INSTALLATION MANUAL
-
CONTENTS
- Safety Precautions - Installation Diagram - Outline And Dimensions - Installation of Indoor Unit - Installation Of Outdoor Unit - Refrigerant Piping Work - Electrical Wiring Connection - Vacuuming and Charging - Accessory Parts - Indicator Lights - Overall Checking - Standard Operation Conditions…
-
INSTALLATION DIAGRAM
English Wireless Remote Control Drain Hose INDOOR UNIT Air Discharge Louver IR Receiver LED Light Front Panel Air Intake Grille Air Filter (behind the grille) Air Discharge Louver Remote Control Refrigerant Piping Air Intake Air Intake OUTDOOR UNIT Air Discharge Wired Remote Control Drain Hose Air…
-
OUTLINE AND DIMENSIONS
-
141.5 English 746.5 141.5 20.0 Outdoor Unit : SL30C / 40C / 50C & CR 40.0 400.0 320.0 40.0 850.0 20.0 1030.0 25.0 50.0 85.0 All dimensions are in mm. ! Caution Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places.…
-
Unit Installation
890.0 mm (Ceiling board opening) • Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging rod. • The installation template is extended according to temperature and humidity. Check on dimensions in use. • The dimensions of the…
-
Drain pipe must be in downward gradient for smooth drainage. • Avoid installing the drain pipe in up and down slope to prevent reversed water flow. Indoor Unit • During the drain pipe connection, be careful not to exert extra force on the drain connector at indoor unit. Pipe Clamp • The outside…
-
Control Box
LED Wire From Front Panel Air Swing Wire NOTE Install the front frame panel firmly to prevent cool air leakage which will cause condensation and water dripping. Indoor Unit Cool Air Cool Air Air Leak Air Leak Ceiling Board Ceiling Board Panel Panel Bad Installation Good Installation Air intake…
-
INSTALLATION OF OUTDOOR UNIT
• A place protected from rain, direct sunlight and well-ventilated wherever practicable. • A place capable of bearing the weight of the outdoor unit and isolating noise and vibration. • A place where there are no obstruction of air flow into or out the unit. • Do not put any object which may become…
-
Piping Connection
• Do not use contaminated or damaged copper tubing. If any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, then vacuum and purge with field supplied refrigerant. Generally, do not remove plastic, rubber plugs and brass nuts from the valves, fittings…
-
Interconnection Cable
COMP COMP L Indoor Unit Terminal Block N N Outdoor Unit Terminal Block N Power Supply Cable ! CK20A / 25A / 30A <> SL20B / 30B There must be a double pole switch with minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. CK30A / CK40A & CK50A MODEL INDOOR…
-
Heat Pump
CK20AR / CK25AR MODEL INDOOR OUTDOOR CK20AR CK25AR SL20BRK SL25BRK 220 - 240V / 1ph / 50Hz + 2225 / 1940 2937 / 2435 11.48 / 10.35 14.0 / 12.40 2.5 2.5 3 3 2.5 2.5 5 5 VOLTAGE RANGE POWER INPUT (cooling/heating), W RATED CURRENT (cooling/heating), A POWER SUPPLY CABLE SIZE (mm2) NUMBER OF CONDUCTORS…
-
English Outdoor Coil Sensor A 4WV OF Outdoor Unit Terminal COMP L A 4WV Indoor Unit Terminal Block N Interconnection Cable OF R COMP S L T N N Power Supply Cable ! There must be a double pole switch with minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation…
-
Possible Opening Dimension For Duct Connection
PCD fl140 fl100 Air Intake Knock Out Hole Air Discharge Knock Out Hole NOTE • Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator freezing. • In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no…
-
• Ensure that :1) The unit has been mounted solidly and rigid in position
2) Piping and connections are leak proof after charging. 3) Proper wiring has been installed. • Drainage check - pour some water into the main drain pipe from the flexible drain hose. • Test run 1) Conduct a test run after water drainage test and gas leakage test. 2) Check the following items :a. Is…
-
SERVICE AND MAINTENANCE
SERVICE PARTS Indoor air filter Indoor unit MAINTENANCE PROCEDURES PERIOD 1. Remove any dust adhered on the filter by using a vacuum cleaner or wash in lukewarm water (below 40oC) with neutral cleaning detergent. At least once every 2 weeks. 2. Rinse well and dry the filter before placing it back…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.