19.2.4 Exterior appearance
(1) Indoor unit (a) Ceiling recessed type (FDT) ¡ Decorative panel Pearl white (b) 2-way outlet ceiling recessed type (FDTW) Air outlet Air inlet ¡ Decorative panel (i) Standard type Panel part No. Type Panel color With Auto swing Pearl white TW-PSA-22W-E TW-PSA-32W-E Applicable model FDTW28, 45, 56…
-
(c)
1-way outlet ceiling recessed type (FDTS) Panel Ceramic white Air inlet grille Ceramic white ¡ Decorative panel Panel part No. TS-PSA-26W-E TS-PSA-36W-E Type Panel color With Auto swing Misty white Applicable model FDTS22, 28, 36, 45 type FDTS71 type (d) Cassetteria type (FDR) Silent panel type…
-
(g) Wall mounted type (FDK)
3 2 No. Parts name 1 Side plate 2 Front panel 3 Inlet grill 4 Outlet grill 5 Bottom plate 6 Right and Left louvers Color Ceramic white Light gray (h) Floor standing exposed type (FDFL) Dark gray (Outlet grill) Ceramic white (Body) Black (Bottom plate) (i) Floor standing hidden type (FDFU) Zinc steel…
-
Indoor B unit Strainer FDCP type: Check Joint 63H1 · OFF 3.24 MPa (33kgf/cm2), ON2.65MPa (27kgf/cm2)(For protection) 63H2 · OFF 2.79 MPa (28.5kgf/cm2), ON2.26MPa (23kgf/cm2)(For heating FMo and control of high pressure) Sub-cooling coil Accumlator Thermistor (ThO-R) Cooling cycle Expansion valve…
-
Indoor B unit
) Thermistor (ThO-D1) Suction Strainer FDCP type: 63H1 · OFF 3.24 MPa (33kgf/cm2), ON2.65MPa (27kgf/cm2)(For protection) 63H2 · OFF 2.79 MPa (28.5kgf/cm2), ON2.26MPa (23kgf/cm2)(For heating FMo and control of high pressure) Solenoid valve (SV2) Sub-cooling coil Accumlator Thermistor (ThO-R) Cooling…
-
19.2.6 Selection chart
(1) Correct the cooling and heating capacity in accordance with the conditions as follows.The net cooling and heating capacity can be,obtained in the following way. Indoor unit Each indoor unit = System performance × Indoor unit capacity Indoor unit capacity when operating simultaneously. Outdoor…
-
(c)
When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when the outdoor unit is located at a higher height than the indoor unit in heating operation, the following values should be subtracvted from the values in the above table. Height difference between the…
-
(Standard) 0 0 Total capacity of indoor unit to be operated simultaneously Cooling 31.5 Heating Rated capacity Rated capacity Rated capacity 22.4 22 Rated capacity 26 28 System capacity (kw) 790 System capacity (kw) FDCP224HKXE2B,FDCJ224HKXE2B (Standard) 250 Cooling 350 364 Total capacity of indoor…
-
(3) Sensible heat capacity
(a) FDT Series Model FDTJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.89 2.83 2.76 2.68 2.60 2.53 2.46 TC 2.98 2.91 2.85 2.77 2.70 2.63 2.56 TC 3.05 2.99 2.92 2.86 2.80 2.72 2.64 TC 3.13 3.07 3.01 2.95 2.88…
-
Model FDTJ71KHXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 7.33 7.18 7.00 6.80 6.60 6.42 6.23 TC 7.55 7.39 7.22 7.04 6.85 6.67 6.48 TC 7.75 7.58 7.41 7.26 7.10 6.90 6.70 TC 7.94 7.78 7.63 7.47 7.31 7.13 6.94 TC 8.13 7.99 7.83 7.66…
-
(b) FDTS Series
Model FDTSJ22HKXE2B Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.27 2.22 2.17 2.11 2.05 1.99 1.93 TC 2.34 2.29 2.24 2.18 2.12 2.07 2.01 TC 2.40 2.35 2.30 2.25 2.20 2.14 2.08 TC 2.46 2.41 2.36 2.31 2.27 2.21 2.15 TC…
-
Model FDTSJ71HKXE2B
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 SHC 5.56 5.49 5.41 5.33 5.23 5.15 5.06 18.0°CWB TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 SHC 5.59 5.52 5.45 5.37 5.30 5.21 5.13 19.0°CWB TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 SHC 5.61 5.55…
-
Model FDRJ56HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 5.80 5.67 5.53 5.39 5.21 5.07 4.91 TC 5.97 5.84 5.70 5.57 5.43 5.25 5.11 TC 6.13 6.00 5.87 5.73 5.60 5.47 5.30 TC 6.25 6.15 6.04 5.90 5.77 5.63 5.50 TC 6.42 6.28 6.17 6.07…
-
Model FDRJ140HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB TC 14.50 14.17 13.83 13.47 13.02 12.68 12.26 SHC 10.78 10.63 10.48 10.31 10.12 9.97 9.78 18.0°CWB TC 14.92 14.59 14.25 13.92 13.58 13.13 12.77 SHC 10.84 10.69 10.55 10.40 10.26 10.07 9.91 19.0°CWB TC 15.32 15.01 14.67 14.34…
-
