Инструкция на Коммерческие тепловые насосы прямого нагрева MDV серии RSJ: наружные блоки RSJ-120/ZN1-H, RSJ-200/SZN1-H. Руководство по установке.
Смотрите также: Полное техническое руководство →
Загружаем документ…
Текст инструкции
-
COMMERCIAL HEAT PUMP
INSTALLATION AND OPERATION INSTRUCTIONS Applicable model RSJ-120/ZN1-H RSJ-200/SZN1-H Please read this manual carefully before use and keep it properly. The cover effect drawing is for reference only, and the specific model is subject to the real object.
-
CONTENTS
ACCESSORIES 01 1 INTRODUCTION 01 2 SAFETY CONSIDERATION 02 3 SELECTING THE INSTALLATION LOCATION 3.1 Precautions before installation 04 4 IMPORTANT ITEMS FOR INSPECTING INSTALLATION OF THE UNIT 4.1 Installation 4.2 Electric wiring 4.3 Installation space 4.4 Carrying the unit onto the installing site…
-
7 ELECTRIC CONNECTION OF THE UNIT
7.1 Electric wiring 7.2 Specifications of power supply 7.3 Total horsepower manual switch and fuse capacity 7.4 Selecting the capacity of the manual switch and fuse of the deconcentrator 7.5 When 5-cord shield wire in the accessories pack is not long enough, please refer Table 7-3 7.6 Power cable…
-
ACCESSORIES
Unit Installation & Operation Manual Wire control assembly Water Tank Temperature senso Y-shaped filter Quantity Shape Purpose Unit Quantity / Use for installation (only need for setting the main module) wire controller connection line 1 Shape 1. INTRODUCTION Air outlet Air inlet (3 faces) Exhaust…
-
2. SAFETY CONSIDERATION
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage. The safty precautions listed here are divided into two categories. In either case, important safty information…
-
CAUTION
conductor or telephone earth wire. In order to avoid injury, do not remove the fan guard of the outdoor unit. Do not operate the heater pump with a wet hand. An electric shock may happen. Do not touch the heat exchanger fins. These fins are sharp and could result in cutting injuries. After a long…
-
3.1 Precautions before installation
Decide the correct way of conveying the quipment. Try to transport this equipment with the original package. if the unit needs to be installed on a metal part of the building, electric insulation must be perforned, and the installation must meet the relevant technical standards of electric devices.…
-
If the unit installed in a underground chamber, an indoor room or other hermetic place, please pay attention to where surrounding air, as well as which air exhust and air circulating system. Table 4-1 Model RSJ-120/ZN1-540V1 RSJ-200/SZN1-540V1 Static Pressure (Pa) High Fan Speed (m3/h) Low Fan Speed…
-
5.PIPES CONNECTION OF THE UNIT
During install connective pipe, you must beware that do not let any dust or other foreign substance intrude into pipe system.Water inlet and outlet pipes could be installed as long as the water-heater have been fixed. 5.1 Thermal insulation Thermal insulation materials should be employed to seal up…
-
5.3 Selecting the inlet/outlet pipelines of the RSJ-120/ZN1-540V1 model
Table 5-1 Quantity of units connected in parallel Size of inlet water pipe Size of outlet water pipe 1~2 DN25 DN25 3~5 DN32 DN32 6~10 DN50 DN50 5.4 Selecting the inlet/outlet pipelines of the RSJ-200/SZN1-540V1 model Table 5-2 Quantity of units connected in parallel Size of inlet water pipe Size of…
-
6.2 Water cycle pump selection
Rated head of circulative pump: ∑on-way resistance+∑ local resistance + unit resistance. Rated flow of circulative pump: Rated flow of a single circulation heating unit × Circulating unit quantity. Temp. preservation water tank (Open type) Water outlet L5 port L1 L2 L4 Rated flow when the unit is…
-
6.5 Installing the auxiliary heater
