Инструкции на Кондиционеры серии FDC-HKX
Кондиционеры серии FDC-HKX. Инструкция по монтажу и эксплуатации. Часть 1.
Смотрите также: Часть 3 →Часть 2 →
Загружаем документ…
Текст инструкции
-
19. INVERTER DRIVEN
MULTI-INDOOR UNIT CLIMATE CONTROL SYSTEM (OUTDOOR UNIT) Refrigerant R22 use models FDCJ140HKXE2B, 224HKXE2B, 280HKXE2B Alternative refrigerant R407C use models FDCP140HKXE2B, 224HKXE2B, 280HKXE2B (INDOOR UNIT) FDTJ28HKXE2 FDTWJ28HKXE2B FDTSJ22HKXE2B FDRJ22HKXE2 36HKXE2 45HKXE2B 28HKXE2B 28HKXE2…
-
19.1 GENERAL INFORMATION
19.1.1 Specific features (1) Fuzzy control (a) Response speed and stability are enhanced. ¡ The system automatically controls changes of return air temperature, set temperature and room temperature according to the fuzzy control. ¡ The system response speed, can keep room temperature constant, and…
-
(5) Connectable indoor capacity
Capacity from 50% to 130% is possible. ¡ FDCJ(P)140 type ¡ FDCJ(P)280 type Number of connectable units : 1 to 8 units Number of connectable units : 1 to 16 units Connectable capacity : 7000 ~ 18200 W Connectable capacity : 14000 ~ 36400 W ¡ FDCJ(P)224 type Number of connectable units : 1 to 13 units…
-
19.1.2 How to read the model name
Example: FDC P 224 H KX E 2 B CE marking model Application power source...See the specifications Multi KX series Heat pump type Nominal capacity P: R407C models J: R22 models Model name Indoor unit : FDT, FDTW, FDTS, FDR, FDUM FDE, FDK, FDFL, FDFU Outdoor unit : FDC 19.1.3 Table of models Capacity…
-
19.2 SELECTION DATA
19.2.1 Specifications (1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2 Models Item FDTJ28HKXE2(3) FDTJ36HKXE2(3) 3600 Nominal cooling capacity*1 W 2800 Nominal heating capacity*2 W 3200 4000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height…
-
Models FDTJ45HKXE2, 56HKXE2, 71HKXE2
Models FDTJ45HKXE2(3) FDTJ56HKXE2(3) W 4500 5600 7100 W 5000 6300 8000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ71HKXE2(3) 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg Hi: 38 Me: 35 Lo: 34 Unit:260 Hi: 40 Me: 38…
-
Models FDTJ90HKXE2, 112HKXE2, 140HKXE2
Models FDTJ90HKXE2(3) FDTJ112HKXE2(3) W 9000 11200 14000 W 10000 12500 16000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ140HKXE2(3) 1 Phase 220/240V 50Hz dB(A) Hi: 42 Me: 40 Lo: 39 Exterior dimensions Height Width Depth mm Unit: 260 Panel:30 Net weight kg Noise…
-
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Models FDTWJ28HKXE2B(3) FDTWJ45HKXE2B(3) FDTWJ56HKXE2B(3) W 2800 4500 5600 W 3200 5000 6300 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight…
-
Models FDTWJ71HKXE2B, 90HKXE2B
Models FDTWJ71HKXE2B(3) Item FDTWJ90HKXE2B(3) Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 Noise level dB(A) Hi: 41 Me: 38 Lo: 35 Exterior dimensions Height Width Depth mm Unit:330 Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 41 Me: 39 Lo: 36 1054 620…
-
Models FDTWJ112HKXE2B, 140HKXE2B
Models FDTWJ112HKXE2B(3) Item FDTWJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 44 Me: 41 Lo: 38 Exterior dimensions Height Width Depth mm Unit:345 Net weight kg Hi: 45 Me: 42 Lo: 39 1524 620…
-
(c)
1-way outlet ceiling recessed type (FDTS) Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B Model FDTSJ22HKXE2B(3) FDTSJ28HKXE2B(3) W 2200 2800 3600 W 2500 3200 4000 Noise level dB(A) Hi: 39 Lo: 38 Exterior dimensions Height Width Depth mm Net weight Kg Item 1 Nominal cooling capacity* Nominal heating…
-
Models FDTSJ45HKXE2B, 71HKXE2B
