+00A08-010_01EN_SVM_HighWallHeatPump.book Page 1 Wednesday, March 4, 2009 11:22 AM
FILE NO. A08-010 AIR-CONDITIONER (SPLIT TYPE) SERVICE MANUAL Model name: Indoor Unit Outdoor Unit <High Wall, Heat Pump Type> <Heat Pump Type> (Standard Type) (Standard Type) RAS-07PKVP-E RAS-10PKVP-E RAS-13PKVP-E RAS-16PKVP-E RAS-18PKVP-E RAS-07PAVP-E RAS-10PAVP-E RAS-13PAVP-E RAS-16PAVP-E…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 2 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Contents SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 3 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-10-1. Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 8-10-2. Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 4 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-22-1. Parts Name of Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 8-22-2. Name and Functions of Indications on Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . 55 8-23. Hi POWER…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 5 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type SAFETY PRECAUTIONS The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 6 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type CAUTION TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY A switch or circuit breaker that can disconnect all poles must be included in the fixed wiring. Be sure to use an approved circuit breaker or switch. DANGER • ASK AN AUTHORIZED DEALER OR QUALIFIED…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 7 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type CAUTION • Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water. • Do not install in a place that can increase the vibration of the unit. Do not install in…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 8 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 1 SPECIFICATIONS 1-1. Specifications RAS-07PKVP-E/RAS-10PKVP-E/RAS-13PKVP-E, RAS-07PAVP-E/RAS-10PAVP-E/RAS-13PAVP-E RAS-07PKVP-ND/RAS-10PKVP-ND/RAS-13PKVP-ND, RAS-07PAVP-ND/RAS-10PAVP-ND/ RAS-13PAVP-ND Unit model Indoor RAS-07PKVP-E(-ND) RAS-10PKVP-E(-ND)…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 9 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type RAS-16PKVP-E/RAS-18PKVP-E, RAS-16PAVP-E/RAS-18PAVP-E RAS-16PKVP-ND/RAS-18PKVP-ND, RAS-16PAVP-ND/RAS-18PAVP-ND Unit model Indoor RAS-16PKVP-E(-ND) RAS-18PKVP-E(-ND) Outdoor RAS-16PAVP-E(-ND) RAS-18PAVP-E(-ND) Cooling capacity (kW) 4.5 5.0 Cooling capacity…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 10 Wednesday, March 4, 2009 11:22 AM
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 11 Wednesday, March 4, 2009 11:22 AM
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 12 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 1-3. Capacity Variation Ratio According to Temperature Capacity ratio (%) Capacity ratio (%) RAS-07PKVP-E(-ND), RAS-10PKVP-E(-ND), RAS-13PKVP-E(-ND) Cooling Heating Conditions Outdoor temperature (°C) Capacity ratio (%) Capacity ratio (%) Conditions Outdoor…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 13 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2 REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 14 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2-2. Refrigerant Piping Installation 2-2-1. Piping Materials and Joints Used For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 15 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Flare processing procedures and precautions 1) Cutting the Pipe By means of a pipe cutter, slowly cut the pipe so that it is not deformed. 2) Removing Burrs and Chips If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 16 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Table 2-2-6 Flare and flare nut dimensions for R22 Dimension (mm) Nominal diameter Outer diameter (mm) Thickness (mm) 1/4 6.35 0.8 9.0 9.2 6.5 13 17 3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.4 19.0 16.0 23 27 3/4…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 17 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2-3. Tools 2-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 18 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2-4. Recharging Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 19 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type NOTE NOTE • Be sure to make setting so that liquid can be charged. • When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 20 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2-5. Brazing of Pipes Types of flux • Non corrosive flux Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800°C. • Activated flux Most of fluxes generally used for silver brazing are…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 21 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Brazing method to prevent oxidation 1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder. 2) Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder. 3) Apply a seal onto the clearance between the piping…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 22 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 3 CONSTRUCTION VIEWS 3-1. Indoor Unit RAS-07PKVP-E, RAS-10PKVP-E, RAS-13PKVP-E, RAS-16PKVP-E, RAS-18PKVP-E RAS-07PKVP-ND, RAS-10PKVP-ND, RAS-13PKVP-ND, RAS-16PKVP-ND, RAS-18PKVP-ND (At the time of operation) 9 296.2 790 Moving panel Plasma ion charger