19.5.3 Installation of outdoor unit
(1) Selection of installation location (a) A place where air will not be stagnant. (b) A place where the exhaust air will not be shortcycled. (c) A place with enough space for air flow around the unit. (d) A place where the unit will not be affected by other heat sources. (when there are multiple…
-
(b) In the case that there is a wall above the unit
-
(3) When the wall heights H1 and H3 exceed the limited value, keep dimensions for L1 and L3 as shown below. L1 = H1 – 500 L3 = 300 + (H3–700) / 2 However, there is no limitation in wall height H3 if L3 exceeds 600. Oblique blow (standard) W1 1,500 and over W2 800 and over W3 1,500 and over W4 1,500…
-
(c) Securing outdoor unit (in the case of exposure to severe weather conditions)
Fix the unit in the following way. ● Use overturning prevention brackets. ● Rig with wires. Ring with wires Fix the unit using achor bolts (Use rigging wires that are resistant to corrosion and sufficient in strengh. For example SUS304-W1, wire thickness 2.9 mm) (4) Installation Fix the unit in a…
-
19.5.4 Refrigerant piping
(1) Precautions no refrigerant piping work for prevention against compressor lock Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant piping conditions, The precautions for refrigerant piping are as belows. (a) Be sure to…
-
(2) Table for selection of piping size
-
Example of piping
Outdoor unit: FDCJ280HKXE2B Indoor unit: Combination of 8 units [Branch pipe set : DIS-2KX10-E × 1 set, DIS-2KX20-EX × 3 set, DIS-2KX30-E × 3 set] [Total capacity: 363 (36300W) ] • Selecting piping size Piping size (in) Gasline Liquid line A Same as the outdoor unit piping size ø28.58 ø12.7 B Total…
-
(3) Specification of unit piping (Pipe diameter, Connecting method)
-
(b) Refrigerant connection piping
Connection to left direction Refrigerant piping Electric wing Electric wing Connection to front direction Electric wing Refrigerant piping Refrigerant piping Connection to rear direction Connection to right direction Connection to lower direction (c) Connection to rear, right and front directions.…
-
(6) Evacuating
Evacuating can be completed faster by evacuating both the check joint on the liquid side service valve and the check joint of the evacuating gas pipe (accessory) connected to the gas side operation valve at the same time. (Of course, evacuating is possible even through the liquid side check joint…
-
19.5.5 Electric wiring
(1) Power supply wiring (a) Outdoor unit power supply • Use separate power supplies for the outdoor and indoor unit respectively. (Standard specification) • The table below shows the power specification for outdoor unit only. Item Power source Model Wire length (m) 3.5 FDC140 type FDC224 type…
-
(2) Precaution in electric wiring
(a) Use separate power supplies for the outdoor and indoor units respectiveliy (Standard specification) (b) Signal wiring (for indoor and outdoor units) • Double-core cable with a diameter 0.75 to 2 mm2 should be used for the signal wires. • Never make the indoor and outdoor connecting signal line…
-
Models FDC224, 280type
Power source (outdoor unit side) 3phase 380/415V50Hz Earth leakage breaker Outdoor unit Circuit Breaker Earth Signal wire (Between outdoor and indoor units) Signal wire (Between indoor units) Circuit breaker Earth leakage breaker Indoor unit <I> remote controller wire <II> <III> <IV> <V> <VI> <VII>…
-
Indoor and outdoor signal wiring (a) If only one Outdoor unit is used A Outdoor signal teminal block B Double cores 0.75 ~ 2 mm2 Total length of signal wires: 1000 m or less A B A B A B Indoor signal terminal block Notes (1) The indoor and outdoor signal wiring are without polarity B B B B A A A A…
-
(5) Remote controller wiring
(a) Wiring for controlling only one indoor unit. X Y Z Red White Black X Y Z Red White Black Indoor unit terminal blocks Note (1) Cables for the remote controller have polarity. Be sure to connect terminal blocks with the same numbers. If mis wiring occurs, E1 is displayed and disables the unit from…
-
(6) Setting of unit address
Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning power on. Indoor unit Outdoor unit…
-
Set the address switch of outdoor unit at 49. (This is set at 49 at shipment from factory.) 2) Set the address switch of indoor unit at 49. (This is set at 49 at shipment from factory) 3) Turn power on for the indoor and outdoor units. Addresses are set automatically. (No. in a range of 0 - 7 is set…
-
Detail of setting from the remote controller
1) If the power switch is turned on, the outdoor No. on the display flashes, and "--" on the return air temperature display section and "U--" on the time display section are lit. If power is not supplied to the outdoor unit, the outdoor No. only lights and you cannot set the address. In such…
-
