Инструкции на Пассивные климатические балки Lindab серии Carat
Пассивные климатические балки Lindab серии Carat для охлаждения. Инструкция по эксплуатации.
Смотрите также: Инструкция по монтажу →
Загружаем документ…
Текст инструкции
-
Service & maintenance
-
1.0 Installation
1.1 Product description Lindab’s chilled beam Carat is placed above a perforated suspended ceiling and supplies cooling, with a low air velocity, to the room below. Carat has a high radiation quotient of approx. 35% (compared to approx. 5% for traditional finned products). This gives great freedom…
-
1.4.1 Push-on fittings
Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a pressure test after assembly of the pipe work. Both flow and return pipe is covered by a plastic or rubber protection cover, which…
-
Push-on valve
Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. 1.4.2 Compression fitting Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a…
-
–– The copper insert should be placed inside the pipe on the beam. Always support
the copper pipe coil when inserting the copper insert into position. Mount a compression coupling and/or a valve to the pipe. Don’t stress the nut too much, since this may crush the pipe. Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes.…
-
After removing the protection cover, make sure that the pipe is intact and undamaged, especially at the pipe end. Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburring tool before installation Mount a push-on fitting to…
-
2.0 Commissioning
2.1 Product labeling Fig.1: Label location exterior (Above water connection) On the label you’ll find: Order: Order identification number. Pos: Order position. Product: Product configuration. Project: Project name. Mark: Marking noted on order. Nozzles: Number of nozzles. Plugs: Number of plugged…
-
3.0 Maintenance
The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the Carat beams only need cleaning every 5 years. 3.1 Cleaning instructions Only use lukewarm water and a mild detergent. 8 We reserve the right to make changes
-
4.0 Product and system specification
4.1 Material data Carat 31 Carat 44 Carat 58 Carat 71 Carat 84 Weight, kg/m 1.7 2.5 3.3 4.2 5.0 Water content, l/m 0.4 0.5 0.7 0.9 1.06 Copper pipes, EN 12735-2 EN 12735-2 EN 12735-2 EN 12735-2 EN 12735-2 quality CU-DHP CU-DHP CU-DHP CU-DHP CU-DHP Pressure class PN10 PN10 PN10 PN10 PN10 4.2…
-
The water velocities should not exceed 1m/s, and should be kept as close to the nominal flow as possible to minimize noise and optimize the energy yield There should be used in-line strainers to remove dirt particles from the water. If the water contains any additive inhibitor this must be…
-
Support
Hjælp Hjälp Tuotetuki Unterstützung Supporto UK - Here you can find product updates/mounting instructions and support telephone number/mail. www.lindab.com Right to alterations reserved. DK - Her kan du finde seneste produkt opdateringer/montagevejledninger samt support tlf. nr/mail. www.lindab.dk…