Direct Heating Commercial Heat Pump 50Hz Technical Manual Applicable Model: RSJ-120/ZN1-540V1 RSJ-200/SZN1-540V1 RSJ-420/SZN1-H RSJ-800/SZN1-H Midea reserves the right to discontinue, or change specification or designs at any time without notices and without incurring obligations. 1 Midea CAC…
-
Part 1 General Information
1 Product lineup 4 2 External appearance 4 3 Nomenclature 5 3 Midea CAC Confidential
-
Product lineup
-
Nomenclature
RSJ - 200 / S Z N1 - 540V1 Design code Refrigerant Type N1:R410A Heating Type Z: Direct heating Power Supply S: 380~415V, 50Hz, 3Ph Omit for 220~240V, 50Hz, 1Ph Rated heating capacity of heat pump (*100W) Midea air source heat pump water heater 5 Midea CAC Confidential
-
Features
High efficient, COP is up to 4.04 (20kW, 39kW) and 4.00 (12kW, 80kW). Unit applies refrigerant heating technology to increase the total energy absorb. Refrigerant E-heater design can ensure that hot water can be produced stably during defrosting period. Multi protection: High and low…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Specifications Table 2-1.1: RSJ-120/ZN1-540V1 specifications Model name RSJ-120/ZN1-540V1 Power supply V/Ph/Hz 1 Water heating 220-240/1/50 Capacity kW 11.8 Rated power input kW 2.95 COP 4.00 Max. power input kW 3.7 Max. input current A 18.0…
-
Table 2-1.2: RSJ-200/SZN1-540V1 specifications
Model name RSJ-200/SZN1-540V1 Power supply V/Ph/Hz 1 Water heating 380-415/3/50 Capacity kW 20.4 Rated power input kW 5.05 COP 4.04 Max. power input kW 7.80 Max. input current A 13.3 Type Scroll Quantity Compressor Outdoor fan 1 Capacity kW 16.2 Input kW 5.2 Rated current (RLA) A 9.1 Locked rotor…
-
Table 2-1.3: RSJ-420/SZN1-H specifications
Model name RSJ-420/SZN1-H Power supply V/Ph/Hz 1 Water heating 380-415/3/50 Capacity kW 39.0 Rated power input kW 9.65 COP 4.04 Max. power input kW 14.5 Max. input current A 24.0 Type Scroll Quantity Compressor 1 Capacity kW 29.2 Input kW 9.2 Rated current (RLA) A 20 A 118 ⁰C 135 Locked rotor Amp…
-
Table 2-1.4: RSJ-800/SZN1-H specifications
Model name RSJ-800/SZN1-H Power supply V/Ph/Hz 1 Water heating 380-415/3/50 Capacity kW 80.0 Rated power input kW 20.0 COP 4.0 Max. power input kW 26.0 Max. input current A 45.0 Type Scroll Quantity Compressor 2 Capacity kW 29.95 Input kW 9.5 Rated current (RLA) A 20.7 A 142 ⁰C 135 Locked rotor Amp…
-
Dimensions
Figure 2-3.1: Dimensions of RSJ-120/ZN1-540V1, RSJ-200/SZN1-540V1 (Unit: mm) 12 Midea CAC Confidential
-
Figure 2-3.2: Dimensions of RSJ-420/SZN1-H (Unit: mm)
13 Midea CAC Confidential
-
Figure 2-3.3: Dimensions of RSJ-800/SZN1-H (Unit: mm)
14 Midea CAC Confidential
-
MCAC-HTSM-201906 Service space Figure 2-4.1: Service space of RSJ-120/ZN1-540V1, RSJ-200/SZN1-540V1 (Unit: mm) 15 Midea CAC Confidential
-
Figure 2-4.2: Service space of RSJ-420/SZN1-H (Unit: mm)
16 Midea CAC Confidential
-
Figure 2-4.3: Service space of RSJ-800/SZN1-H (Unit: mm)
17 Midea CAC Confidential
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Refrigerant circuit Figure 2-5.1: Refrigerant circuit of RSJ-120/ZN1-540V1, RSJ-200/SZN1-540V1 18 Midea CAC Confidential
-
Figure 2-5.2: Refrigerant circuit of RSJ-420/SZN1-H
19 Midea CAC Confidential
-
Figure 2-5.3: Refrigerant circuit of RSJ-800/SZN1-H
20 Midea CAC Confidential
-
MCAC-HTSM-201906 Wiring diagrams Figure 2-6.1:Wiring diagram of RSJ-120/ZN1-540V1 21 Midea CAC Confidential
-
Red
Black Y/G Red White Blue Blue Blue Black Red White AC Contactor I Red White CT1 Red White Blue Black 22 Midea CAC Confidential Brown Brown Current Leakage Protector Black A1 Red 2 White 4 6 SV2 Blue AC Contactor II A2 1 Black 3 Black 5 White Black Black Black Black Red Black TCO Red Blue White Black…
-
Figure 2-6.3: Wiring diagram of RSJ-420/SZN1-H
23 Midea CAC Confidential
-
Figure 2-6.4: Wiring diagram of RSJ-800/SZN1-H
