Инструкция на Чиллеры с воздушным конденсатором.
McPower 228.2-478.3 Чиллеры с воздушным конденсатором. Справочное руководство.
Смотрите также: Руководство по установке и обслуживанию →
Загружаем документ…
Текст инструкции
-
Product Manual
508 B – 04/01 A Data: January 2004 Supersedes: None Air cooled screw chillers McPower 228.2÷478.3 Standard Efficiency – Cooling capacity from 760 to 1600 kW High Efficiency – Cooling capacity from 820 to 1680 kW 50Hz – Refrigerant: HFC 407C 508 B – 04/01 A – pag. 1/52
-
New air cooled screw chillers McQuay McPower
McQuay International introduces its newest air cooled screw chillers equipped with new single screw compressors. McQuay air cooled McPower are a new range of chillers using the last generation of McQuay StarGateTM Frame 4 single screw compressors. They are manufactured by McQuay to satisfy the…
-
10 different lines
New McPower line is available with two different efficiencies in order to satisfy every kind of requirements. Acoustic flexibility up to 65 dBA thanks to different noise level versions: • • SE Standard Efficiency with COP up to 2,45 (nominal condition-only compressor power input). - ST Standard…
-
The rugged design of the single-screw compressor allows it to be tolerant of liquid slugging. McPower screw chiller will start and operate under conditions that would often destroy other compressors. • Very low loading enhances the bearing and compressor reliability. Due to symmetrical compression…
-
This refrigerant is safe and chemically stable and is listed in ASHRAE Standard-34 (Number Designation and Safety Classification For Refrigertants) as “A-1” refrigerant: lowest toxicity, non-flammable. HFC 407C has “Glide”. Glide describes the property of a refrigerant boiling across a temperature…
-
Electronic expansion valve (EEXV)
McPower air cooled chiller is equipped with the most advanced electronic expansion valve to achieve precise control of refrigerant mass flow. As today’s system requires improved energy efficiency, tighter temperature control, wider range of operating conditions and incorporate new features like…
-
MicroTech II C Plus controller
MicroTech II C Plus controller is installed as standard on all the units; it can be used to modify unit set points and check control parameters. A display illustrates the machine's operating status, programable values and setpoints e.g. temperatures, and pressures of fluids (water, refrigerant).…
-
System security
Phase monitor Freeze protection An evaporator’s flow controller input (stops the unit) Remote on/off input. Regulation type Proportional + integral + derivative regulation on the input probe of the evaporator water leaving temperature. Condensation The condensation can be carried out according to…
-
MicroTech II C Plus remote control
Compatibility with supervisory systems is becoming increasingly important in HVAC. MicroTech II C Plus allows easy interfacing with BMS (Building Management Systems), the external world that can be: • • • Full compatible Siemens, Johnson; Every MODBUS compatible system; ( Satchwell, Honeywell )…
-
Fan Silent Mode - The microprocessor clock switches the fan at low speed according to the client setting (i.e. Night & Day), providing that the ambient temperature/condensing pressure is allowing the speed change. It allows a perfect condensing control down to –18°C Speedtrol – Continous fan speed…
-
Space requirements
The ALS units are air-cooled, hence it is important to observe the minimum distances which guarantee the best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling capacity and an increase in electricity consumption. To…
-
Acoustic protection
The low noise levels of the McPower units means that they meet the most restrictive regulations, thanks to the availability of four versions with different sound levels. When the noise level must meet special requirements it will be necessary to pay the maximum attention to ensure the perfect…
-
Table 5 – Ethylene glycol and low ambient temperature correction factors