1) Using the address switch (green) on the outdoor unit PCB, set the address of the outdoor unit in a range of 00 - 47 avoiding duplication with any other outdoor unit. 2) Using the address switch (green) on the indoor unit PCB, set the outdoor No. at the same No. as the outdoor unit which is…
-
19.5.6 Test run
(1) Before starting operation (a) Measure resistances between the electrical parts terminal blook and ground grounded area using a 500V Megger, insulator. Resistance must be higher than 1M Ω. (b) Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hours…
-
19.6 MAINTENANCE DATA
(1) Before starting troubleshooting (a) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs (Printed circuit board) of indoor/outldoor units The microcomputer detects errors on electrical components…
-
Check Indicator Table
Stays OFF Keeps flashing Keeps flashing Keeps flashing E11 Stays OFF or Keeps flashing Keeps flashing Keeps flashing Keeps flashing 2 time flash Keeps flashing Stays OFF Stays OFF 2 time flash Keeps flashing Keeps flashing Keeps flashing 2 time flash Keeps flashing E10 Stay OFF 2 time flash Keeps…
-
Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays…
-
3) Display sequence of error, inspection display lamp
a) One kind error Display corresponding to the error is shown. b) More than one errors. Section Display section Error code of remote controller • Displays the error of higher priority (When plural errors are persisting) Inspection LED (red) of indoor unit PCB E¡ E¡º E¡¡ E™ E£ E∞ E¶ Eª E¡™ E¢§…
-
d)
Recording and reset of error Error display Memory Reset Error code • Saves in memory the mode (1) of higher priority Indoor unit inspection lamp (red) • Cannot save in memory • Stop the unit operation by pressing the ON/OFF switch of remote controller. • Operation can be started again if the error…
-
(a) Diagnosis by the power supply reset
When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc. Check at the indoor unit side. Error Are the return air temperature and Center/ Remote displayed on the remote controller? YES Is any errror code display ? NO YES NO Check the error…
-
(2) Reference
Effect of noise ¡ When noises inturude into remote controller. Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote or…
-
● Function of jumper wires
(ii) Parts layout on the indoor unit printed circuit board Transformer primary side Model selector switch Control selection ( Transformer secondary side Power supply connector for PCB Name With None (1) With J2 None (1) J1 ) J3 J4 J5 J6 (2) J6 (2) J7 J8 Return air Outdoor unit number HA connector…
-
Error display : No display LCD display : No display [Polarity determination trouble] Indoor unit Outdoor unit Red LED Stays OFF Red LED Stays OFF Green LED Lights continuously Green LED Lights continuously ● When the LCD display (Center/Remote, temperature display, etc.) of remote controller…
-
Error display : No display
LCD display : No display 2 [Power supply line error] Outdoor unit Red LED Stays OFF Green LED Stays OFF Unit is normal (Malfunction by noisse) YES Indoor unit Red LED Stays OFF Green LED Stays OFF YES Power supply checked between 1~2 or L1, L2, L3, N? NO Indoor unit Red LED *3 time flash (During…
-
Red LED
Green LED Indoor unit *3 times flash Keeps flashing Red LED Green LED Outdoor unit Stays OFF Keeps flashing * Lamp OFF if remote controller wire is broken at power ON. • Remote controller normal voltage (DC) X ~ Z: 10.5 ~ 10.8V Y ~ Z: 5 ~ 10.8V Unit is normal. (Interference by temporary noise on…
-
Error display : e2 [Duplicated indoor unit No. or More than 49 indoor unit are connected.] Indoor unit 1 time flash Keeps flashing Red LED Green LED Red LED Green LED Outdoor unit Stays OFF Keeps flashing (1) Is the indoor unit No. duplicated or More than 49 indoor unit are connected? YES Correction…
-
Error display : e9 [Drain trouble] Indoor unit 1 time flash Keeps flashing Red LED Green LED Red LED Green LED Outdoor unit Stays OFF Keeps flashing Defective indoor unit PCB Replacement (Defective condensate motor output circuit) NO (1) Is the angle of drain piping good. Is there any problem? YES…
-
[Address No. combination eroor or addressing is preformed with the following combinations.] Error display : e12 Red LED Green LED Indoor unit 1 time flash Keeps flashing Are unit number set for see following?(1) Red LED Green LED YES Outdoor unit Stays OFF Keeps flashing Unit number correction NO…
-
(ii) Parts layout on the outdoor unit PCB
• Function of DIP switch PCB power supply connector (Secondary side) LED (red) Name 7-segement indicator SW3-1 LED (green) SW3-2 SW3-3 SW3-4 SW3-5 SW3-6 SW3-7 SW3-8 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Function Inspection LED reset Normal Backup operation - With Backup operation…
-
(iv) Check procedure depending on indication lamps (For the outdoor unit)
1 Error display : e3 [Error on the outdoor unit signal line] (Detected during operation only) Indoor unit Red LED 2 time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF YES Power supply check between R ~ N or terminal block NO Is there AC 17V checked between CNA2…