Front…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 23 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 3-2. Outdoor Unit RAS-07PAVP-E, RAS-10PAVP-E RAS-07PAVP-ND, RAS-10PAVP-ND dia.11-14 U-shape hole (For dia.8-10 anchor bolt) Dia.11 ×14 long hole (For dia.8-10 anchor bolt) 8-dia.7 hole (For fixing outdoor unit) C L [B] leg part 483 di 21 a. Fan guard…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 24 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type RAS-13PAVP-E, RAS-16PAVP-E, RAS-18PAVP-E RAS-13PAVP-ND, RAS-16PAVP-ND, RAS-18PAVP-ND dia.11-14U-shape hole (For dia.8-10 anchor bolt) 600 320 Anchor bolt long hole pitch 306 26 dia.11x14 long hole (For dia.8-10 anchor bolt) dia.7 hole pitch 90 290 [A] leg…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 25 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 4 WIRING DIAGRAM REACTOR 4WAY VALVE COIL FOR SWITCHING COOLING AND HEATING P17 CN704 21 21 P16 (WHI) YEL RED (RED) 1 1 + ~ ~ - + - POWER RELAY MOSFET Q300 ~ Q305 F03 FUSE 250V ~ T3.15A + + - - CT DIODE BLOCK YEL P32 F04 FUSE 250V ~ 15A P.C.BOARD MCC-5070…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 26 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 5 SPECIFICATIONS OF ELECTRICAL PARTS 5-1. Indoor Unit RAS-07PKVP-E, RAS-10PKVP-E, RAS-13PKVP-E, RAS-16PKVP-E, RAS-18PKVP-E RAS-07PKVP-ND, RAS-10PKVP-ND, RAS-13PKVP-ND, RAS-16PKVP-ND, RAS-18PKVP-ND No. Parts name 1 Fan motor (for Indoor Unit) Room temp. sensor…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 27 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 6 REFRIGERANT CYCLE DIAGRAM 6-1. Refrigerant Cycle Diagram TA P Pressure measurement Gauge attaching port Vacuum pump connecting port V INDOOR UNIT TC Indoor heat exchanger T1 Temp. measurement Deoxidized copper pipe Outer dia.: 07PAVP-E(-ND) : 9.52mm…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 28 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 6-2. Operation Data Cooling Temperature condition (°C) Indoor Outdoor Model name RAS- 27/19 07PKVP-E 07PKVP-ND 10PKVP-E 10PKVP-ND 10PKVP-E 10PKVP-ND 16PKVP-E 16PKVP-ND 18PKVP-E 18PKVP-ND 35/– Standard pressure P (MPa) Heat exchanger pipe temp. T1 (°C) T2 (°C)…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 29 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 7 CONTROL BLOCK DIAGRAM 7-1. Indoor Unit RAS-07PKVP-E, RAS-10PKVP-E, RAS-13PKVP-E, RAS-16PKVP-E, RAS-18PKVP-E RAS-07PKVP-ND, RAS-10PKVP-ND, RAS-13PKVP-ND, RAS-16PKVP-ND, RAS-18PKVP-ND Humidity Sensor Indoor Unit Control Unit M.C.U. Louver Motor Heat Exchanger…
-
Heat exchanger
temp.sensor (TE) Suction temp. sensor (TS) Outdoor air temp. sensor (TO) Discharge temp. sensor (TD) M.C.U MCC5070 (P.C.B) Driver circuit of P.M.V. P.M.V. Relay circuit Freeze prevention heater 4-way valve Relay circuit 4-way valve Inverter (DC AC) Cooling/heating Comp. cylinder switching switching…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 31 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8 OPERATION DESCRIPTION 8-1. Outline of Air Conditioner Control • Judgment of inlet indoor heat exchanger temperature by using heat exchanger sensor (TCj sensor)(Super heat control etc.) • Judgment of suction air humidity of the indoor heat exchanger by using…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 32 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-2. Basic Operation 8-1-3. Contents of Operation Command Signal (Serial Signal) 8-2-1. Operation Control Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 33 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-2-2. Cooling/Heating Operation Remote controller Selection of operation conditions ON/OFF Control contents of remote controller • ON/OFF (Air conditioner/Air purifier) • Operation select (COOL/HEAT/AUTO/DRY) • Temperature setup • AIr direction • Swing • Air…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 34 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-3. Indoor Fan Motor Control 4) When AUTO operation has started within 2 hours after heating operation stopped and if the room temperature is 20°C or more, the fan operation is performed with ”Super Ultra LOW” mode for 3 minutes. Then, select an operation…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 35 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Table 8-3-1 Indoor fan air flow rate (Cooling, Dry) Fan speed level WF RAS-07PKVP-E RAS-07PKVP-ND RAS-10PKVP-E RAS-10PKVP-ND RAS-13PKVP-E RAS-13PKVP-ND Fan speed (rpm) Air flow rate (m3/h) Fan speed (rpm) Air flow rate (m3/h) Fan speed (rpm) Air flow rate…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 36 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-3-2. In Heating Operation 1) When setting the fan speed to L, L+, M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Fig. 3 and Table 8-3-2. 2) When setting the fan speed to AUTO on the remote controller…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 37 Wednesday, March 4, 2009 11:22 AM
