Тепловые насосы Lennox серии HP 29 7,5 / 10 (26.4-35.2 kW). Инструкция по сервисному обслуживанию.
Смотрите также: Технические данные →
Загружаем документ…
Текст инструкции
-
HP29
Corp. 0101−L1 Revised 06−2003 Service Literature Heat Pumps−7.5 &10 Ton (26.4 & 35.2 kw) Litho U.S.A. HP29 HEAT PUMP SERIES The HP29 7.5 and 10 (26.4 and 35.2 kW) ton heat pump units are designated for light commercial applications, with a remotely located blower−coil unit or a furnace with an…
-
SPECIFICATIONS
Model No. HP29−090−2 HP29−120−2 7.5 (26.4) 10 (35.2) Nominal Size − Tons (kW) Liquid line (o.d.) in. (mm) connection (sweat) 5/8 (15.9) Vapor line (o.d.) in. (mm) connection (sweat) Outdoor Coil Net face area sq. ft. (m2) 1−3/8 (34.9) Outer coil 21.80 (2.03) Inner coil 20.94 (1.95) Tube diameter in.…
-
ELECTRICAL DATA
Model No. HP29−090−2 Line voltage data 60 hz − 3 phase HP29−120−2 208/230v 460v 575v 208/230v 460v 575v Rec. max. fuse or circuit breaker size (amps) {Minimum circuit ampacity Rated load amps 28.8 14.7 10.8 37.8 17.2 12.4 Locked rotor amps Full load amps (total) 3 1.5 1.2 2.4 (4.8) 1.3 (2.6) 1 (2)…
-
HP29−090−3 MODEL PARTS ARRANGEMENT
fan guard control box outdoor fan (B4) vapor line service valve reversing valve defrost thermostat (S6) discharge line thermostat (S5) high pressure switch (S4) compressor (B1) defrost pressure switch (S46) loss of charge switch (S24) liquid line service valve low ambient switch (S11) FIGURE 1…
-
HP29−090−3 CONTROL BOX
transfer relay K8 low ambient kit relay K58 outdoor fan relay K10 defrost relay K4 CMCI defrost/timer R latch relay K6 G G1 ground lug capacitor C1 terminal strip TB 14 compressor contactor K1 W1 W2 Y1 C FIGURE 3 HP29−120−3 CONTROL BOX relay switch K6 terminal strip TB 14 cmc1 defrost / timer…
-
I−UNIT COMPONENTS
A latch relay (figure 5 ) has two coils: a SET" coil and a The HP29−090 and HP29−120 components are shown in figures 1 and 2. RESET" coil. When 24VAC is applied to the SET" coil, the A−CONTROL BOX COMPONENTS The HP29−090 control box components are shown in fig ure 3. The HP29−120P control box…
-
6 − Transfer Relay K8 (all units)
B−COOLING COMPONENTS Transfer relay K8 ensures that the indoor blower will oper ate during all modes of operation. K8 also completes the circuit to Y1 on the defrost control board CMC1. The com bined operation of latch relay K6 and transfer relay K8 al lows the HP29 unit to use a conventional…
-
SUCTION
SUCTION INTERMEDIATE PRESSURE GAS 2 1 CRECENT SHAPED ORBITING SCROLL GAS POCKET STATIONARY SCROLL SUCTION FLANKS SEALED POCKET BY CENTRIFIGUAL FORCE SUCTION SUCTION MOVEMENT OF ORBIT 3 4 HIGH PRESURE GAS DISCHARGE POCKET FIGURE 8 The counterclockwise orbiting scroll draws gas into the 2 − Crankcase…
-
5 − Discharge Line Thermostat S5
C−Defrost System S5 is an automatic reset SPST N.C. switch which opens on a temperature rise. The switch is located on the discharge line and wired in series with the CMCI board and S4 pres sure switch. When discharge line temperature rises to 275° + 5°F the switch opens and the compressor is de−en…
-
Defrost Control CMC1
The defrost control board combines functions of a time / temperature initiated and time / pressure terminated defrost control, defrost relay, time delay, diagnostic LEDs and field connection terminal strip. See figure 10. The control provides automatic switching from normal heating operation to…
