Инструкция на Кондиционеры настенные Toshiba серии RAS...PKVSG-E
Настенная сплит-система Toshiba серии PKVSG-E: RAS-10, 13, 16PKVSG-E /RAS-10, 13, 16PAVSG-E. Инструкция по монтажу.
Загружаем документ…
Текст инструкции
-
R32
INSTALLATION MANUAL AIR CONDITIONER (SPLIT TYPE) ENGLISH Indoor unit RAS-10, 13, 16PKVSG-E Outdoor unit RAS-10, 13, 16PAVSG-E 1118350194-1
-
PRECAUTIONS FOR SAFETY
Read the precautions in this manual carefully before operating the unit. This appliance is filled with R32. • Before installation, please read these precautions for safety carefully. • Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown…
-
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY. • TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. • CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE…
-
• Do not use any refrigerant different from the one specified for complement or
replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body. • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. •…
-
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. • Do not install the unit at place where leakage of flammable gas may…
-
ACCESSORY PARTS
Indoor Unit No. Part name No. 2 1 Wireless remote control × 1 Installation Plate × 1 3 Part name ES 4 Battery × 2 Remote control holder × Mounting screw × 6 Toshiba new IAQ filter × 1 EN FR IT DE 8 7 Flat head wood screw × 2 Owner’s Manual × 1 PT PL ! 9 Flat head wood screw × 1 Installation Manual ×…
-
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
65 mm or more For the rear left and left piping 300 mm Wall Hook or m ore 1 Installation plate 300 Flat head wood screw Hoo 7 mm Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation. or m ore k The auxiliary piping can be connected to the left, rear…
-
INDOOR UNIT
When the installation plate is directly mounted on the wall Installation Place 1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit. 2. To mount the installation plate on a concrete wall with anchor bolts, use the anchor bolt…
-
Front panel
Control wire 1 Control wire Screw (Ø3.1×16L) for hang remote controller Hole for hang remote controller Remote controller Wall Screw Screw Remote controller Screw cap 70 mm 2 8 * Wire size 28-22AWG or 0.08-0.32 mm2 Outer diameter not over 4.7 mm, control wire length 30 m. or less. 3 Screw (Ø3.1×25L)…
-
How to remove the drain hose
• The drain hose can be removed by removing the screw securing the drain hose and then pulling out the drain hose. • When removing the drain hose, be careful of any sharp edges of steel plate. The edges can injuries. • To install the drain hose, insert the drain hose firmly until the connection part…
-
2. Put water in the drain pan and make sure that the water is drained out of
doors. 3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe. CAUTION Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping. Shield pipe Drain hose Inside the room This air conditioner has the…
-
• Tightening torque of flare pipe connections
The operating pressure of R32 is higher than that of R22 (approx. 1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but…
-
ELECTRICAL WORKS
The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow the instruction as following. Model RAS-10PKVSG-E Power source RAS-13PKVSG-E RAS-16PKVSG-E 50Hz, 220 – 240 V Single phase Maximum running current…
-
Power Supply and Connecting Cable Connection
Power Supply Input at Indoor Unit Terminal Block (Recommend) Indoor Unit Power supply cable Outdoor Unit Stripping length of the power supply cable Power supply cable connect to L N Terminal block (L N 1 2 3) Terminal block Earth line EN 50 mm 10 mm N L Earth line Connecting cable 10 mm 70 mm Earth…
-
Power Supply Input Wiring Diagram
Power supply input at Indoor unit Terminal Block (Recommend) Indoor Terminal Block Power supply input CHASSIS INDOOR UNIT OUTDOOR UNIT Outdoor Terminal Block CHASSIS EARTH Power supply input at Outdoor unit Terminal Block (Optional) Indoor Terminal Block CHASSIS INDOOR UNIT OUTDOOR UNIT Outdoor…
-
OTHERS
Gas Leak Test Test Operation To switch the TEST RUN (COOL) mode, press [RESET] button for 10 seconds. (The beeper will make a short beep.) Check places for the indoor unit. EN ES FR OPERATION / RESET Button Check places for the outdoor unit. DE Auto Restart Setting • Check the flare nut connections…
-
R22 R32, R410A 0.8 Ø6.4 0.8 Ø9.5 0.8 Ø12.7 3. When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and the pipes were not repaired and refilled. y There is the possibility of rain water or air, including moisture, entering the pipe. 4. When refrigerant cannot…