Corp. 9709−L5 Revised 5−2000 Service Literature HP29 SERIES UNITS The HP29 is a residential split-system heat pump. Outdoor coil size, circuiting and air volume result in a minimum SEER rating of 10.0. All HP29 units are designed for use with thermal expansion valves. Some HP29 units (−211 through…
-
SPECIFICATIONS
-
ELECTRICAL DATA
Model No. Line voltage data 60 hz HP29-018 HP29-024 HP29-030 208/230v 1ph 208/230v 1ph 208/230v 1ph 208/230v 1ph 208/230v 3ph 460v 3ph 7.9 10.1 14.7 16.0 11.0 5.6 Rated load amps Compressor HP29-036 Power factor .97 .96 .90 .91 .83 .83 Locked rotor amps 49.0 60.0 84.0 100 75.0 37.5 Full load amps…
-
1 − Transformer T5
2 − Dual Capacitor C12 Transformer T5 is used on all J" voltage units. T5 is used as a step-down transformer for the outdoor fan motor. The transformer is located inside the unit control box (see figure 3). The transformer is rated at 3.4 VA with a 575 volt primary and a 460 volt secondary. The…
-
3 − Potential Relay K31 (Start)
All single-phase units with a reciprocating compressor, use a potential relay which controls the operation of the starting circuit. The potential relay is located inside the unit control box (see figure 4). The relay is normally closed when contactor K1 is de-energized. When K1 energizes, the…
-
NOTE − COMPONENT LOCATIONS WILL VARY WITH BOARD MANUFACTURER
PRESSURE SWITCH SAFETY CIRCUIT CONNECTIONS PRESSURE SWITCH SAFETY CIRCUIT CONNECTIONS CONNECTION FOR ONE OPTIONAL SWITCH High Pressure Switch DIAGNOSTIC LEDs FACTORY−INSTALLED JUMPER (Remove to add pressure switches) FACTORY−INSTALLED JUMPER (Remove to add pressure switches) DEFROST INTERVAL TIMING…
-
Defrost Control Timing Pins
9 − Defrost System Units built April 2002 and later The HP29 defrost system includes two components: a defrost thermostat and a defrost control. Defrost Thermostat The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When defrost thermostat…
-
Pressure Switch Circuit
Time−Delay Relay The defrost control incorporates a pressure switch circuit that allows the application of an optional high pressure switch. See figure 7. During a demand cycle, the defrost control will lock out the unit if the optional high pressure switch opens. The diagnostic LEDs will display a…
-
B − Compressor (Reciprocating & Scroll)
DANGER Make sure all power is disconnected before beginning electrical service procedures. Some HP29 units utilize a conventional reciprocating compressor. Table 6 shows the specifications of reciprocating compressors used in HP29 series units. TABLE 6 HP29 COMPRESSOR SPECIFICATIONS MAN/MODEL…
-
1 − Compressor Cover (Figure 9)
A compressor cover constructed of vinyl-faced fiberglass is used on all HP29 units. The cover provides an acoustic barrier. The cover slides over the compressor and is held secure with snap buttons. Slits are provided for installation around the discharge and suction lines. CONDENSER FAN MOTOR AND…
-
LIQUID LINE SERVICE VALVE (VALVE OPEN)
IMPORTANT INSERT HEX WRENCH HERE Service valves are closed to the heat pump unit and open to line set connections. Do not open until refrigerant lines have been leak tested and evacuated. All precautions should be exercised to keep the system free from dirt, moisture and air. STEM CAP SERVICE PORT…
-
VAPOR LINE SERVICE VALVE (VALVE OPEN)