Model FDTSJ45HKXE2B(3) Item FDTSJ71HKXE2B(3) 1 Nominal cooling capacity* W 4500 7100 Nominal heating capacity*2 W 5000 8000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 43 Me: 40 Lo: 38 Hi: 44 Me: 40 Lo: 38 Exterior dimensions Height Width Depth mm Unit:194 Panel:10 Unit:194 Panel:10 Net…
-
(d) Cassetteria type (FDR)
Models FDRJ22HKXE2, 28HKXE2 Models FDRJ22HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ28HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 2200 2800 Nominal heating capacity*2 W 2500 3200 Power…
-
Models FDRJ45HKXE2, 56HKXE2
Models FDRJ45HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ56HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 4500 5600 Nominal heating capacity*2 W 5000 6300 Power source 1 Phase 220/240V 50Hz…
-
Models
FDRJ71HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ90HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-36W-E R-PNLC-36W-E R-PNLS-36W-E R-PNLC-36W-E Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 Power source 1 Phase 220/240V 50Hz Noise…
-
Models
FDRJ112HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ140HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-46W-E R-PNLC-46W-E R-PNLS-46W-E R-PNLC-46W-E Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz Noise…
-
(e)
Satellite ducted type (FDUM) Models FDUMJ36HKXE2, 45HKXE2 Models FDUMJ36HKXE2(3) Item FDUMJ45HKXE2(3) 1 Nominal cooling capacity* W 3600 4500 Nominal heating capacity*2 W 4000 5000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg Hi: 34 Me…
-
Models FDUMJ56HKXE2, 71HKXE2, 90HKXE2
Models Item FDUMJ56HKXE2(3) FDUMJ71HKXE2(3) FDUMJ90HKXE2(3) 1 Nominal cooling capacity* W 5600 7100 9000 Nominal heating capacity*2 W 6300 8000 10000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 35 Me: 32 Lo: 29 Exterior dimensions Height Width Depth mm 299 Net weight kg 750 Hi: 35 Me…
-
Models FDUMJ112HKXE2, 140HKXE2
Models FDUMJ112HKXE2(3) Item FDUMJ140HKXE2(3) Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 Noise level dB(A) Hi: 38 Me: 35 Lo: 32 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 39 Me: 37 Lo: 34 350 1370 Refrigerant…
-
(f)
Ceiling suspension type (FDE) Models FDEJ36HKXE2B, 45HKXE2B Models FDEJ36HKXE2B(3) FDEJ45HKXE2B(3) W 3600 4500 W 4000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 5000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 43 Me:40 Lo: 38 Exterior dimensions Height Width Depth mm…
-
Models FDEJ56HKXE2B, 71HKXE2B
Models FDEJ56HKXE2B(3) Item FDEJ71HKXE2B(3) 1 Nominal cooling capacity* W 5600 7100 Nominal heating capacity*2 W 6300 8000 Noise level dB(A) Hi: 43 Me:40 Lo: 38 Hi: 44 Me:40 Lo: 38 Exterior dimensions Height Width Depth mm 184 184 Net weight kg Power source 1 Phase 220/240V 50Hz 1000 650 1260 22…
-
Models FDEJ112HKXE2B, 140HKXE2B
Models FDEJ112HKXE2B(3) Item FDEJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 Noise level dB(A) Hi: 49 Me:46 Lo: 42 Hi: 50 Me:47 Lo: 42 Exterior dimensions Height Width Depth mm 239 239 Net weight kg Power source 1 Phase 220/240V 50Hz 1260 650…
-
(g) Wall mounted type (FDK)
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Models FDKJ22HKXE2(3) FDKJ28HKXE2(3) FDKJ36HKXE2(3) W 2200 2800 3600 4500 W 2500 3200 4000 5000 Noise level dB(A) Hi: 40 Lo: 37 Exterior dimensions Height Width Depth mm Net weight kg Item 1 Nominal heating capacity*2 Nominal cooling capacity* Power…
-
Models FDKJ56HKXE2, 71HKXE2
Model FDKJ56HKXE2(3) FDKJ71HKXE2(3) W 5600 7100 W 6300 Item 1 Nominal cooling capacity* Nominal heating capacity*2 8000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 46 Me:43 Lo: 39 Hi: 47 Me:44 Lo: 40 Exterior dimensions Height Width Depth mm 375 1148 375 Net weight kg 20 194 Louver fins…
