Инструкции на Микропроцессорный контроллер Lindab серии Regula Combi
Микропроцессорный контроллер Lindab серии Regula Combi для регулирования воздушных и водяных климатических систем помещений. Инструкция по монтажу.
Смотрите также: Технический каталог →
Загружаем документ…
Текст инструкции
-
Mounting
1. Demount the face plate. 2. Remove the front including the circuit board 3. Mount the bottom plate on electrical box or directly on the wall 4. R emount in inverse arrangement when the plinths are connected. Notice that the front and bottom plate only can be fitted to each other in one way. See…
-
Electrical wiring diagrams
10 G Supply voltage 24 V AC 11 G0 Supply voltage 0 V 12-14 No function. 20 GDO 24 V AC out common for DO. Internally connected to terminal 10, G. 21 G0 0 V common for UO. Internally connected to terminal 11, G0. 22 UO3 Control output forcing (cooling). For a 0...10 V DC actuator, max 5 mA. The…
-
Parameter list
Parameter number Description Default 0 Regula Combi Programs: 0=Regin Regio Midi RC-CDOC, 1=Water, 2=VAV, 3=eHybrid, 4=Change Over digital, 5=Change Over sensor, 6=Pascal VAV supply, 7=Pascal VAV exhaust 1 1 Basic heating setpoint 21ºC 2 Basic cooling setpoint 22ºC 3 Neutral zone at Stand-by…
-
Program descriptions
be activated by pressing the Occupancy button once (for less than 5 seconds). 1. Water The regulation of temperature takes place in sequences with heating, cooling and forced (cooling) ventilation by signals from the universal outputs UO1 (heating), UO2 (cooling) and UO3 (forced cooling…
-
The universal outputs for UO1, UO2 and UO3 are default
set to 0-10V. The basic airflow is set to 20% (default), so the cooling sequence will result in signals from 20-100%. By pressing the Occupancy button for more than 5 seconds operating mode Off will occur, that will change the UO2 signal to 0% regardless of cooling or heating demands. This match…
-
4. Change Over digital
Change-over is a function, which makes it possible to use the same pipe/duct for both heating and cooling, depending on requirements during for example summer (cooling output) and winter (heating output). When using the digital signal input DI2 (potential-free contact), closing the contact switches…
-
Circuit diagrams
Display handling and indications The maximum number of actuators that can be connected to the digital output (ON/OFF) is 10 for cooling and heating, respectively. When more than 4 actuators for cooling or heating are connected, terminal blocks 10 and 20 must be connected with a cable. Regula Combi…