the position corresponding to the new type of gas indicated in the figure; ENGLISH 7 4.3 - ADAPTATION TO THE USE OF…
-
4.4 - IMPORTANT NOTES
NOTE The safety pressure switch against lack of water does not give electric consent for burner start when the pressure is below 0.4 bar. The water pressure in the heating system must not drop below 0.8/1 bar; open the filling tap on the boiler when the pressure is too low. This operation must be…
-
KEY
A1 A9 CMP DK E. ACC./RIL MVD P SR Services connectors Modulating pump control Water deficiency safety pressure switch Ignition/detection electrode Diverter valve motor (ONLY B) Pump Flow heating sensor SRR SS TL TLC VG VM SE TA1 / OT TA2 Return heating sensor Domestic hot water probe (Pred. for R…
-
4.6 - ERROR CODES
The symbol flashes on the display monitor when the boiler detects an anomaly. service 1) In the event of an anomaly that does not stop boiler operation, press the unblock key to display the error code; in the event the boiler is in stand-by, the error code appears and remains fixed on the display.…
-
SPEED OUT OF Check fan operation (18) and CONTROL the connections. Alteration of the fan speed; the speed is not reached. SPEED OUT OF Check fan operation (18) and CONTROL the connections. Alteration of the fan speed; the speed is above that requested. HIGH TEMPERATURE Boiler temperature too high. 8…
-
BLOCK Check the gas supply or that No gas or failed burner ignition. the ignition/detection electrode is working properly (4). 11 16 PARASITE FLAME Flame detected upon ignition. CHIMNEY Check the wiring of the Ign/Det. electrode and remove any oxidation, check for humidity between drain wire and…
-
00335776 - 1st ed. 02/16