Model FDUMJ71HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 TC 8.14 7.97 7.82 7.70…
-
(e) FDE Series
Model FDEJ36HKXE2B Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 TC 4.13…
-
Model FDEJ112HKXE2B
Air flow 3 (m /min) 28 Indoor air temperature Outdoor air temp. 17.0°CWB (°CDB) TC 11.60 11.33 11.07 10.77 10.42 10.15 9.81 SHC 8.72 8.60 8.48 8.35 8.20 8.08 7.93 18.0°CWB TC 11.94 11.67 11.40 11.13 10.86 10.51 10.21 SHC 8.77 8.66 8.54 8.42 8.31 8.16 8.04 19.0°CWB TC 12.25 12.01 11.74 11.47 11.20…
-
Model FDKJ36HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 TC 4.13 4.04 3.97 3.90…
-
(g) FDFL, FDFU Series
Models FDFLJ28HKXE2, FDFUJ28HKXE2 Air flow 3 (m /min) 12 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.90 2.83 2.77 2.69 2.60 2.54 2.45 TC 2.98 2.92 2.85 2.78 2.72 2.63 2.55 TC 3.06 3.00 2.93 2.87 2.80 2.73 2.65 TC 3.12 3.07 3.02 2.95 2.88…
-
19.2.7 Characteristics of fan
(1) Cassetteria type (FDR) How to interpret the blower characteristics table ¡ External static pressure table Duct specs. Example : Case of FDRJ71HKXE2 1 2-spot blowout Square duct (3) 40 (4) 45 (4.5) 85 (8.5) 45 (4.5) 85 (8.5) FDR45 56 type FDR71 type 14 - - 50 (5) 85 (8.5) 50 (5) 18 30 (3) 65…
-
Models FDRJ45HKXE2, 56HKXE2
-
Model FDRJ140HKXE2
-
(2) Satellite ducted type (FDUM)
¡ External static pressure table Duct specs. 1 spot closing Standard Square duct Example : Case of FDUMJ71HKXE2 40 (4) 18 35 (3.5) 70 (7) FDUM90 type 20 30 (3) 65 (6.5) 50 (5) 85 (8.5) 55 (5.5) 90 (9) FDUM112 type 28 50 (5) FDUM140 type 34 50 (5) 75 (7.5) 60 (6) 85 (8.5) 65 (6.5) 95 (9.5) Static…
-
Model FDUMJ71HKXE2
-
19.2.8 Noise level
-
Model FDTWJ90HKXE2B
-
(d) Cassetteria type (FDR)
Unit 1.5m Measured based on JIS B 8616 Mike position as below Mike (center & low points) Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Model FDRJ28HKXE2 Models FDRJ45HKXE2, 56HKXE2 Noise level 43 dB (A) at HIGH Noise level 44 dB (A) at HIGH 41 dB (A) at MEDIUM 41 dB…
-
Mid octave band frequency (Hz)
-
1m
-
Model FDKJ56HKXE2
Noise level 46 dB (A) at HIGH 43 dB (A) at MEDIUM 39 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Model FDKJ71HKXE2 Noise level 47 dB (A) at HIGH 44 dB (A) at MEDIUM 40 dB (A) at LOW Mid octave band frequency (Hz) Mid octave band…
-
TB
-
FMI
-
49FI
-
WH
-
CFI1,2
-
таблицы и схемы — в просмотре
-
FMI
-
TB
-
CM
-
Y/GN
-
19.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Remote controller (Optional parts) FDR, FDUM, FDFL and FDFU series are not provided with AUTO SWING switch. Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for the purpose of explanation. Pull the knob on the cover to this side…
-
(2) Operations of major functional items under each operation mode
Operation mode Cooling Functional item Heating Fan Thermostat ON Thermostat OFF Complete stop Thermostat ON Thermostat OFF Defrosting Indoor unit fan Remote controller Remote controller Remote controller Remote controller Intermittent operacommand command command command tion (3) →× Indoor unit…
-
Dehumidifying (Thermal dry) [Indoor unit adaptation] D C Low -2°c B ▲ A +2°c High Room temperature setting point • Indoor unit fan will be operated in D block as shown below. 20 sec. Lo OFF 4 min. Temperature check (5) 22 model 28 model 36 model 45 model 56 model 71 model 90 model 112 model 140…
-
Outdoor unit heat exchanger temp
(Tho-R) (d) Defrosting (i) Conditions for starting defrosting When all the following conditions are met, the defrosting operation will start: 1) The cumulative operating time of the compressor comes up to 48 minutes after completion of a defrosting operation, or it comes up to 33 minutes after a…
-
(e) Compressor operation frequency UP control
1) If any indoor unit demands the maximum frequency for more than 3 minutes continuously during heating operation (provided either one of the following conditions is met), the compressor operation frequency will be increased by 5 Hz. Further increase of 5 Hz will repeat at each time when the maximum…
-
Compressor protection control