24 Midea CAC Confidential
-
MCAC-HTSM-201906 Main PCB descriptions Figure 2‐7.1: Main PCB description of RSJ-120/ZN1-540V1 Midea CAC Confidential
-
Table 2-7.1: Main PCB descriptions
Label in Figure 2-7.1 CN31 CN32 CN13 CN7 CN57 CN56 CN11 CN17 CN16 CN41 AC Power input Transformer input Compressor contactor control port connection Fan motor connection and refrigerant pipe E-heating connection Electric ball valve on Electric ball valve off Compressor crank E-heating connection…
-
Figure 2-7.2: Main PCB description of RSJ-200/SZN1-540V1 27 Midea CAC Confidential
-
Table 2-7.2: Main PCB descriptions
Label in Figure 2-7.1 Code CN37 CN26 CN27 CN29 CN30 CN34 CN35 11 CN43 CN21 CN15 CN40 CN3 CN2 CN36 CN38 CN28 CN25 CN24 CN41 CN16 CN17 CN11 CN56 CN57 CN7 CN13 CN32 CN42 CN31 Content Current detection Black: Air side heat exchanger temperature sensor connection; White: Ambient temperature sensor…
-
Figure 2‐7.3: Main PCB description of RSJ‐420/SZN1‐H 29 Midea CAC Confidential
-
Table 2-7.3: Main PCB descriptions of RSJ-420/SZN1-H
Label in Figure 2-7.3 Code 0 CN39 Communication port for other unit 1 CN40 Communication port for wired controller 2 CN15 High pressure switch connection 3 CN21 Low pressure switch connection 4 CN30 E-heater pipe Temp. sensor connection of refrigerant 5 CN35 Water tank Temp. sensor connection 6 CN34…
-
Figure 2‐7.4: Main PCB description of RSJ‐800/SZN1‐H 31 Midea CAC Confidential
-
Table 2-7.4: Main PCB descriptions of RSJ-800/SZN1-H
Label in Figure 2-7.4 Code 0 CN39 Communication port for other unit 1 CN40 Communication port for wired controller 2 CN15 High pressure switch connection 3 CN21 Low pressure switch connection 4 CN30 E-heater pipe Temp. sensor connection of refrigerant 5 CN35 Water tank Temp. sensor connection 6 CN34…
-
MCAC-HTSM-201906 Electrical characteristics Table 2-8.1: Electrical Characteristics Model Outdoor unit Power supply (A) Compressor (A) OFM RSJ-120/ZN1-540V1 RSJ-200/SZN1-540V1 RSJ-420/SZN1-H RSJ-800/SZN1-H Voltage 220~240V, 1Ph 380~415V, 3Ph 380~415V, 3Ph 380~415V, 3Ph Min. 198V 342V 342V 342V Max.…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Capacity table Table 2-9.1: RSJ-120/ZN1-540V1 capacity table Mode Outdoor temperature (°C DB) RSJ-120/ZN1-540V1 Inlet water Temp. (°C) Outlet water Temp. (°C) Capacity (kW) COP 40 15.05 5.53 45 15.19 5.35 50 15.18 5.15 55 15.10 4.81 60 14.95…
-
Table 2-9.1: RSJ-120/ZN1-540V1 capacity table (continued)
Mode Outdoor temperature (°C DB) 7 2 Inlet water Temp. (°C) 9 9 RSJ-120/ZN1-540V1 0 -7 -15 Outlet water Temp. (°C) Capacity (kW) COP 40 10.13 3.9 45 10.08 3.48 50 10.52 3.65 55 10.43 3.5 40 9.66 3.08 45 9.04 3.54 50 9.19 3.47 55 9.29 3.31 40 9.35 3.2 45 8.97 2.96 50 9.42 3.2 40 9.42 3.06 45 8.11…
-
Table 2-9.2: RSJ-200/SZN1-540V1 capacity table
Mode Outdoor temperature (°C DB) Inlet water Temp. (°C) RSJ-200/SZN1-540V1 Outlet water Temp. (°C) Capacity (kW) COP 40 29.90 6.08 45 30.37 5.71 50 30.56 5.51 55 30.45 5.19 60 30.15 4.86 40 28.83 5.94 45 29.14 5.70 50 29.16 5.37 55 28.93 5.03 60 28.40 4.66 40 25.36 5.59 45 25.15 5.23 50 24.74 4.82…
-
Table 2-9.2: RSJ-200/SZN1-540V1 capacity table (continued)
Mode Outdoor temperature (°C DB) 2 0 Inlet water Temp. (°C) 9 9 RSJ-200/SZN1-540V1 -7 -15 9 9 Outlet water Temp. (°C) Capacity (kW) COP 40 16.50 3.05 45 12.20 3.11 50 11.90 2.85 55 11.76 2.66 40 11.82 2.45 45 11.65 2.91 50 11.54 2.66 40 11.35 2.52 45 9.71 2.38 50 9.61 2.22 40 9.54 2.13 45 7.23 1.89…
-
Table 2-8.3: RSJ-420/SZN1-H capacity table
Mode Outdoor temperature (°C DB) Inlet water Temp. (°C) RSJ-420/SZN1-H Outlet water Temp. (°C) Capacity (kW) COP 40 55.72 6.36 45 55.40 6.00 50 54.75 5.64 55 54.58 5.28 60 52.46 5.03 40 56.99 6.50 45 55.14 5.89 50 55.00 5.58 55 54.42 5.31 60 52.67 5.19 40 51.15 5.71 45 51.13 5.36 50 50.98 5.05 55…
-
