Инструкции на Кондиционеры Lennox серии FLATAIR
Горизонтальные трансформируемые моноблочные кондиционеры Lennox серии FLATAIR FMC-H / FIC-H / FSC-H (R410A). Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Загружаем документ…
Текст инструкции
-
Installation, operating
and maintenance FLATAIR R410A FMC-H/ FIC-H/ FSC-H Providing indoor climate comfort MIL115E-1011 10-2011 Original manual translation
-
WARNING: Read this manual before installation, reparation o maintenance works
TABLE OF CONTENTS POINTS TO BEAR IN MIND PAGE 2 DATA PAGE FOR COMMISSIONING UNIT PAGE 3 1.- GENERAL CHARACTERISTICS PAGE 4 4-5 5 6 7-8 9-14 15 1.1.- PHYSICAL DATA 1.2.- ELECTRICAL DATA 1.3.- OPERATING LIMITS 1.4.- FAN PERFORMANCES 1.5.- PIPING DRAWINGS 1.6.- UNIT DIMENSIONS 1.7.- DUCT POSITION 2.…
-
POINTS TO BEAR IN MIND
DANGER AND WARNING SIGNS Abrasive surfaces Low temperatures High temperatures Risk of injury by moving objects Electrical voltage Risk of injury by rotating objects ELECTRICAL CONNECTIONS Make sure to switch off the power before installing, repairing or carrying out maintenance on the unit, in order…
-
DATA PAGE FOR UNIT COMMISSIONING
UNIT: SERIAL Nr: CONTROL PANEL IDENTIFICATION CODE: INSTALLATION ADDRESS: INSTALLER: INSTALLER TEL: INSTALLER ADDRESS: DATE OF COMMISSIONING: CHECKS: SUPPLY VOLTAGE: RATED VOLTAGE OF THE UNIT: YES NO UNIT ON SHOCK ABSORBERS DRAINAGE WITH TRAP MAIN POWER SUPPLY CONNECTION CONTROL PANEL CONNECTION…
-
1.1.- PHYSICAL DATA
F M C 015 S N C: Cooling only S: One Circuit H: Heat pump X: Cooling only / Heat pump M: Compact unit Approximate cooling S: Outdoor unit capacity in kW I: Indoor unit M Unit FLATAIR 1 M Type of refrigerant M: R-410A M: 400V/3/50 Number of revision FMC: Cooling only unit R-410A. FMH: Heat pump unit…
-
1.2 .- ELECTRICAL DATA
Electrical consumptions to add to the unit indoor and to the set 10 230V I 10 Standard 3 3 4,5 7,5 Medium Standard 13,0 7,5 11,3 18,8 Medium 26,1 15 15 22,5 High - 22,5 22,5 30 ELECTRICAL HEATER Maximum power (KW) High Maximum current (A) 1.3.- OPERANTING LIMITS OPERATING LIMITS (COOLING ONLY)…
-
1.4.- FAN PERFORMANCES
INDOOR UNITS Airflow (m3/h) Available static pressure (Pa) UNITS 2350 2300 3575 4850 5750 5500 10 2275 2250 3495 4785 5730 5455 20 2240 2200 3410 4715 5705 5405 30 2190 2150 3330 4645 5670 5350 40 2140 2100 3250 4575 5630 5285 50 2080 2040 3170 4500 5580 5220 60 2025 1975 3095 4425 5530 5140 70 1975…
-
COOLING ONLY UNITS 10-12-15
1.8.- PIPING DRAWINGS INDOOR UNIT OUTDOOR UNIT Fan motor Scroll compressor LP HP PT Fan CH IS Coil Coil Orifice OS OPTION ELEMENT HEAT PUMP UNITS 10-12-15 INDOOR UNIT OUTDOOR UNIT Fan motor LP Scroll compressor HP 4-way valve PT Fan IS Coil Coil Suction Acumulator Orifice Filter drier Orifice OS…
-
HEAT PUMP UNITS 20-25-30
1.8.- PIPING DRAWINGS OUTDOOR UNIT INDOOR UNIT Fan motor Scroll compressor LP HP PT Fan CH IS Coil Coil OS Expansion valve Filter drier (ELEMENTO OPCIONAL) OPTION ELEMENT HEAT PUMP UNITS 20-25-30 OUTDOOR UNIT INDOOR UNIT Fan motor Fan LP Scroll compressor HP 4-way valve PT Fan IS Coil Coil Suction…
-
FIX 10-12
FSC / FSH 10-12
-
FIX 15
FSC / FSH 15 10
-
FIC / FIH 20
FSC / FSH 20 11
-
FIC / FIH 25-30
FSC / FSH 25-30 12
-
FMC/FMH 10-12
FMC/FMH 15 13
-
FMC/FMH 20
FMC/FMH 25-30 14
-
1.5.- DUCT POSITION
-
2.1.- PRELIMINARY PREPARATIONS
All INSTALLATION, SERVICE and MAINTENANCE work must be carried out by QUALIFIED PERSONNEL. The unit must be transported in a HORIZONTAL POSITION on its metal mounting frame. Any other position may cause serious damage to the machine. When the unit is received, it should be checked to assure that it…
-
2.3.- OPTIONAL OPERATIONS PRIOR TO UNIT INSTALATION