(i) Start of compressor protection 1) Inverter is operated at the frequency not exceeding the upper limit of 65 Hz for 1 minute and 45 seconds after the start in order for protection of compressor and then changes the frequency to the selected frequency. CM2 (for 224, 280) is stopped for the same…
-
[Hz]
To target frequency 5 Hz/min. Hour [Hz] 5 Hz/2-min. Note (1) If operation is stopped within 20 minutes, second and later starts are subject to this control. (d) Under-dome temperature control Fluid bypass solenoid valve (SV1) and indoor expansion valve are controlled based on the temperature of…
-
(ii)
Compressor control Retention Compressor capacity is reduced. Compressor capacity is reduced at every minute. Reset 115°C 120°C Discharge pipe temperature ( Tho-D1 ) (iii) Discharge pipe temperature error • When the discharge pipe temperatures (Tho-D1, D2 detection) rise beyond 130˚C and is…
-
(l)
Non-inverter compressor (CM2) overcurrent protection (Only for 224, 280 models) If the T phase current at the secondary side of 52C2 is detected exceeding the setting value for approx. 0.5 second, the compressor stops. The compressor is reset automatically after a 3-minute delay. If the error is…
-
Cooling operation control at lower outdoor air temperature (down to –5˚C) (a) This control starts 1 minute after starting compressor during cooling or dehumidifying operation, controls the outdoor fan at the outdoor temperature (Tho-A) being below 22˚C and enables the cooling operation. Disabled…
-
Silent mode control Silent mode is selected if the CnG (equipped with short circuiting pin) is shorted during normal operation. (a) When the highest speed for the specific model of outdoor fan (140 : 3 speed, 224, 280 : 4 speed) is selected, the speed is stepped down by one step. However, the…
-
(17) FILTER sign
When the operation time (time when the ON/OFF switch is turned to ON) is counted up at 600 hours (1), the filter sign on the remote controller flickers. This condition can be reset any time with the “Filter reset” switch. It is effective also to turn power OFF to reset. Note (1) The function is…
-
Indoor unit operation mode
OFF (1) COOL DRY During compressor ON FAN (2) HEAT Control A During compressor OFF Notes (1) Including OFF and error stop during COOL, DRY, FAN and HEAT. (2) Including “FAN” operation due to unmatch of operation mode. Control B • Flow chart of drain motor operation Float switch operation (Contactor…
-
(b) Control of input signal
(Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control unit.) Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit. However, when the operation…
-
(22) External input operation
External input: From CnS1, operation permission/prohibition control; From CnS2: Demand control/normal operation switching. • J1: Switches between CnS1 and CnS2 input method. J1 short circuit: Level input by CnS1 and CnS2. J1 open: Pulse input by CnS1 and CnS2. (a) From CnS1, operation…
-
(b) From CnS2, operation permission/prohibition control
Input : CnS2 CnS2 input method Formula switching: J1 Short circuit J1; Short circuit Level input Demand control Normal operation J1; Open circuit Pulse input Normal operation/Demand control switching (Reversal) J1; Short circuit Normal operation Demand control Open circuit Short circuit Open circuit…
-
19.5 APPLICATION DATA
SAFETY PRECAUTIONS • Please read these “Safety Precautios” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in…
-
19.5.1 Installation of indoor unit
(1) Ceiling recessed type (FDT) h (a) Selection of installation location 1) Select location where the space above ceiling is larger than those mentioned Space above ceiling (h) Type below and perfect draining can be assured. FDT28, 36, 45, 56, 71, 90 Over 270mm 2) Places where perfect drainage can…
-
1) Drain piping should always be in downhili grade (1/50 ~ 1/100) and avoid riding across and elevation or making traps. • Good piping Suspension bolts • Improper piping Avoid riding across an elevation 1.5 m ~ 2 m Air vent Keep free from traps Do not pipe under water Heat A downhill grade…
-
(e) Fixing of Decorative Panel (The panel fixing bolts are attached on the panel.)