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 38 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-5. Capacity Control Outdoor fan speed (rpm) 07PAVP-E 10PAVP-E 13PAVP-E 16PAVP-E 18PAVP-E Tap 07PAVP-ND 10PAVP-ND 13PAVP-ND 16PAVP-ND 18PAVP-ND f0 f1 f2 f3 f4 f5 f6 f7 f8 f9 fA fB fC fD fE fF The cooling or heating capacity depending on the load is adjusted.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 39 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-6. Current Release Control 8-7. Release Protective control by Temperature of Indoor Heat Exchanger This function prevents troubles on the electronic parts of the compressor driving inverter. This function also controls drive circuit of the compressor speed…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 40 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-8. Defrost Control (Only in Heating Operation) 8-7-2. In heating operation Prevent-overpressure control for refrigerating cycle This function removes frost adhered to the outdoor heat exchanger. The temperature sensor of the outdoor heat exchanger (TE…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 41 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-9. Louver Control 8-8-2. Finish of Defrost Operation 8-9-1. Louver Position Returning conditions from defrost operation to heating operation 1) Temperature of outdoor heat exchanger rises to +8°C or higher. 2) Temperature of outdoor heat exchanger is kept…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 42 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-10.SLEEP MODE Operation Louver position in dry operation Dry operation Horizontal blowing Inclined blowing Inclined blowing Inclined blowing Inclined blowing blowing downward PKVP PKVP PKVP PKVP PKVP W6 W5 +1 zone W4 5 W3 ± –1 zone (min 1) +6.5 +6.0 +5.5…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 43 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-11.Temporary Operation 8-10-2. Heating Operation When pushing [SLEEP MODE] button on the remote controller, a quiet and mild operation is performed by reducing the fan speed and the compressor speed. TA-Tsc [°C] 0 –0.5 –1.0 –1.5 –2.0 –2.5 –3.0 –4.0 –5.0…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 44 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-12.Air Purifying Control [3] Air purifier operates [4] Air conditioner + Air Purifier operation 8-12-1. Purpose Operation indicator OFF PURE indicator OFF PURE indicator OFF Air purifier OFF This function generates negative ion while cleaning the air in the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 45 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-13.Discharge Temperature Control 8-12-3. Operation The sequence that PURE indicator (Orange) is turned on are described in the following flowchart. 1) If the air purifying error input was detected by 5 times or under, turn on the purifier again approx. 10…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 46 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-14.Pulse Motor Valve (PMV) Control 8-15.Clean Operation This function controls throttle amount of the refrigerant in the refrigerating cycle. According to operating status of the air conditioner, this function controls the open degree of valve with an…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 47 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-15-4. Setting the Clean Operation Clean operation times Operation time Clean operation time No clean operation performed (0 minutes) Up to 10 minutes Cooling: AUTO (Cooling) Dry 10 minutes or longer 4 hours Heating: AUTO (Heating) No clean operation…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 48 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-16.Select Switch on Remote Controller 8-16-4. Setting the Remote Controller 1) Slide and open the remote controller cover and remove the batteries. 2) Cut the jumper wire inside the battery compartment using nippers. 8-16-1. Purpose This operation is to…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 49 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-17.Set Temperature Correction 5) Push the button of the remote controller that was set in step 1 to stop the air conditioner. (This operation will change the setting to “B”.) 6) Check that the remote controller operates the indoor unit. 8-17-1. Purpose When…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 50 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-18.Outdoor Quiet Control 8-19. 8°C HEAT Operation (-ND Model Only) 8-18-1. Purpose 8-19-1. Start 8°C HEAT Operation When the Air Conditioner is Stopped For the users who concern about noise of the outdoor unit, this control controls the maximum revolutions…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 51 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type During stop Push [8°C] button. Push [8°C] button. OPERATION lamp ON 8°C HEAT operation starts Shifts to [8°C] HEAT operation. Push [8°C] button. NO Do you stop 8°C HEAT operation? button When 8°C HEAT operation, the indoor fan control rises up automatically.