Table 2-8.3: RSJ-420/SZN1-H capacity table (continued)
Mode Outdoor temperature (°C DB) 2 0 Inlet water Temp. (°C) Outlet water Temp. (°C) 9 9 RSJ-420/SZN1-H -7 -15 9 9 Capacity (kW) COP 40 25.76 3.28 45 23.20 2.99 50 20.64 2.72 55 19.59 2.48 40 19.21 2.88 45 21.18 2.83 50 20.65 2.72 40 18.43 2.88 45 19.21 2.80 50 19.60 2.67 40 18.15 2.28 45 17.65 2.13…
-
Table 2-8.4: RSJ-800/SZN1-H capacity table
Mode Outdoor temperature (°C DB) Inlet water Temp. (°C) RSJ-800/SZN1-H Outlet water Temp. (°C) Capacity (kW) COP 40 102.34 5.74 45 102.02 5.42 50 101.36 5.09 55 100.39 4.76 60 99.08 4.44 40 102.27 5.78 45 100.43 5.25 50 100.28 4.97 55 100.05 4.73 60 97.95 4.35 40 94.77 5.39 45 94.75 5.06 50 94.60…
-
Table 2-8.4: RSJ-800/SZN1-H capacity table (continued)
Mode Outdoor temperature (°C DB) 2 0 Inlet water Temp. (°C) 9 9 RSJ-800/SZN1-H -7 -15 9 9 Outlet water Temp. (°C) Capacity (kW) COP 40 55.09 3.44 45 52.53 3.14 50 49.97 2.86 55 47.41 2.60 40 46.87 2.98 45 48.84 2.93 50 49.78 2.82 40 39.46 2.56 45 40.23 2.50 50 40.03 2.38 40 30.46 2.19 45 29.97 2.04…
-
10 Accessories
Table 2-10.1: Accessories Name Shape Quantity Outdoor unit installation and owner’s manual 1 Y-shaped filter1 1 Wired controller 1 Temperature sensor for domestic hot water tank 1 Transit line for wired controller 1 Notes: 1. Y-shaped filter is not available for RSJ-800/SZN1-H 42 Midea CAC…
-
Safety information
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage. The unit must be earthed effectively. The earthing pole of socket must be grounded well, make sure that…
-
Do not operate the unit with a wet hand. An electric shock may be caused. The installation height of power supply should be over 1.8m, if there is any water spattered, separate the power supply from water. A one-way valve must be installed on the water inlet side, which is available from…
-
2.1 Unit outlook
Figure 3-2.1: Unit outlook for RSJ-120/ZN1-540V1, RSJ-200/SZN1-540V1 Figure 3-2.2: Unit outlook for RSJ-420/SZN1-H Figure 3-2.3: Unit outlook for RSJ-800/SZN1-H 46 Midea CAC Confidential
-
2.2 Carrying of unit
Handling rope should at least can bear 3 times of the unit weight, and must go through the handling holes shown in following pictures, and make sure there is enough strength to add a pad between the rop and unit in order to protect the unit. For RSJ-120/ZN1-540V1 and RSJ-200/SZN1-540V1, before…
-
Figure 3-2.6: Lifting of RSJ-800/SZN1-H
2.3 Unit installation caution The unit can be installed on the ground or on the suitable roof, but enough ventilation volume should be ensured in both cases. The unit should not be installed where noise and vibration are required to a certain extent. The installed unit should be sheltered from…
-
MCAC-HTSM-201906 The unit can be installed on the ground or ont the suitable roof, but it should follows the relative standards or laws to all lightnin-proof measures for the whole water heating system. 2.4 Distance of unit ground screws Figure 3-2.7: Distance of unit ground screws (Unit: mm)…
-
2.5 Unit installation space
Figure 3-2.8: Unit installation space (Unit: mm) RSJ-120/ZN1-540V1, RSJ-200/SZN1-540V1 RSJ-420/SZN1-H RSJ-800/SZN1-H 50 Midea CAC Confidential
-
MCAC-HTSM-201906 Ensure there is enough air flow to supply the heat exchanger, take influence of down draft caused by tall building around the unit to air discharge into condenser when installing. If install the unit at a place where ventilation is drastic, such as exposed roofs, short wall or…
-
Table 3-2.3: Water pipe joint specifications for multi units RSJ-200/SZN1-540V1
Amount of units connected in parallel Water inlet pipe joint Water outlet pipe joint 1 DN25 DN25 2 DN32 DN32 3-5 DN50 DN50 6-10 DN65 DN65 Table 3-2.4: Water pipe joint specifications for multi units RSJ-420/SZN1-H Amount of units connected in parallel Water inlet pipe joint Water outlet pipe joint 1…