-
Error display : e5
Red LED Green LED [Outdoor unit signal line error, power supply error] Indoor unit 2 time flash Keeps flashing (1) Outdoor unit Stays OFF Red LED Stays OFF Green LED Did turn off the power of outdoor unit during operatioon? YES Power supply ON NO • Blown fuse? • Broken or loose wire at L1, L2 or N…
-
Error display : Red LED Green LED e30 [Connection error indoor and outdoor unit] Indoor unit Stays OFF Keeps flashing Connection of indoor and outdoor unit OK? Outdoor unit 1 time flash Keeps flashing Red LED Green LED NO Repair YES Defective outdoor unit PCB Replacement 4 Error display : Red LED…
-
Error display : Red LED Green LED e33 [Or overcurrent error (CM2), motor lock (CM1)] Indoor unit Stays OFF Keeps flashing Red LED Green LED Outdoor unit 1 time flash (1) Keeps flashing Note (1) Single flashing of outdoor unit LED indicates CM1 and double flashing indicates CM2. Is AC 380V or 415V…
-
Error display
Red LED Green LED e37 [Defective outdoor unit heat exchanger thermistor] Indoor unit Stays OFF Keeps flashing Is the outdoor unit heat exchanger themistor connector OK? Outdoor unit 1 time flash Keeps flashing Red LED Green LED Are the outdoor unit heat exchanger themistor characteristics OK, is…
-
Error display : Red LED Green LED e39 [Defective discharge gas thermistor] Indoor unit Stays OFF Keeps flashing Outdoor unit 1 time flash (1) Keeps flashing Red LED Green LED Note (1) Single flashing of outdoor unit LED indicates Th0-1 and double flashing indicates Th0-2. Are the discharge gas…
-
Error display : e4 1 Red LED Green LED [Power transistor overheating] Indoor unit Stays OFF Keeps flashing Red LED Green LED Does the FMO rotate? Power transistor overheating(1) Outdoor unit 1 time flash Keeps flashing YES Is the outdoor unit installation space proper? NO YES Does the IM (Inverter…
-
Current cut is indicated and the compressor cannot operate
Is the insullation resistance of the compressor(1) proper? Disconnect the compressor wiring YES Notes (1) when a short-circuit or ground-fault occurs in the compressor motor, the current cut function is also activated. If the insulation resistance is 10MΩ or more, it is normal. The insulation…
-
Error display : e43 Red LED Green LED [Excessive number of indoor units connected] Indoor unit Stays OFF Keeps flashing Outdoor unit 1 time flash Keeps flashing Red LED Green LED Doesn't the number of indoor unit connected exceed the specified value? (1) YES Repair NO Power supply reset Is it…
-
Error display : e46 Red LED Green LED Automatic address setting and manual address setting coexstents in the same network Indoor unit Stays OFF Keeps flashing Red LED Green LED Outdoor unit 1 time flash Keeps flashing Are automatic YES address and manual address coexstent on the same network Repair…
-
Louver motor does not operate
▼ 2) Inspect at the indoor unit side. Does the louver operate at power on? Operate more than 1 min. later NO NO Is LM wire broken? YES YES YES NO Defective indoor unit PCB YES Repair the wire Is the louver operated with the remote controller Is LM locked? Replace LM Normal NO It is normal if it…
-
(ii) When the compressor does not operate although the remote controller display is normal (Without the check display) Take following steps first before confirming the following items: • Confirm that it is normal at the indoor unit side, LED1 (green) keeps flashing on the outdoor unit control PCB…
-
Procedure for checking the outdoor unit irrespective of indoor/outdoor transmission
Turn off the outdoor unit power supply (Or pull out the connector CnA2 on the outdoor unit PCB) Set 45 in outdoor unit No. Turn ON the outdoor unit PCB (SW3-8) Turn ON the outdoor unit power supply Open the 63H1 (When connecting the CnA2 on the outdoor unit PCB) (Pull out Faston No.T24 on the PCB)…
-
Inverter inspection procedures (There is no output on the compressor (U,V,W).) NO Is 52C turned ON? Inspect control PCB at outdoor side. YES Error on the power supply system Is LED1 (green) on inverter PCB flashing? NO Is DC 540V detected at CNW on inverter PCB? NO Remote controller trouble code E45…
-
When the heating effect is insufficient
• Check if the protective function (1) has operated and, as a result, the compressor operation frequency has dropped below the specified frequency. Note (1) The frequency drops when the high pressure control (Operated at 63H2:2.50 open/2.06 close, Mpa (25.5 open/ 21close kgf/cm2)[FDCP:2.79open/2.26…
-
TB
If good 52C 7-segment indicator ~ 2 ~ 3 ~ 1 5 CN11 Detail of communication It is normal if 5V or abnormal if 0V It is normal 5V or abnormal if OV 6 Inverter overheat 7 Current cut Swings between 4.5 ~ 5V 4 Receiving from inverter Watchdog (Communication from Swings between 2 ~ 4V 5 invert PCB to…