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 52 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-21.Auto Restart Function 8-19-5. Compressor Speed Control This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 53 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type When the unit is operating The unit is in operation. When the unit is stand-by (Not operating) The green indicator is on. The unit is on standby. (Push [RESET] button for more than 3 seconds.) The unit stops operating. (Push [RESET] button for more than 3…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 54 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 7 Auto louver button (SWING) 8-22.Remote Controller and Its Functions Each time you press the SWING button, you can change the swing mode. (A receiving beep is heard.) (Vertical swing → Horizontal swing → Vertical and Horizontal swing → Stop swinging) Press…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 55 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-22-2. Name and Functions of Indications on Remote Controller Display All indications, except for the clock time indicator, are displayed by pushing the (MEMORY) indicator Flashes for 3 seconds when the MEMO button is pressed during operation. The mark is…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 56 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 8-23.Hi POWER Mode When [Hi POWER] button is pushed while the indoor unit is in Auto, Cooling or Heating operation, Hi POWER mark is indicated on the display of the remote controller and the unit operates according to the present operation mode as described…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 57 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9 INSTALLATION PROCEDURE 9-1. Installation Diagram of Indoor and Outdoor Uunits The indoor unit shall be installed so that the top of the indoor unit is positioned at least 2 m high. Also, avoid putting anything on the top of the indoor unit. For the rear…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 58 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-2. Optional Parts, Accessories and Tools 9-2-1. Optional Installation Parts Part Code Parts name Q’ty Refrigerant piping Gas side (Outer diameter) RAS-07PKVP-E, RAS-07PKVP-ND RAS-10PKVP-E, RAS-10PKVP-ND RAS-13PKVP-E, RAS-13PKVP-ND 6.35 mm 9.52 mm…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 59 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-2-3. Installation/Service Tools Changes in the product and components On air conditioners using R410A, in order to prevent any other refrigerant from being accidentally charged, the service port diameter size of the outdoor unit control valve (3 way valve)…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 60 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-3. Installation of Indoor Unit 1) Decide the installation plate mounting position on the wall. 2) Mark the corresponding pipe hole wall positions according to the positioning marks ( ) on the installation plate. 3) Drill the pipe holes (Dia. 65 mm or Dia.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 61 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 5) Insert the connecting cable fully into the terminal block and secure it tightly with screws. Make a loop with the earth wire under the terminal block and secure it with the earth screw. 6) Tightening torque: 1.2 N·m (0.12 kgf·m) 7) Secure the connecting…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 62 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 4) Attach the drain cap Insert hexagonal wrench (4 mm). NOTE • Connecting cable (Indoor unit/outdoor unit) • Wire type: H07RN-F or 60245IEC66 (1.0 mm2) 9-3-5. Piping and Drain Hose Installation 5) Firmly insert drain cap. Piping and drain hose forming No gap…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 63 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Piping on the bottom right or the bottom left CAUTION 1) After making slits on the front panel with a knife or similar tool, cut them out with a pair of nippers or an equivalent tool. • Bind the auxiliary pipes (two) and connecting cable with facing tape…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 64 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 3) When connecting extension drain hose, insulate the connection part of extension drain hose with shield pipe. • For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing the bottom up at the specified places.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 65 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-4. Installation of Outdoor Unit Snow protection plate Front 9-4-1. Installation Location Snow protection hood At least 50 cm • A place which provides enough space around the outdoor unit as shown in the diagram. • A place which can bear the weight of the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 66 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Projection margin in flaring: A (Unit: mm) 4) When water still leaks even after performing steps 1) and 2), add caulking material, putty or other sealants. Rigid (Clutch type) [8] Water-proof rubber caps (supplied with the outdoor unit) Outer diameter of…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 67 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 3) Open fully the low pressure side handle of the gauge manifold valve. 