-
Figure 3-2.10: Multi units connection
Table 3-2.6: Icons explanation Stop valve Motor operated valve Flexible rubber joint (soft-connect) Water pump Water using end Water supply controller Solenoid valve Pressure reducing valve Reflux valve Auto air-exhaust valve Pressure gage E-heater Y-shape filter Water flow switch 53 Midea CAC…
-
2.7 Water tank installation
The water tank temperature sensor (T5) can not be placed in the water or on the water pipe directly. The water tank must be set a temperature pipe where the temperature sensor (T5) is installed. The water tank must have some safety devices to protect it such as temperature cut off switch…
-
RSJ-800/SZN1-H
Circulative heating rated water flow 14 m3/h Water resistance of circulative rated water flow 160 kPa The hot water circulative pump must use hot water pump; the temperature resistance of the circulative water pump cannot lower than 80°C. Rated head of circulative pump: Σ On-way resistance + Σ Local…
-
The unit must be ground wiring reliably. Set leakage protective devices according to the requirements of national technical standard about electric equipment. Power supply wire and signal wire should be arranged properly without interruption to each other, do not contact with connecting pipes…
-
RSJ-420/SZN1-H
Power supply 380-415V, 3Ph, 50Hz Min. wire size Wire size (˂30m) 10# (UL1015) (metal pipe & synthetic resin pipe wire) Ground wire 10# (UL1015) Manual switch 63 A Fuse 50 A Manual switch Leakage protector 30mA 0.1sec below RSJ-800/SZN1-H Power supply 380-415V, 3Ph, 50Hz Min. wire size Wire size…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Specifications of controlling wire Item Size (UL1015) Remarks E-heater controlling wire 18# 2-core Circulating water pump controlling wire 18# 2-core Remote alarm control wire 18# 2-core Communication cable (shield) 22# 3-core Wired…
-
Electric wiring figure Electric control schematic diagram of the unit (Only for reference) MCAC-HTSM-201906 When power supply wire of the wired controller is less than 20m, wiring can be applied as the location shown 59 Midea CAC Confidential
-
as imaginary lines, when it it exeeds 20m, the power adapter is necessery
Pay attention to the power phase sequence, if wrong connection of the phase sequence, the compressor will not operate, and digital screen of the water heater electrical control board will display error code. Change the phase sequence, and powering again until the digital screen does not display…
-
Trial run
3.1 Check list Please check the items before operation in the table 3-3.1. Table 3-3.1: Checking list before operation No. Item 1 Whether the unit is installed firmly. 2 Whether the air inlet and outlet of the unit has obstacle. 3 Whether the dial codes of each unit has dial to the correct position.…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Fault analysis and solutions 4.1 Abnormal phenomena Table 3-4.1: No distribution to malfunctions Phenomena Cause When the unit is defrosting, the sound of the 4-way valve being shifted. Air supply motor stop automatically to defrost. At the…
-
Table 3-4.3: Phenomena need to contact Midea service agency
Phenomena Possible reason Detect and settle measure 1. Power errors. Connected with wrong phase sequence. 2. Wire connection is loosening. Check and fasten again. 3. Relay or fuse errors. Check and repair. 4. Compressor errors. Change the compressor. 1. Fixing screw of the fan is loosening.…
-
4.2 Error code list
Normal display contents: 1. Under standby and no error and protection situation, the main unit will display the detected water tank sensor temperature (T5), the slave unit will display the address of this unit. 2. Under the main unit with T5 situation, display T5 temperature; if without T5 or T5…
-