20 Service panel 10-12-15 Supply panel Service panel with opening Supply panel with opening 25-30 Intake opening Supply panel Air filter panel Supply panel with opening with opening Service panel Supply panel with opening Intake opening Air filter panel Service panel Service panel Air filter panel…
-
2.4.- UNIT LOCATION
The bedplate is made up of three galvanized metal channels, capable of withstanding the weight of the units whether hung from the ceiling or mounted on the floor. If the unit is floor mounted, then the profiles should be isolated with shock absorbing material such as anti-vibration or pads. Keep in…
-
2.7.- REFRIGERANT CONNECTIONS
Split units are supplied with gas and liquid lines sealed with copper covers, and located 60mm from casing. Service ports Gas Cupper cover Terminal block Brazing Liquid Split units are supplied with nitrogen gas, this must be removed and then proceed as folow: 1. Remove the nitrogen gas through the…
-
2.7.- REFRIGERANT CONNECTIONS
To locate the outdoor and the indoor units, refer to the following information: OUTDOOR UNIT INDOOR UNIT A,B,C: Units positions L: Total length 1: Gas line 2: Liquid line OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT INDOOR UNIT POSITION A: A syphon suction must be installed on the vertical line of the gas…
-
2.7.- ELECTRICAL CONNECTIONS
- BEFORE MAKING ANY ELECTRICAL CONNECTIONS, ENSURE THAT ALL CIRCUIT BREAKERS ARE OPEN. - IN ORDER TO MAKE THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE UNIT. POWER SUPPLY POWER SUPPLY 230V SINGLE PHASE UNITS Nº DE CABLES X SECCIÓN (mm2) UNIDAD MODELO Alimentación sin…
-
3.- COMMISSIONING AND OPERATION
3.1.- PRELIMINARY CHECKS . Check that drain pipe connections and their fixtures are secure and that the level of the unit is tipped toward the drain. 2. Inspect the state of the ducts and grilles 8clean and open grilles, no breaks in the duct, etc.) 3. Check that the power supply is the same as…
-
3.- COMMISSIONING AND OPERATION
3.2.- PRELIMINARY CHECKS AT FIRST INSTALLATION The unit must be installed in accordance with local safety codes andregulations and can only be used in a well ventilated area. Please readcarefully the manufacturer’s instructions before starting this unit All work on the unit must be carried out by a…
-
4.1.- PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE PREVENTS COSTLY REPAIRS. THIS REQUIRES PERIODIC INSPECTIONS: - AIR FILTER : The air filter can be removed through the side by sliding it over the rail or downwards. (See figure). For downwards removal, remove the two profiles that support it (depending on the model) which are…
-
4.2.- CORRECTIVE MAINTENANCE
- Take very special care if 4-way or check valves are to be replaced since these have internal components that are very heat-sensitive such as plastic, teflon, etc. - If a compressor is to be replaced, disconnect it electrically and un-braze the suction and discharge lines. Remove the securing…
-
4.3.- FAILURE DIAGNOSIS
In case of failure or malfunction of the unit, the display on the control panel will show an error or alarm warning which is explained in the control panel manual. Nevertheless, whenever there is a unit fault, the unit should be shut down and our service technicians consulted. FAULT UNIT DOES NOT…
-
4.- MANTENANCE
4.4.- REGULACTION COOLING LP HP HEATING RESET SET SET RESET 3,5 4,5 1,7 2,7 outdoor fan speed regulation PT 34 defrost Tables values in bar g. 1.- OUTDOOR FAN SPEED REGULATION (Low ambient 0ºC or - 15ºC option) CMC,CMH LOW AMBIENT -15ºC OPTION LOW AMBIENT 0ºC OPTION FAN SPEED CFM (Fan speed) 100% ON…
-
www.lennoxeurope.com
BELGIUM, LUXEMBOURG www.lennoxbelgium.com PORTUGAL www.lennoxportugal.com Due to Lennox’s ongoing commitment to quality, the Specifications, Ratings and Dimensions are subject to change without notice and without incurring liability. CZECH REPUBLIC www.lennox.cz RUSSIA www.lennoxrussia.com Improper…