1) Check with the accessory level gauges that indoor unit height and the size of ceiling hole are correct. • Remove the level gauges from the indoor unit before fixing the decorative panel. 2) Screw two bolts out of four accessory bolts less than 5 mm in the indoor unit diagonally. 3) Hang the panel…
-
(2) 2-way outlet ceiling recessed type (FDTW)
(a) Selection of installation location 1) This unit is a ceiling surface direct return air and direct supply air type. Install the unit a place the allows air to reach every part of the room, in accordance with the shape and heigh of the room. • Installation space 100 or more 2) 1000 or more Unit…
-
Places exposed to oil splashes or steam (e.g. kitchens and machine plants.) Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts. 9) Places where corrosive gas (such as sulfurous acid gas) or…
-
1) Open the hole in the installation location to the ceiling opening dimensions. 2) Outlet port Install the suspension bolts (procured locally) at the Pattern paper designated locations. (Use care as the center of the spacing for the suspension Ceiling surface bolts is not at the center of the…
-
When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, 3) For drain pipe, use hard PVC ganeral purpose pipe VP-25 (I.D.1'') which can fix the piping at a point as close as possible to the unit. Level difference part Drain…
-
Note (1) If the connector remains connected, drain water is discharged from the standard pipe connecting port, leading to water leakage. Clear flexible tubing (optional) Hard vinyl chloride piping. Heat General piping VP-20 insulation Rubber plug Remove CNR (Blue·2P) Control box Natural drain port…
-
a)
Remove the panel from the pin (A) in the order of the arrows 1 and 2. b) Open the panel slightly as shown by the arrow 3 and move it to the arrow 4. Then remove it from the pin (B). 2) Screw two bolts out of four accessory bolts less than 5mm in the panel diagonally. 3) Hook the panel on the two…
-
(3) 1-way outlet ceiling recessed type (FDTS)
Preparation of indoor unit It can be installed by either one of the following methods. Select the most adequate method for your particular case. A Standard installation B Higher ceiling Ceiling Ceiling Installation example and limitation 3m ~ 4m 3m or less Floor Floor Note (1) In the case of…
-
Where a space as shown below can be secured
Unit : mm 100 or more 1000 or more 2000 or more 6) 100 or more Obstacle 7) It should be avoided where a machine generating high frequency waves is installed. 8) Select a place to branch the piping so that same distance will be a obtained for each of one way piping. 9) Where humidity may exceed 80%…
-
c) Fixing of Suspension bolt. Fix the bolts securely as shown below or by any other adequate means
Insert Hole-in anchor bolt Hole-in plug Concrete Suspension bolt, M10 d) Installation Drain pump box Unit Duct connection opening for blowing through lowered ceiling. Suspension fixture (4 places) Procedures 1 Install nuts on the Suspension bolts at onside. Suspension the suspension fixtures on the…
-
Check of levelness
Check the levelness as follows. Use a level gauge or adjust the levelness with the following method. Adjust the bottom of main unit and the water level as shown below. Piping side Water injection Water level 0~3 mm Vinyl pipe Slightly lower the piping side 2) Drain pipe a) Set the drain pipe as a…
-
Drain test
[Perform this before installing the ornament panel] ● Perform this upon completion of electrical work. ● Gradually introduce 2,000~3,000cc of water as shown below. Drain piping connection port Fill from outlet port Pour water into a convex joint ( If the electrical work has not been completed…
-
Approx. 15 mm
2 Mount the two (M5 x 35) panel mounting screws to the indoor unit A Detail of Section A 3 Hang the panel on the two mounting screws on the indoor unit by using the two shaped holes. Slide the panel approximately 10 mm. Use the 5 panel mounting screws to secure the panel. Sliding direction 4 Use the…
-
(4) Cassetteria type (FDR)
(a) Preparation of indoor unit Before of during the installation of the unit, assemble necessary optional panel, etc. depending on the specific type. (b) Select places for installation satisfying following conditions and, at the same time, obtain the consent on the part of your client user. 1)…
-
2) Ceiling hole size and position of suspersion bolt