-
(h) Floor standing exposed type (FDFL)
Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2 Model Item FDFLJ28HKXE2(3) FDFLJ45HKXE2(3) FDFLJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 7100 Nominal heating capacity*2 W 3200 5000 8000 Noise level dB(A) Hi: 41 Me:38 Lo: 36 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase…
-
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Model Item FDFUJ28HKXE2(3) FDFUJ45HKXE2(3) FDFUJ56HKXE2(3) FDFUJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 5600 7100 Nominal heating capacity*2 W 3200 5000 6300 8000 Noise level dB(A) Hi: 41 Me:38 Lo: 36 Exterior dimensions Height Width Depth mm…
-
(2) Outdoor unit
(a) Alternative refrigerant R407C use models Models FDCP140HKXE2B, 224HKXE2B, 280HKXE2B Models FDCP140HKXE2B(3) Item Power source FDCP224HKXE2B(3) FDCP280HKXE2B(3) 3 Phase 380/415V 50Hz Nominal cooling capacity*1 W 14000 22400 28000 Nominal heating capacity*2 W 16000 25000 31500 Noise level dB(A)…
-
(b) Refrigerant R22 use models
Models FDCJ140HKXE2B, 224HKXE2B, 280HKXE2B Models FDCJ140HKXE2B(3) Item Power source FDCJ224HKXE2B(3) FDCJ280HKXE2B(3) 3 Phase 380/415V 50Hz Nominal cooling capacity*1 W 14000 22400 28000 Nominal heating capacity*2 W 16000 25000 31500 Noise level dB(A) Exterior dimensions Height Width Depth mm Net…
-
(3) Operation chart
Since the Multi KX series air conditioner units are free multitype to which the indoor units of different capacity and different model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual operation characteristics of indoor and…
-
FDTS Series
(220 V/240 V) Models FDTS Series 45 71 Power input (kW) 22 0.07/0.08 0.09/0.11 0.12/0.15 Running current (A) 0.33/0.36 0.43/0.46 0.58/0.63 Item 28 36 FDR, FDUM Series (220 V/240 V) Models FDR, FDUM Series Item 22 28, 36 Power input (kW) 0.09/0.11 0.11/0.13 Running current (A) 0.41/0.46 0.51/0.56…
-
Operation characteristics of each unit
(Cooling/Heating) Models FDCJ224HKXE2B FDTJ71HKXE2 FDTJ45HKXE2 Power input (kW) 9.8/8.3 0.10/0.10 0.10/0.10 Running current (A) 15.7/13.0 0.47/0.47 0.45/0.45 Item 1 Total power input (kW) (Cooling) 9.8 + (0.10 × 4) = 10.2 (kW) (Heating) 8.3 + (0.10 × 4) = 8.7 (kW) 2 Total running current (A) .…
-
1) Correction factor of compressor power input
Models FDCJ140HKXE2B, FDCP140HKXE2B 1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 (Rating) Total capacity of concurrently operating indoor unit Models FDCJ224HKXE2B, FDCP224HKXE2B 1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating…
-
Models FDCJ280HKXE2B, FDCP280HKXEB
1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 (Rating) Total capacity of concurrently operating indoor unit 2) Compressor and outdoor fan power input in rated operation. (380 V/415V) Power input (kW) Compressor Outdoor fan Outdoor unit Cooling…
-
19.2.2 Range of usage & limitations
System FDCP140HKXE2B FDCJ 140HKXE2B FDCP280HKXE2B FDCJ280HKXE2B FDCP224HKXE2B FDCJ224HKXE2B Item Indoor intake air temperature (Upper, lower limits) Refer to the capacity characterstics. Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Number of connected…
-
19.2.3 Exterior dimensions
(1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2, 45HKXE2, 56HKXE2, 71HKXE2, 90HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid…
-
Models FDTJ112HKXE2, 140HKXE2
Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping φ9.52(3/8") 267 Drain hose (Accessories) (Local setting) D 422 675 (Suspension bolts pitch) Exhaust air…