Air ambient temperature °C % of ethylene glycol by weight Cooling capacity correction factor Power input correction factor Flow rate correction factor Water pressure drops correction factor -3 10 0,991 0,996 1,013 1,070 -8 20 0,982 0,992 1,040 1,129 -15 30 0,972 0,986 1,074 1,181 -23 40 0,961 0,976…
-
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
McPower unit size Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) McPower unit size Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max…
-
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) A A A A A A 228.2 255.2 1068 524 374.3 395.3 1033 1316 761 1008 1040 46 1086 1343 811 276.2 300.2 400 V…
-
Physical data McPower SE XXN HFC 407C
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
Electrical data McPower SE XXN HFC 407C
Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans…
-
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans…
-
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans…
-
Physical data McPower XE XXN HFC 407C
McPower unit size Cooling capacity (1) Power input (1) COP McQuay singlescrew compressors Refrigerant circuits Oil charge Min % of capacity reduction Condenser fans N° of fans / Nominal power fan Fan speed Diameter Total air flow Evaporator Evaporator / Water volume Max operating pressure Water…
-
Electrical data McPower XE XXN HFC 407C
Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) Grandezza unità McPower Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans…
-
McPower Unit Size 63 Hz 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 418.3 445.3 464.3 478.3 78,5 78,5 79,0 78,0 78,5 78,5 79,0 79,5 79,5 79,0 79,0 79,0 Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 ) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 79,0 79,0 78,5…
-
McPower Unit Size 63 Hz 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 418.3 445.3 464.3 478.3 76,0 76,0 76,0 76,0 76,0 76,5 76,0 77,0 77,5 78,0 77,5 78,0 Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 ) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 73,5 73,5 74,0…
-
276.2 300.2 320.2 340.3 374.3 395.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower SE 228.2 ÷ 395.3 ST, CN TEMPERATURA AMBIENTE - °C 25 Potenza 30 Potenza Potenza 35 Potenza Potenza 40 Potenza Potenza 42 Potenza Potenza Potenza frigorifera assorbita frigorifera assorbita…
-
464.3 478.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower SE 418.3 ÷ 478.3 ST, CN TEMPERATURA AMBIENTE - °C 25 Potenza 30 Potenza Potenza 35 Potenza Potenza 40 Potenza Potenza 42 Potenza Potenza Potenza frigorifera assorbita frigorifera assorbita frigorifera assorbita…
-
uscita acqua
evap. (°C) Standard ratings McPower SE 228.2 ÷ 395.3 LN, XN 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 Note: TEMPERATURA AMBIENTE - °C Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza…
-
uscita acqua
evap. (°C) Standard ratings McPower SE 418.3 ÷ 478.3 LN, XN 418.3 445.3 464.3 478.3 Note: TEMPERATURA AMBIENTE - °C Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza…
-
uscita acqua
evap. (°C) Standard ratings McPower SE 228.2 ÷ 340.3 XXN 228.2 255.2 276.2 300.2 320.2 340.3 TEMPERATURA AMBIENTE - °C Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza frigorifera Assorbita frigorifera Assorbita frigorifera Assorbita frigorifera Assorbita frigorifera…
-
uscita acqua
evap. (°C) Standard ratings McPower SE 374.3 ÷ 478.3 XXN 374.3 395.3 418.3 445.3 464.3 478.3 Note: Note: TEMPERATURA AMBIENTE - °C Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza frigorifera Assorbita frigorifera Assorbita frigorifera Assorbita frigorifera Assorbita…
-
276.2 300.2 320.2 340.3 374.3 395.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower XE 228.2 ÷ 374.3 ST, CN TEMPERATURA AMBIENTE - °C Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza frigor. assorb. frigor. assorb. frigor. assorb.…
-
464.3 478.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower XE 418.3 ÷ 478.3 ST, CN TEMPERATURA AMBIENTE - °C Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza frigor. assorb. frigor. assorb. frigor. assorb. frigor. assorb. frigor.…