MCAC-HTSM-201906 When the unit satisfies the unit stopping conditions, the counting of stop frequency will be cleaned. By the way, also it will be cleaned when the unit has not any protection in 10 hours. Otherwise, if switch off the unit by wired controller, the counting of stop frequency will not…
-
4.3 Spot check
Table 3-4.5: Spot check list No. Display Specification 1 Water outlet temperature T1 temperature value 2 Coil temperature T3 temperature value 3 Ambient temperature T4 temperature value 4 Water tank temperature T5 temperature value 5 Refrigerant heating pipe temperature T6 temperature value 6…
-
4.4 Troubleshooting
E1: Power phase sequence error E2: Communication error of host unit and wired controller, main unit and slave unit. E8: Error of circulating water flow detector (only host unit displays). The water flow switch is detected once then circulate pump is on; E8 appears when water flow switch can’t be…
-
E3: Error of water outlet temperature sensor (T1)
E4: Error of water temperature sensor in the water tank (only host unit displays) (T5). E5: Error of air heat-exchanger temperature sensor (T3). E6: Error of outdoor ambient temperature sensor (T4) E7: Error of E-heater pipe temperature sensor (T6). E9: Error of suction temperature sensor (Th). Ed…
-
P0: System low pressure protection. P0 appearances when suction pressure ≤ 0.05MPa
69 Midea CAC Confidential
-
P1: System high pressure protection. P1 appearances when discharge pressure ≥ 4.4MPa
70 Midea CAC Confidential
-
P2: Compressor current of system is overload. P2 appearances when compressor current ≥lo*
-
P4: Protection for discharge high temperature. P4 appearances when compressor discharges temperature ≥ 115°C. 72 Midea CAC Confidential
-
P7: Host unit is not matched with wired controller, host unit will display P7, and wired controller will display E2. (Power supply of wired controller is 10VAC, if the power supply is not stable, the code of protection or error will also be displayed.) 73 Midea CAC Confidential
-
P8: Water outlet high temperature protection. P8 appearances when water outlet temperature ≥ 68°C for more than 2 minutes. C1: Compressor low current protection. C1 appears when compressor current is less than 2A during operation. 74 Midea CAC Confidential
-
MCAC-HTSM-201906 Maintenance All the safety protection devices in the unit will be set before leaving the factory, the user can not adjust or remove them, in case to damage the unit. First switch on the unit or switch off the power for a long-term stop (More than 1 day) and then re-power on, it…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Under using the clean agents, it should accord to the dirt deposition to adjust the detergent concentration, cleaning time and temperature. It needs to neutralize the waste liquid after cleaning; the waste liquid processing should contact…
-
Specifications
Model KJR-51/BMKE-A Input Voltage 10.0V Operating environment temperature Operating RH -10ºC~+43ºC RH 40%~RH 90% Performance Features 2 Touch key operation. LCD displays operation parameters. Multiple timers. Real-time clock (battery life: 5~8 years). Introduction of function buttons The…
-
④ Timing ON/OFF indication (
MCAC-HTSM-201906 ): Indicate the timing information. ⑤ Function icon: : Display when water heater system connects to Modbus network; : Displays when other heat source is provided to the system. : Displays when water heater maintenance is needed. Press and hold ‘AUXILIARY’ key for 3 seconds to…
-
step setting under timing setting status. Press these keys to turn over the unit parameter information under check status. 12 OK key: Press this key to confirm settings. Press and hold this key for 3 seconds to unlock under locking status. 13 Setting key: Setting water temperature, timing and mode…
-