INSERT HEX WRENCH HERE VAPOR LINE (BALL TYPE) SERVICE VALVE (VALVE OPEN) STEM CAP INLET (TO INDOOR COIL) USE ADJUSTABLE WRENCH ROTATE STEM CLOCKWISE 90_ TO CLOSE ROTATE STEM COUNTER-CLOCKWISE 90_ TO OPEN SCHRADER VALVE OUTLET (TO COMPRESSOR) OUTLET (TO COMPRESSOR) SERVICE PORT CAP STEM CAP STEM BALL…
-
B − Plumbing
See figure 15 for unit refrigerant components. Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections). Use Lennox L10 (flare) or L15 (sweat, non−flare) series line sets as shown in table 9 or use field−fabricated refrigerant lines. TABLE 9 Length of…
-
IV − CHARGING
C − Evacuating the System Unit charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.5 m) line set. For varying lengths of line set, refer to table 10. TABLE 10 Liquid Line Set Diameter Ounce per 5 foot (ml per mm) adjust from 15 ft. (4.5 m)* 5/16 in. (8mm) 3/8 in. (10 mm) 2…
-
TABLE 12
IMPORTANT The following procedures require accurate readings of ambient (outdoor) temperature, liquid temperature and liquid pressure for proper charging. Use a thermometer with accuracy of +2°F( + 1.1°C) and a pressure gauge with accuracy of +5PSIG ( + 34.5kPa) 1 − Expansion Valve Systems The…
-
TABLE 13
SUBCOOLING METHOD AMBIENT TEMPERATURE BELOW 60 _F (16 _C) Model Condensing Temp°F Warmer Than Liquid Line TABLE 14 SUBCOOLING METHOD AMBIENT TEMPERATURE BELOW 60 _F (16 _C) Model Condensing Temp°F Warmer Than Liquid Line 8°F (4.4°C) 6°F (3.3°C) 10°F (5.6°C) 8°F (4.4°C) 12°F (6.7°C) 13°F (7.2°C) 5°F…
-
VI − REFRIGERANT LINE NOISE
It is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall,ceiling or floor) causes some objectionable noise when vibration is translated into sound. The following illustrations demonstrates procedures which ensure proper…
-
REFRIGERANT LINE SETS
HOW TO INSTALL HORIZONTAL RUNS To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties. Wire Tie (around vapor line only) 8 feet Floor Joist or Roof Rafter Tape or Wire Tie 8 feet Strapping Material (around vapor line only) Metal Sleeve Tape or…
-
VII − WIRING DIAGRAMS AND SEQUENCE OF OPERATION
HP29 SINGLE-PHASE WITH RECIPROCATING COMPRESSOR HP29−1 / −2 UNITS Page
-
HP29 SINGLE-PHASE WITH RECIPROCATING
COMPRESSOR Page
-
HP29 SINGLE-PHASE WITH RECIPROCATING
COMPRESSOR Page
-
HP29 SINGLE−PHASE WITH SCROLL COMPRESSOR
HP29−1 / −2 UNITS Page
-
HP29 SINGLE−PHASE WITH SCROLL
COMPRESSOR Page
-
HP29 SINGLE−PHASE WITH SCROLL
COMPRESSOR Page
-
HP29 SINGLE-PHASE OPERATING SEQUENCE
a−HP29 P Voltage Operation Sequence This is the sequence of operation for HP29 P" voltage units. This sequence applies to HP29 models equipped with either a reciprocating, or scroll compressor. The sequence is outlined by numbered steps which correspond to circled numbers on the adjacent diagram.…
-
HP29 THREE−PHASE WITH RECIPROCATING
OR SCROLL COMPRESSOR HP29−1/−2 NOTE−Scroll three−phase compressors must be phased correctly. Compressor noise may be significantly higher indicating phasing is incorrect. Compressor operating backwards will not provide cooling. Continued backard operation will cause compressor to cylce on internal…
-
HP29 THREE−PHASE WITH RECIPROCATING
OR SCROLL COMPRESSOR Page
-
HP29 THREE-PHASE OPERATING SEQUENCE
a−HP29 Y", G", and J" Voltage Operation Sequence This is the sequence of operation for HP29 Y" voltage. HP29 G" and J" voltage units are similar, but have a few additions. The G" voltage units have an outdoor fan relay, while the J" voltage units have the outdoor fan relay plus an outdoor fan…