-
DEFROST CONTROL BOARD HP29−2 UNITS
COMPRESSOR CONNECTIONS DIAGNOSTIC LEDs LED 2 DEFROST INTERVAL TIMING PINS PRESSURE SWITCH SAFETY CIRCUIT CONNECTIONS AMBIENT THERMISTOR CONNECTION 24V TERMINAL STRIP CONNECTIONS SERVICE LIGHT CONNECTION DEFROST SWITCH CONNECTIONS REVERSING VALVE NOTE− There is an internal jumper between inside PS1…
-
COOLING MODE
REVERSING VALVE LOW PRESSURE HIGH PRESSURE COMPRESSOR ACCUMULATOR EXPANSION VALVE BI−FLOW DRIER CHECK VALVE INDOOR COIL TO REFRIGERANT DRUM OUTDOOR COIL NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW VAPOR LINE SERVICE LIQUID LINE VALVE SERVICE VALVE EXPANSION VALVE OUTDOOR UNIT INDOOR UNIT…
-
LIQUID LINE SERVICE VALVE (VALVE OPEN)
II− REFRIGERANT SYSTEM A−Plumbing INSERT HEX WRENCH HERE Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor evaporator coil (sweat connections). Refer to table 2 for field−fabricated refrigerant line sizes. Refer to Lennox Re frigerant…
-
DANGER
Do not attempt to backseat this valve past the retaining ring. Attempts to backseat this valve past the retaining ring will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result. VAPOR LINE SERVICE VALVE USE ADJUSTABLE WRENCH ROTATE…
-
Three−Phase Compressor Rotation
Threephase scroll compressors must be phased se quentially to ensure that the compressor rotates and operates correctly. When the compressor starts, a rise in discharge and drop in suction pressures indicate proper compressor phasing and operation. If dis charge and suction pressures do not perform…
-
TABLE 3
UNIT MODEL NUMBER MATCHED INDOOR UNIT HCFC22 FOR 25 FEET (7.6 m) OF LINE HP29 090 2 HP29−090−2 HP29−090−3 CB17/CBH17 95 CB17/CBH17−95 23 lbs. (10.4 kg) 21.5 lbs. (9.8 kg) HP29 120 2 HP29−120−2 HP29−120−3 CB17/CBH17 135 CB17/CBH17−135 31 lbs. (14.1 kg) 30 lbs. (13.6 kg) LIQUID LINE DIAMETER…
-
C−Charging
If the system is completely void of refrigerant, the recom mended and most accurate method of charging is to weigh the refrigerant into the unit according to table 3. If weighing facilities are not available or if unit is just low on charge, the following procedure applies. The following procedures…
-
TABLE 5
-
V−MAINTENANCE
At the beginning of each cooling season, the system should be checked as follows: WARNING Electric shock hazard. Can cause inju ry or death. Before attempting to per form any service or maintenance, turn the electrical power to unit OFF at dis connect switch(es). Unit may have multiple power…
-
VI−Wiring Diagram and Sequence of Operation
-
After each thermostat demand, time delay locks out the circuit to compressor contactor coil and defrost control for 5 + 2 minutes. At the end of the time period, the time delay allows the compressor contactor and defrost control to be energized upon demand. COOLING 1 − Cooling demand energizes…
-
After each thermostat demand, time delay locks out the circuit to compressor contactor coil and defrost control for 5 + 2 minutes. At the end of the time period, the time delay allows the compressor contactor and defrost control to be energized upon demand. COOLING 1 − Cooling demand energizes…
-
E− THERMOSTAT CONNECTIONS
Page 26
-
SERVICE NOTES
Page 27