following order each time the key is pressed
The setting options in the dotted line frame are not general setting. The wired controller automatically judges the needed setting according to the model of main unit. Setting water temperature Press the ▲ or ▼ button to adjust the water temperature after the controller is powered on. Or press…
-
means the current setting is the minute of Timer 1 on, press the ▲ or ▼ to adjust, press
key when finished, the LCD will display as the following: At this time the hour of the clock will flash, which means the current setting is the hour of Timer 1 off, press the ▲ or ▼ to adjust, press key when finished, and then the minute of the clock will flash, which means the current setting is…
-
During any period of timing setting to press OK key, the timing periods which have been set will be effective (only if the on and off of one timing period have been set, the setting is effective). Check timing information: to check the timing which has been set, press or key under main page, the on…
-
Midea R410A Direct Heating Type HPWH 50Hz Technical Manual Set clock Press the SET key 4 times to enter clock setting. The hour of the clock will flash, which means the current setting is the hour of the clock, press the ▲ or ▼ key to adjust, press key when finished, and then the minute of the clock…
-
Operation method: press AUXILIARY key twice to enter this function. The
MCAC-HTSM-201906 icon will flash, press OK key to confirm. The ’CYCLE’ icon will be on if the cycle heating running requirement is fulfilled and will be off if not fulfilled. Water pump (reserved for future use) This function is used to run the main water pump in the device installing and…
-
Press the ▲ or ▼ key to adjust the main unit serial number and check 16 unit’s status information from #0~#9. Press or to adjust the check sequence number of one unit and check all the status information of this unit. Check content: Water outlet temperature T1→2, Outdoor pipe temperature T3→3…
-
The wiring should adapt to the wired controller current. Otherwise, electric leakage or heating may occur and result in fire. The specified cables shall be applied in the wiring. No external force may be applied to the terminal. Otherwise, wire cut and heating may occur and result in fire. …
-
4.3 Dimensions
4.4 Wire connection There are two methods to connection between wired controller and main unit. 88 Midea CAC Confidential
-
4.5 Back cover installation
Use straight head screwdriver to insert into the buckling position in the bottom of wired controller, and spin the screwdriver to take down the back cover. Pay attention to spinning direction, otherwise will damage the back cover. Use three M4×20 screws to directly install the back cover on the…
-
Use cross head screws to fix the wired controller bottom cover in the electric control box through the screw bar. Make sure the wired controller bottom cover is on the same level after installation, and then install the wired controller back to the bottom cover. Over fasten the screw will lead…
-
Method 3
4.7 Front cover installation After adjusting the front cover and then buckle the front cover. It should avoid to clamping the communication switching wire during installation. Correct install the back cover and firmly buckle the front cover and back cover, otherwise will make the front cover…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Коммерческие тепловые насосы прямого нагрева MDV серии RSJ: наружные блоки RSJ-800/SZN1-H. Руководство по установке.PDF · 10.78 Mb
- Коммерческие тепловые насосы прямого нагрева MDV серии RSJ: наружные блоки RSJ-420/SZN1-H. Руководство по установке.PDF · 8.60 Mb
- Коммерческие тепловые насосы прямого нагрева MDV серии RSJ: наружные блоки RSJ-120/ZN1-H, RSJ-200/SZN1-H. Руководство по установке.PDF · 3.49 Mb