-
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Unit : mm Drain hose (Accessories) (Local setting) Holes of tapping screws 5 - φ4 264 Hole Suspension fitting 91 Center of panel 640 70 Suspension bolts (M10 × 4 pcs.) (Ceiling hole size) 446 Control box (Suspension bolts pitch) (Suspension bolts pitch) 40…
-
Models FDTWJ71HKXE2B, 90HKXE2B
Unit : mm 1054 295~ 325 Liquid piping φ9.52(3/8") ↑ 240 Holes for tapping screws 8 – φ4 128 Drain (VP25) (condensate pump drain) Hole for wiring 20 Drain (VP20) (Natural drainage) Exhaust air opening for ducting (knock out) Decorative Panel 64 Gas piping φ15.88(5/8") or less Hole A Hole VIEW A 148…
-
Models FDTWJ112HKXE2B, 140HKXE2B
Unit: mm 310 Suspension fitting 20 Fresh air opening for ducting (knock out) A→ 345 Hole 255 Hole 20 78 Holes for tapping screws 8-ø4 128 Exhaust air opening for ducting (knock out) 20 Liquid piping ø9.52(3/8") Gas piping ø15.88(5/8") Drain(VP25) (condensate pump drain) Drain (VP20) (Natural…
-
(c) 1-Way outlet ceiling recessed type (FDTS)
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B, 45HKXE2B Panel center Drain hose (Accessories) (Local setting) VIEW A 295~325 ←C or less Max. Drain up 70 Suspension bolts (M10×4 pcs.) Air outlet 920 245 Fresh air opening for ducting (Knock out) Air inlet grille 1200 1290 Holes for tapping screws (φ4.0 − 6…
-
Model FDTSJ71HKXE2B
Unit : mm 1440 (Ceiling hole size) 1250 (Suspension bolts pitch) (φ4-6pcs.) Panel center 250 60 Drain hose(Accessories) (Local setting) 295~325 1200 or less Max. Drain up Suspension bolts (M10×4pcs.) 150 VIEW A ←C 30 70 Fresh air opening for ducting (Knock out) Air outlet 1180 Air inlet grille Holes…
-
(d) Cassetteria type (FDR)
Model FDRJ22HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) ↑ 213 MIN95 40 MIN81 650 or less MIN320 MIN225 510 A Drain(VP25) (Natural drainage) Hole for wiring (φ35) 250 460 Holes for tapping screws 4-φ4.0 150 1040 45 φ170 φ170 950 Air inlet 45 75 φ149 MIN156 00 φ2 B→ 80…
-
Model FDRJ22HKXE2
Canvas Panel (Model: R-PNLC -26W-E) 804 (Ceiling hole size) Drain hose (Accessories) (Load setting) 9 Fresh air opening for ducting (Knock out) C↓ Drain (Connectable with VP25) Liquid piping φ6.35(1/4") Gas piping φ12.7(1/2") Control box Panel center 352 525 (Ceiling hole size) 90 786 (Suspension…
-
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bols pitch) 137 Fresh air opening for ducting (Knock out) (Local setting) Supply air duct 405 75 panel center (Ceiling hole size) Control box C↓ 545 (Suspension bolt pitch) VIEW C Drain (Connectable with VP25) Gas…
-
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Canvas Panel (Model: R-PNLC-26W-E) Unit : mm Drain hose (Accessories) 804 (Ceiling hole size) 9 786 (Suspension bolts pitch) (Local setting) 9 Fresh air opening for ducting (Knock out) 45 Control box Drain (Connectable with VP25) Panel center Liquid piping 28, 45 type: φ6.35 (1/4") 56 type: φ9.52…
-
Unit : mm 1180 (Ceiling hole size) 986 (Suspension bolts pitch) Drain hose (Accessories) (Local setting) Fresh air opening for ducting (Knock out) 545 (Suspension bolts pitch) 45 Panel center 71 Drain (Connectable with VP25) B→ Drain (VP20) (Natural drainage) ↑A MIN95 MIN320 Hole for wiring (φ35)…
-
Unit : mm Drain hose (Accessories) (Local setting) 1004 (Ceilinghole hole size) 986 (Suspension bolts pitch) Fresh air opening for ducting (Knock out) Drain (Connectable with VP25) Control box Panel center Liquid piping φ9.52(3/8") B→ 295~325 Suspension bolts (M10 × 4pcs.) VIEW C Max. Drain up 71…