-
276.2 300.2 320.2 340.3 374.3 395.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower XE 228.2 ÷ 395.3 LN, XN TEMPERATURA AMBIENTE - °C 25 Potenza 30 Potenza Potenza 35 Potenza Potenza 40 Potenza Potenza 42 Potenza Potenza Potenza frigorifera assorbita frigorifera assorbita…
-
464.3 478.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower XE 418.3 ÷ 478.3 LN, XN TEMPERATURA AMBIENTE - °C 25 Potenza 30 Potenza Potenza 35 Potenza Potenza 40 Potenza Potenza 42 Potenza Potenza Potenza frigorifera assorbita frigorifera assorbita frigorifera assorbita…
-
uscita acqua
evap. (°C) Standard ratings McPower XE 228.2 ÷ 395.3 XXN 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 Note: TEMPERATURA AMBIENTE - °C Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera…
-
464.3 478.3 Note: Temperatura uscita acqua evap. (°C) Standard ratings McPower XE 418.3 ÷ 478.3 XXN TEMPERATURA AMBIENTE - °C Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW) Potenza assorbita (kW) Potenza frigorifera (kW)…
-
Evaporator Pressure Drop – McPower 228.2 ÷ 478.3
508 B – 04/01 A – pag.40/52
-
Water Pump Diagram
-
Partial Heat Recovery Ratings McPower 228.2÷478.3
LEAVING DESUPERHEATERS WATER TEMPERATURE – °C 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 418.3 445.3 464.3 478.3 Leaving chilled water temperature 7°C ∆T 5°C – Air temperature 35 °C A4LS Unit Size Heating capacity (kW) Heating capacity (kW) Heating capacity (kW) Partial Heat Recovery Exchanger…
-
A4LS
Temperatura uscita acqua evap. (°C) Total Heat Recovery Ratings – McPower 228.2÷395.3 228.2 255.2 276.2 300.2 320.2 340.3 374.3 395.3 Heat recovery leaving water temperature - °C Total Heat Total Heat Total Heat Total Heat Recovery duty Recovery duty Recovery duty Recovery duty [kW] [kW] [kW] [kW]…
-
A4LS
418.3 445.3 464.3 478.3 Temperatura uscita acqua evap. (°C) Total Heat Recovery Ratings – McPower 418.3÷478.3 Heat recovery leaving water temperature - °C 40 Total Heat Recovery duty [kW] 1864,2 1910,5 1957,3 2004,8 2053 2101,8 1987,6 2037,2 2087,5 2138,5 2190,1 2242,5 2079,4 2131 2183,3 2236,2…
-
Total Heat Recovery Exchanger Pressure Drop – McPower 228.2÷478.3
508 B – 04/01 A – pag. 45/52
-
Dimensions
-
Technical Specification Air Cooled Screw Chiller – McPower 228.2÷478.3
To supply and install, where specified in the project n° unit(s) air cooled water chiller with cooling capacity of kW, to cool l/sec. of water from °C to °C working with °C ambient temperature. The unit should work with electricity at V, 3ph, 50Hz. The electrical power absorbed should not exceed kW.…
-
Refrigerant system differential pressure shall provide oil flow throught service replaceble, 0.5 micron, full flow, cartridge type oil filter internal to compressor. Filter bypass or oil pump not acceptable. The compressor’s oil cooling must be realized by liquid injection. External dedicated heat…
-
Refrigerant circuit
The unit must have refrigerant circuits completely independent of each other with one compressor per circuit. Each circuit shall include an: electronic expansion valve, compressor discharge shut-off valve, a liquid line shut-off valve with charging connection, replaceable core filter-drier, sight…
-
Display Capabilities
The controller as a minimum shall be capable of monitoring and displaying the following data: Analogue Inputs (AI) Entering Evaporator fluid Temp. Leaving Evaporator fluid Temp. Outside Air Temp. Not Used Discharge Press., one per comp. Discharge Press., one per comp. Setpoint Override (Setpoint…
-
NOISE REDUCTION SOLUTIONS
The unit compressors shall be mounted on a metal baseframe which shall be connected with unit’s metal baseframe by rubber antivibration supports to prevent the transmission of vibrations to all metal unit structure and so to control the unit noise. (for all Noise Versions) The discharge compressor…
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay Italia S.P.A. S.S. Nettunense, km 12+300 – 00040 Cecchina (Roma) Italia – Tel. (06) 937311 – Fax (06) 9374014 508 B – 04/01 A – pag.52/52