The user can select the auxiliary electric heater, and the master unit provides the control signals of the auxiliary heater (220-240V~ 50Hz). The installation location of the auxiliary heater must strictly comply with the installation schematic diagram. Table 6-3 Quantity of units connected in…
-
7.2 Specifications of power supply (Table 7-1)
Table 7-1 Model Power RSJ-120/ZN1-540V1 220-240V~ 50Hz RSJ-200/SZN1-540V1 380-415V 3N~ 50Hz 7.3 Total horsepower manual switch and fuse capacity (Table 7-2) Table 7-2 Total horsepower(HP) Manual switch(A) Fuse(A) 32 30 7.4 Selecting the capacity of the manual switch and fuse of the deconcentrator.…
-
Table 7-4
Item Power supply Model RSJ-120/ZN1-540V1 RSJ-200/SZN1-540V1 Min. wire size (mm2 ) (Metal pipe & synthetic resin pipe wire) Manual switch(A) RCCB Size Ground Capacity Fuse (Continuous wire length: ≤30 m) 30 mA 220-240V~ Below 6 50Hz 0.1 sec 380-415V 3N~ 50Hz mA 30 Below 0.1 sec 7.6.4 signal wire…
-
CAUTION
When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper distance. (Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A). Black Black Red Red C2 H1 H2 A1 A2 Yellow-Green Blue Brown…
-
Brown Brown Blue Blue White White
Red White Blue Black A B C N C1 C2 H1 H2 A1 A2 Circulating Electric Remote Pump Auxiliary Heater Alarm Power Input Passive switch signal output only, can’t drive the device directly RSJ-200/SZN1-540V1 electric wiring diagram 7.7 Setting wire controller By means of a detachable service panel, the…
-
7.9. Dial code and sensor instructions
Table 7-6 S1 S3 Address code dial (Host unit) D C B E F 0 1 A 2 Address code dial (Slave unit) E D C B A ADDRRSS F choice of auxiliary heater No E-heater (Default) ON ADDRRSS As to slave unit 1, 2, 3, the pointer will be at 1, 2, 3 respectively(invalid when exceeding 3) As a host unit, the pointer…
-
8.2 Characteristics of heat water supply operation
During operation, if outdoor temperature in high degree, the air supply motor will runs at low air volume. 8.3 About heat water supply operation and defrosting function In case of the unit appear frost during water supply , prevent the heating efficiency from decrease, de-frosting operation will…
-
8.8 COP & Cap. and temperature curve
RSJ-120/ZN1-540V1 COP curve of unit 6 COP (W/W) -15 -5 Ambient temperature(℃) Fig.8-1 RSJ-120/ZN1-540V1 Capability curve of unit 35 30 Capability (kW) -15 -5 Ambient temperature(℃) Fig.8-2 16
-
RSJ-120/ZN1-540V1
COP (W/W) COP curve of unit 5 4.5 4 3.5 3 2.5 2 1.5 1 0.5 0 -15 -5 Ambient temperature(℃ ) Fig.8-3 RSJ-120/ZN1-540V1 Capability curve of unit 16 Capability (kW) -15 -5 Ambient temperature(℃ ) Fig.8-4 17
-
Specific data are shown in the following table
Table 8-1 Model Ambient temperature(℃) Inlet water temperature(℃) Outlet water temperature(℃) Capability(kW) COP(W/W) -15 1.7 -7 9 55 6.6 2.5 -2 9 55 7.9 2.8 2.6 8.6 2.9 9.56 3.3 10.4 3.6 12.6 4.2 13.1 4.5 13.3 4.52 14.1 4.65 14.4 4.72 15.1 4.81 -15 9 50 6.7 1.59 -7 9 50 9.5 2.13 11.4 2.52 11.8 2.45…
-
8.9 About RCCB
However this unit with a built-in RCCB, to be on the safe side, pleases install an additional RCCB between in user power supply and the unit. In case the unit cannot act but not attribute to power failure, please check these two RCCB switches at first. Before operate the RCCB inside of units, please…
-
The ground wire is connected correctly
The supply voltage is consistent with the rated voltage of the unit. The air inlet and outlet of the unit is free from obstacles. The RCCB is active. 9.2 Trial run Check whether the switch of the wire controll is normal. Check whether the functional keys of the wire controll are normal. Check…
-
11. SPECIFICATIONS & PARAMETERS OF THE UNIT
Table 11-1 Model RSJ-120/ZN1-540V1 RSJ-200/SZN1-540V1 Heat-water heating volume (kW) 11.8 20.4 Consumed power/ current 2.95kW / 13A 5.23kW / 9.0 A Heat water output value (m3/h) 0.25 0.45 Rated input power (kW) 3.7 7.8 Rated input current (A) 18.0 13.0 Power supply 220-240V~ 50 Hz auto start…
-