4) Operate the vacuum pump to begin evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters (15 minutes for 20 meters) (assuming a pump capacity of 27 litres…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 68 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Packed valve handling precautions Stripping length of connecting cable • Open the valve stem until it touches the stopper. Once it is in contact with the stopper, refrain from applying any more force than is necessary. • Securely tighten the valve stem cap…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 69 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-5. Test Operation CAUTION 9-5-1. Gas Leak Test • Incorrect wiring connection may cause electrical parts to burn out. • Be sure to comply with local regulations/codes when running the wire from outdoor unit to indoor unit. (Size of wire and wiring method…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 70 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-6. Removing the Main Parts 9-5-4. Select Switch on Remote Controller • If two indoor units are installed in the same room or adjoining rooms, when the user tries to operate only one unit, both units may receive the same remote controller signal and operate.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 71 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-6-2. Removing the Moving Panel 5) Pull out the moving panel towards the left side to remove. 1) 1. Open the moving panel, and support the moving panel by the panel support on the right side. 2) Remove the lead wire cover on the right side. (1 screw) 9-6-3.…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 72 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 9-6-4. Removing the Vertical Air Flow Louver 2) Secure the horizontal air flow louvres to the connector joints. Louver fixture CAUTION Connectors The horizontal air flow louvres cannot be released from the vertical air flow louver. Air flow louver 1) Open the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 73 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10 TROUBLESHOOTING The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 74 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type CAUTION A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other lowvoltage circuits. The sensor leads and other wires are covered with insulated tubes for protection. Nevertheless, care must be taken to…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 75 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-3.First Confirmation 10-3-1. Confirmation of Power Supply Confirm that the power breaker operates (ON) normally. 10-3-2. Confirmation of Power Voltage Confirm that power voltage is AC 220–230–240 ± 10%. If power voltage is not in this range, the unit may…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 76 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-5.Judgment by Flashing LED of Indoor Unit While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the contents of self-diagnosis are displayed with block on the indoor unit indication section. Table…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 77 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-6.Self-Diagnosis by Remote Controller (Check Code) • If the lamps are indicating B to E as shown on Table 10-5-1, execute the self-diagnosis by the remote controller. • When the remote controller is set to the service mode, the indoor controller diagnoses…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 78 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-6-2. Check Code 1) After servicing, push the START/STOP button to return to the normal mode. 2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power supply again so that memory in the microcomputer…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 79 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Block distinction Check code Block Outdoor P.C. board Operation of diagnosis function Check code Cause of operation Air conditioner status Remarks Judgment and action Being out of place, disconnection or shortcircuit of the outdoor heat exchanger sensor (TE)…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 80 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-7.Judgment of Trouble by Symptom 10-7-1. Power of Indoor Unit Does not Turned on (Does not Operate Entirely) Primary check 1) Is the supply voltage normal? 2) Is the normal voltage provided to the outdoor unit? 3) Is the crossover cable connected properly?…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 81 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-7-3. Only the Indoor Motor Fan Does not Operate Primary check 1) Is it possible to detect the power supply voltage (AC220–240V) between [1] and [2] on the terminal block? 2) Does the indoor fan motor operate in cooling operation? (In heating operation, the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 82 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-7-4. Indoor Fan Motor Automatically Starts to Spin by Turning on Power Supply Cause The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor. If the P.C. board is soldered imperfectly or the IC is defective…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 83 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-7-5. Troubleshooting for Remote Controller Primary check 1) Check that A or B selected on the main unit is matched with A or B selected on the remote controller. The unit does not beep at all. Push the START/STOP button. Operation lamp on indoor unit is…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 84 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-7-6. Outdoor Unit Does not Operate 1) Is the voltage between [2] and [3] of the indoor terminal block varied? 2) Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the following diagram. NOTE • Measurement should…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 85 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-8.Check Code 1C (Miswiring in Indoor/Outdoor Units) and 1E Check procedure 1C 1E Gas leakage, disconnection of TS/TC sensors (Check code 02, 1C) Discharge temp. error, gas leakage (Check code 03, 1E) Valve drive check Is coil of the pulse motor valve…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 86 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-9.Inspection of the Air Purifier Turn off the power breaker once, and turn on again after 10 seconds. Does the OPERATION indicator flash? NO To item “Power supply is not turned on” Primary check YES Turn off the power breaker and remove CN401 (Micro switch…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 87 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-10.Diagnose Trouble in Outdoor Unit Table 10-10-1 Diagnosis/Process flowchart Remove connector of compressor. Check 25A fuse (Part No.F01). OK NG Item Contents Preparation Turn “OFF” the power supply breaker, and remove 3P connector which connects inverter…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 88 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Diagnosis/Process flowchart A Item Contents Check Check winding resistance between phases of compressor, and resistance between outdoor frames by using a tester. B Replace control board assembly. Summary • Is not grounded. → OK if 10MΩ or more • Is not…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 89 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-11.Inspection of the Main Parts 10-11-1.Inspection of the P.C. Board (Indoor Unit) CAUTION • When removing the front panel or the P.C. board, be sure to shut off the power supply breaker. • When removing the P.C. board, hold the edge of the P.C. board and…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 90 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type No. 6 7 Procedure Check points Causes If the above condition (No. 5) still continues, 1. Check whether or not the compressor start the unit in the following condition. operates. • Set the operation mode to HEAT. 2. Check whether or not the OPERATION • Set the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 91 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-11-2.Indoor Unit (Other Parts) No. Part name Room temp. (TA) sensor Heat exchanger (TC) sensor Heat exchanger (TCj) sensor 1 Checking procedure Disconnect the connector and measure the resistance value with tester. (Normal temp.) Sensor Temperature 10°C…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 92 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type No. Part name 4-way valve coil (Comp. cylinder switching) (Model : VHV-01AZ535B1) Checking procedure Measure the resistance value of winding by using the tester. Resistance value 4 7.2 ± 0.36 Under 20°C Connector : Red Pulse motor valve coil (Model…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 93 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 10-12.Inspection of the Outdoor Fan Motor 10-12-1.Symptom • Outdoor fan motor does not rotate. • Outdoor fan motor stops within several tens seconds though it started rotating. • Outdoor fan motor rotates or does not rotate according to the position where the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 94 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11 REPLACING THE MAIN PARTS 11-1.Indoor Unit WARNING Since high voltages is applied to electrical parts, turn off the power without fail before starting replacement work. CHECK WATCH OUT FOR FIRE After repairs have been completed and the front panel and…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 95 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-1-2. Fixing Frame Assembly 11-1-3. Electric Parts Cover Detached 1) Detach the two air filters. 2) Disconnect the plasma ion charger connector and the earth lead (black). (The earth lead is connected to the heat exchanger with a screw.) 3) Remove the two…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 96 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-1-4. Microcomputer P.C. Board 11-1-5. Louver 1) Open the moving panel, and support it with the panel support. 2) Open the vertical air flow louver. 3) Insert a flathead screwdriver into the gap of the louver fixture on the right and left ends of the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 97 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-1-6. Heat Exchanger 11-1-7. Fan Motor 1) Perform all the steps in 11-1-1.Removing the Front Panel and Moving Panel and 11-1-2. Fixing Frame Assembly. 2) Remove the pipe holder at the rear of the unit. 3) Remove the two fixing screws (10 mm) at the left of…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 98 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-1-8. Cross Flow Fan Keep 27mm distance between the support shaft at the rear centre of the unit and the immediate right joint-section of the cross flow fan. 1) Perform all the steps in 11-1-1.Removing the Front Panel and Moving Panel and 11-1-2. Fixing…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 99 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-2.Plasma Ion Charger 5) Lift the high-voltage power supply unit, and pull the projection at the bottom of the high-voltage power supply unit out of the fixing frame. 