When boring at the ceiling, use the pattern sheet included in the accessory of the unit. Leave the pattern sheet on the unit till decorative panel is installed. < Combination with silent panel > Unit : mm 57 A (Suspension bolt pitch) B (Celing hole size) C (Panel dimensions) 57 30 (Panel dimensions)…
-
2) Adjusting the unit’s levelness
1 Adjust the out-of levelness using a level vial or by following method. ● Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below. Piping side Supply water Water level 0 ~ 5 mm PVC hose Bring the piping side slightly…
-
Abt. 30 mm
2 Install the panel outer frame on the Indoor unit. Indoor unit Panel outer frame Temporary setting Panel inner frame Procedures of installation 1 Secure the panel tentatively with 2 of 4 panel set screws (panel accessory) as shown above. 2 When the panel is supported with a pair of set screws…
-
2 Remove the panel inner frame
It can be removed same as the silent panel. Panel inner frame Panel outer frame Remove < How to remove the panel inner frame > Pin (B) Pin (A) Panel outer frame 1 2 Panel inner frame 3 4 ● Detach from pins (A) in the order of arrow 1 → 2 ● Open slightly as shown by the arrow 3. move in the 4 arrow…
-
● Hook the chain of panel outer panel on the holder
Note (1) When hooking the chain. make sure to avoid slackness on it by pushing hard the panel outer frame against the ceiling material. Ceiling material ● Tighten 3 screw in the step 1 till the panel outer frame contacts closely with the ceiling material. ● Secure the canvas duct and the panel outer…
-
● Use a band, etc. to connect the indoor unit and the supply air duct flange
● Conduct the duct installation work before finshing the ceiling. (g) Connection of air inteke and exhaust ducts. State seeing from top of unit Exhaust Port Side fresh air intake port Rear fresh air intake port Fig.1 Fig.2 1) Duct connecting position a) Fresh air intake ● Inlet can be selected from…
-
(h) Drain piping
1) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or making traps. ● Improper piping ● Good piping Suspension bolts Avoid riding across an elevation 1.5 m ~ 2m Air vent Keep free from traps Do not pipe under water Heat insulation A downhill grade…
-
9) Drainage test
a) During trial operation, make sure that drainage is properly execued and check that leakage is not found at connections. b) Be sure to carry out a drainage test when installing the system during a heating season. c) When installing the system in a building under construction, carry out the…
-
(5) Satellite ducted type (FDUM)
(a) Selection of installation location 1) Avoid installation and use at those places listed below. a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants). Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or…
-
(b) Suspension
Be sure to observe the finished length of the suspension bolts given below. Unit : mm Mark 545 Models A A FDUM36, 45, 56 type 786 FDUM71, 90 type 986 FDUM112, 140 type 1406 1) Fixing the suspension bolt (customer ordered parts M10) Securely fix the suspension bolt as illustrated below or in another…
-
(c) Duct installation
1 Supply air duct (to be purchased locally) 4 Return air duct (to be purchased locally) Heat insulation Indoor unit Supply air port (to be purchased locally) 2 Access door 5 Return air port with canvas duct (to be purchased locally) 3 Return air port (to be purchased locally) 1 Supply air duct Same…
-
1) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or makeing traps. ● Improper piping ● Good piping Suspension bolts Avoid riding across an elevation 1.5 m ~ 2m Air vent Heat insulation Keep free from traps Do not pipe under water A downhill grade…
-
9) Drainage test
a) During trial operation, make sure that drainage is properly execued and check that leakage is not found at connections. b) Be sure to carry out a drainage test when installing the system during a heating season. c) When installing the system in a building under construction, carry out the…
-
(6) Ceiling Supension type (FDE)
(a) Selection of installation location 1) A place where good air circulation and delivery can be obtained. Cold air throw Unit : m Models FDE36, 45, 56 type FDE71 type FDE112 type FDE140 type Air throw 7.5 8 9.5 10 Conditions (1) Installation height: 2.4 ~ 3.0 m above the floor (2) Fan speed: Hi (3)…
-
b) Positions of suspension bolts are as in the drawing below