-
Unit : mm 1600 (Ceiling hole size) 1406 (Suspension bolts pitch) 663 45 Panerl center Supply air duct Liquid piping φ19.05(3/4") 295~325 320 VIEW C 80 (Max. Drain up) 1370 495 Drain (Connectable with VP25) 76 Gas piping φ19.05(3/4") Suspension bolts (M10 ×4pcs.) φ20 MIN 96 MIN156 406~420 Drain…
-
Unit : mm 1424 (Ceiling hole size) 1406 (Suspension bolts pitch) Drain hose (Accessories) (Local setting) 9 C ↑ Fresh air opening for ducting (Knock out) Control box Drain (Connecteble with VP25) 495 Liquid piping φ9.52(3/8") 1370 465 405 295~325 or less Suspension bolts (M10 × 4pcs.) 80 Max. Drain…
-
(e) Satellite ducted type (FDUM)
Models FDUMJ36HKXE2, 45HKXE2, 56HKXE2 Unit : mm 786 (Suspension bolts pitch) B 205 Hole of tapping screws (4-φ4) Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) 284 A→ 213 φ149 Control box φ170 Liquid piping 36, 45 type: φ6.35(1/4") 56 type: φ9.52(3/8") 118 472 (Suspension…
-
Models FDUMJ71HKXE2, 90HKXE2
Unit : mm 986 (Suspension bolts pitch) 950 ↑ 18 80 B 205 284 A→ Holes of tapping screws 4-φ4 φ149 Control box 118 472 (Suspension bolts pitch) 45 18 Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) φ170 Liquid piping φ9.52(3/8") Fresh air opening Gas piping for ducting…
-
Models FDUMJ112HKXE2, 140HKXE2
Unit : mm 1406 (Suspension bolts pitch) 1370 ↑ 118 (Suspension bolts pitch) B Holes of tapping screws (4-φ4) 213 φ149 284 A→ 58 76 Supply air duct Drain hose (Accessories) (Local setting) φ170 Drain (Connectable with VP25) Fresh air opening Liquid piping for ducting φ9.52(3/8") (Knock out) Gas…
-
(f)
Ceiling suspension type (FDE) Models FDEJ36HKXE2B, 45HKXE2B, 56HKXE2B Unit : mm 984 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4 pcs. Not included) The brackets face out When the unit is half recesed a bove the ceiling (Suspension bolts pitch) 184 50 The brackets face…
-
Model FDEJ112HKXE2B
Unit : mm 1244 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4pcs. Not included) The brackets face out When the unit is half recesed a bove the ceiling 66 50 1200 30 Liguid piping 584 135 Gas piping 185 Drain hole connection (1) The brackets face interior When the unit is…
-
(g) Wall mounted type (FDK)
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Unit : mm 7.7 Outlet for piping (On both side) 65 155 Detail of mounting plate Space for installation and service 200 Mounting plate φ8 × 48 pcs. (Holes on mounting plate) 150 200 or more or more Available space for rear connection 45 Hole on wall for…
-
Model FDKJ71HKXE2
23 Unit : mm 1436 7.7 155 1306 377.5 155 108 Space for installation and service Mounting plate 377.5 Detail of mounting plate Outlet for piping (On both side) 150 200 or more or more 45 φ8 × 48 pcs. (Holes on mounting plate) or more 1196 Outlet for electric wiring 375 280 ←A Piping cover Hole on…
-
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Note (1) Value in ( Unit : mm ) indicates 71 type. Space for installation and service 110 786 (1071) A 1000 126 166 Slotted hole for wall mounting 4-12 x 24 Peri cover Peri cover B 810(1095) 722(1007) Expansion valve box Control box Drain piping…
-
Connect of
gas piping φ19.05(3/4") 175 110 Dimensions of refrigerant piping connecting mouth(plan) Rear surface Anchor bolts (M10×4pcs.) Connect of liquid piping φ9.52(3/8") Hole for drain (φ50) 40 47.5 192 131 Hole for drain (4-φ20) 80 L4 ) ← Wall height H1 ( service spece suction L2 Wall height H3 170…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.