11-2-1. Common Procedure High-voltage power supply unit 1) Perform all the steps in…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 100 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-3.Outdoor Unit 11-3-1. Common Procedure REQUIREMENT Wear gloves for this job. Otherwise, you may injure your hands on the parts, etc. Detachment 1) Stop operation of the air conditioner, and turn off the power breaker. 2) Remove the valve cover. (ST1TØ4 ×…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 101 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-3-2. Front Cabinet 11-3-3. Control Board Assembly Detachment Detachment 1) Perform all steps of detachment in 11-3-1. Common Procedure. 2) Remove the following screws: Screws (ST1TØ4 × 8L 2 pcs.) fixing the front cabinet and the inverter cover Front…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 102 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type • These capacitors have large capacity. Therefore, it is terminals for dangerous if you short-circuit the , discharging with a screwdriver or the like, which generates a big spark. 4) Perform step 2) of detachment in 11-3-2.Front Cabinet to detach the front…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 103 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Precautions when attaching the inverter box Insert the heat insulator into the gap of the partition board. View from behind Hook the inverter fixing plate to the partition board. Partition board Link up the slit of the partition board with the boss of the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 104 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type CN300: CN704: CN600: CN700: CN603: CN602: CN601: CN703: CN705: • After the board is replaced and accommodated in the inverter box, securely clamp the portions that were clamped before replacement with cable ties to prevent wires from touching hot areas or…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 105 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type NOTE When attaching the fan motor, tighten the flange nut to a tightening torque of 4.9N·m (50kgf·cm). Propeller fan B Fan motor Hook the claw to the bottom plate. D (13, 16, 18) Flange nut Detail A 11-3-7. Reactor Detail B 1) Perform the step of detachment…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 106 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 2) Extract refrigerant gas. 3) Remove the partition board. (ST1TØ4 × 8L 3 pcs.) 4) Remove the sound-insulation material and the sensor. 5) Remove the screw (ST1TØ4 × 8L 1 pc.) fixing the bottom plate and the heat exchanger. 6) Remove the screw (ST1TØ4 × 8L 1…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 107 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type Attachment 1) Insert the claws of the fan guard into the holes in the front cabinet. Press the hooking claws (9 locations) by hand to fix them. REQUIREMENT The entire attaching work has been completed. Check that all the hooking claws are fixed at their…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 108 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 11-3-13.TE Sensor (Outdoor Heat Exchanger Temperature Sensor) 11-3-15.TD Sensor (Discharge Temperature Sensor) Attachment Attachment 1) Install the TE sensor onto the straight part of the condenser output pipe with the lead wires pointing upward and the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 109 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 12 EXPLODED VIEWS AND PARTS LIST 12-1.Indoor Unit RAS-07PKVP-E, RAS-10PKVP-E, RAS-13PKVP-E, RAS-16PKVP-E, RAS-18PKVP-E RAS-07PKVP-ND, RAS-10PKVP-ND, RAS-13PKVP-ND, RAS-16PKVP-ND, RAS-18PKVP-ND 221, (-E) 249 (-ND) 243 (-E) 244 (-ND) 204 * The parts in the…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 110 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 12-2.Microcomputer P.C. Board RAS-07PKVP-E, RAS-10PKVP-E, RAS-13PKVP-E, RAS-16PKVP-E, RAS-18PKVP-E RAS-07PKVP-ND, RAS-10PKVP-ND, RAS-13PKVP-ND, RAS-16PKVP-ND, RAS-18PKVP-ND 411, 412, 413, 414, 415, 406, 407, 408, 409, * The parts in the following parts list…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 111 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 12-3.Outdoor Unit RAS-07PAVP-E, RAS-10PAVP-E, RAS-13PAVP-E, RAS-16PAVP-E, RAS-18PAVP-E RAS-07PAVP-ND, RAS-10PAVP-ND, RAS-13PAVP-ND, RAS-16PAVP-ND, RAS-18PAVP-ND 08,09 FLAG SLEEVE O.D. 12.7mm 16,19,22,25,26 O.D. 9.52mm 15,18,21,24,26 44 38 O.D. 6.35mm…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 112 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type RAS-07PAVP-E, RAS-10PAVP-E, RAS-13PAVP-E, RAS-16PAVP-E, RAS-18PAVP-E RAS-07PAVP-ND, RAS-10PAVP-ND, RAS-13PAVP-ND, RAS-16PAVP-ND, RAS-18PAVP-ND * The parts in the following parts list are conformed to RoHS. Therefore be sure to use the following parts for…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 113 Wednesday, March 4, 2009 11:22 AM
Service Manual High Wall, Heat Pump Type 12-4.P.C. Board RAS-07PAVP-E, RAS-10PAVP-E, RAS-13PAVP-E, RAS-16PAVP-E, RAS-18PAVP-E RAS-07PAVP-ND, RAS-10PAVP-ND, RAS-13PAVP-ND, RAS-16PAVP-ND, RAS-18PAVP-ND 705 BASE, PC BOARD 701 SENSOR, TE 702 SENSOR, TS 703 SENSOR, TO 704 SENSOR, TD 710 PC BOARD…
-
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 12 Wednesday, March 4, 2009 11:22 AM
Copyright © 2009 TOSHIBA CARRIER CORPORATION, All Rights Reserved. Toshiba