● When the suspension brackets face in ● When the suspension brackets face out Suspemsion bolt hole Suspemsion bracket 50 31 Suspension bracket B D Suspemsion bolt hole 650 Air outlet 240 5 A A Air outlet 8 31 C D 8 31 Unit : mm Mark A B C D FDE36, 45, 56 type 1000 FDE71, 112 type 1260 1160 1244…
-
2) In case of exposed installation to the ceiling ( with suspension brackets facing in)
25 ~ 45 mm a) Fix the suspension brackets to suspension bolts Ceiling boards Suspension bolt [M8~M10 (3/8¨)] Suspension bracket (accessory parts) Flat washer (accessory parts) Hexagonal nuts (accessory parts) b) Hook the unit to suspension brackers Suspension bracket Suspension bracket fixing bolts…
-
b) Installation space dimensions
80 (FDE112,140) Unit upper side (Plug in dimensions) (FDE36,45,56,71) Unit: mm Ceiling board 10 c) Mount the unit using suspension bolts Suspension bolts Flat washer (accessory parts) Hexagonal nuts (accessory parts) d) Securely tighten the nuts and fix the indoor unit place. e) Attach the side…
-
(7) Wall mounted type (FDK)
(a) Selection of installation location 1) Select the best position and direction depending on the shape of room and height of ceiling to ensure that the cooled or warmed air will be circulated sufficiently. cooled air throw Unit : m 200 mm or more Item Models FDK22 type FDK28 type FDK36, 45 type…
-
(c) Installation
1) Use an attached pattern sheet and mark the position of screws to attach the mounting plate. 2) Determine the direction to lead the pipe and bore a through hole on the wall aligning with the pipe hole of unit. Wall Indoor Outdoor Sealing plate Wall Sleeve ø 70 mm Sleeve Cut the sleeve for the…
-
6) Hook and install the indoor unit on the mounting plate
from top. Hook slightly at left at first and return to right. 7) Fix the indoor unit on the mounting plate with a screw. 8) Install the lower panel at the original position. 9) Install the right and left side panels at their original position. 10) This is all for the installation. 876
-
(8) Floor standing exposed type (FDFL)
(a) Selection of installation location 1) A place where good air circulation and delivery can be obtained. Cooled (warmed) air throw Unit : m Models All models Air throw 4 [Conditions] (1) Fan speed: Hi (2) Location: Free space without obstacles (3) Distance of reach indicates the horizontal…
-
1) Floor standing installation a) Position of mounting bracket fixing bolts Drill holes by referring to figures below. When fixed on the wall Bolt for wall mounting 4 places Hole for piping & wiring on wall 30 Wall When fixed on the floor Hole for piping & wiring on floor 2 places Note (1) Be sure…
-
The drain piping can be directed to the floor or rear sides as follows
(a) Connect a drain piping to the drain outlet and fix it by use of tigghening band. (b) Indoor side drain piping must be thermally insulated. (c) After finishing the drain piping, check the drainage by pouring some water in the drain pan. Up-and-down bend Bad Bad Trap Decrine (e) Installation of…
-
4) Wiring route
a) Wire from the wiring hole through the rear side of the control box to the terminal block. b) Any suplus wires should be tied up with a cable tie. Remote controller installation section Cable tip Control box Front Side (8) Floor standing hidden type (FDFU) (a) Selection of installation hidden…
-
(b) Bolt positions
1) Bolt positions for metal settings used for floor fixation. 2) Bolt positions for wall fixation • Metal fitting used for floor fixation (accessories). unit : mm 1150(1435) unit : mm 112 786 (1071) 179 Bolt positions for floor mounting hardware Floor mounting hardware Accessory 10 x 30 elongated…
-
The drain piping can be directed to the floor or rear sides as follows
(a) Connect a drain piping to the drain outlet and fix it by use of tigghening band. (b) Indoor side drain piping must be thermally insulated. (c) After finishing the drain piping, check the drainage by pouring some water in the drain pan. Up-and-down bend Bad Bad Decrine 19.5.2 Trap Installation of…
-
(e) Set necessary functions in accordance with the model of indoor unit
Refer to (c) for the setting of functions. (3) Setting the functions Change the setting of selector switches (WS1 ~ SW4) (f ) Couple the upper case with the lower case as they were. and jumper wires (J1~ J4) in accordance the functions of (g) Secure the remote controller cords on the wall or other…