Инструкция на Микропроцессорный контроллер Lindab серии Regula Combi
Микропроцессорный контроллер Lindab серии Regula Combi для регулирования воздушных и водяных климатических систем помещений. Технический каталог.
Смотрите также: Инструкция по монтажу →
Загружаем документ…
Текст инструкции
-
Regula
Contact, Overview, Index 1 Guideline heating and cooling 2 Plexus 3 Professor / Professor Plus 4 Premum / Premax 5 Architect 6 Polaris I & S 7 Plafond 8 Podium 9 Celo 10 Cabinett 11 Capella 12 Carat 13 Fasadium 14 Atrium / Loggia 15 Regula 16 Drypac™ 17 Lighting 18 TEKNOsim 19 © 03.2014 Lindab…
-
Regula
Overview 1 Use Customized control equipment for water and airborne climate systems with individual regulation. 2 Regula Duo controls heating and cooling in sequence. 3 Regula Combi can control heating and cooling in sequence, VAV in combination with heating and cooling, Change-Over systems, as well…
-
Regula Duo Function Regula Duo is used for room individual temperature control, where the desired temperature can be adjusted easily within ±4°C using the control knob. The standard setting is 21°C. The set point for the desired value can be adjusted with a potentiometer between 15 and 25°C. Regula…
-
Regula
be activated by pressing the Occupancy button once (for less than 5 seconds). Program descriptions 1. Water The regulation of temperature takes place in sequences with heating, cooling and forced (cooling) ventilation by signals from the universal outputs UO1 (heating), UO2 (cooling) and UO3 (forced…
-
Control equipment Regula The basic airflow is set to 20% (default), so the cooling sequence will result in signals from 20-100%. By pressing the Occupancy button for more than 5 seconds operating mode Off will occur, that will change the UO2 signal to 0% regardless of cooling or heating demands.…
-
Regula
The universal outputs for UO1 and UO2 is default set to thermal on/off actuators. UO3 is default set to 0-10V. Heating and cooling actuators (UO1 and UO2) are exercised every 23 h. Sequences for temperature, CO2 and occupancy functions are as Program 1 Water. Universal outputs for UO1 and UO3 is…
-
In program 6 the modes Off, Standby, Occupied and Bypass are used. Off can be reached by pressing the occupancy button for more than 5 sec. This will close the volume flow regulator damper. By connecting a presence detector to Regula Combi, Standby will occur if there is no occupancy in the room.…
-
Regula
Display handling and indications Parameter menu Regula Combi has an Occupancy button, as well as an INCREASE button and a DECREASE button to increase and decrease the set point. It is possible to set different parameter values in the parameter menu. The parameter menu is accessed by simultaneously…
-
Regula Parameter number Description Default 0 Regula Combi Programs: 0=Regin Regio Midi RC-CDOC, 1=Water, 2=VAV, 3=eHybrid, 4=Change Over digital, 5=Change Over sensor, 6=Pascal VAV supply, 7=Pascal VAV exhaust 1 1 Basic heating setpoint 21ºC 2 Basic cooling setpoint 22ºC 3 Neutral zone at Stand-by…
-
Regula
All the Regio Midi parameters (with Regin defaults) can be accessed by selecting the value 0 at parameter 0. press the button for less than 5 seconds when the controller is in Bypass mode, it changes operating mode to the Preset operating mode (default: standby/occupancy). Furthermore all parameters…
-
Regula
Electrical wiring diagrams 1 Regula Combi G Supply voltage 24 V AC 11 G0 Supply voltage 0 V 12-14 No function. GDO 24 V AC out common for DO. Internally connected to terminal 10, G. 21 G0 0 V common for UO. Internally connected to terminal 11, G0. 22 UO3 Control output forcing (cooling). For a 0…10…
-
Regula Technical data Model Regula Duo Regula Combi Supply voltage 24 V AC ±15% 18…30 V AC, 50…60 Hz Communication N/A RS485, EXOline or Modbus. 8 data bits, even parity, 1 or 2 stop bit. 9600 bps. Outputs 2 3 UO (either AO or pulsating DO) heating, cooling and forcing (cooling) Inputs 1 temperature…
-
Regula Secura
Security against condensation Lindab has developed a condensation guard for both chilled beams and facade systems. The condensation guard is called Regula Secura. Since the control exercised by Regula Secura is based on actual condensation, a greater effect is obtained than with conventional…
-
Regula Regula Connect Basic REGULA CONNECT BASIC Regula Connect Basic is a connection card that provides flexible connection for chilled beams or façade systems. Regula Connect Basic consists of a connection card with connectors for mains cables, thermostat cables and terminal blocks for actuator…
-
Regula
1 REGULA CONNECT BASIC REGULA CONNECT BASIC N = Neutral L = Load S = Signal Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link_S Cooling link_S Supply link - N Supply link - L Bro Yel 2 N = Neutral L = Load S = Signal Heating out…
-
Lindab's standard actuators are of the type 24V NC (normally closed). Max. temperature: 2…95 °C at 6 bar Kvs value: 0.05-1.2 Static pressure class: PN10 Max. differential pressure: 60 kPa Material:Brass Recommended pressure drop over valve: 8-10 kPa Supply voltage: 24V AC/DC Power consumption: 75 m…
-
Regula
TTR-12 KPa mBar mmWS 1 10² 10³ 10² 10³ 10² 0.050 2 0.100 3 0.170 4 0.250 5 0.350 4 6 0.470 3 7 0.660 8 0.820 9 0.900 10 1.000 2 1 KVs m³/h 5 6 0.1 POSITIONS 10 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.6 0.8 Q m³/h Diagram 7. Valve settings for thermal actuators TTR-12. We reserve the right to…
-
mmWS
mBar 2 TTV-10-12, TTV-12 KPa 1 Regula 10² 10³ 10² 10³ 10² 0.100 3 0.170 0.250 0.350 4 6 0.470 3 7 0.660 8 0.820 9 1.050 10 1.200 10 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.6 0.8 Q m³/h Diagram 8. Valve settings for thermal actuators TTV-10-12 and TTV-12. 0.050 5 13 0.1 KVs m³/h POSITIONS We…
-
Other accessories
CO2 sensor Supply voltage: Power consumption: Protection class: CO2: Temperature: Outputs CO2: Temperature: Regula Presence sensor IR24-P CO2 RT 24 V AC +/- 15 % 3W IP30 0…2,000 ppm 0…50° C Supply voltage: Power consumption: Monitoring area: Installation height: Detectable movement: 24 V AC +/- 2 V…