Инструкции на Чиллеры Lennox серии ECOLOGIC, ECOMAX, MCC, MCB
Чиллеры Lennox серии ECOLOGIC (WA - WAH - RA), ECOMAX (LCH - LCB), MCC, MCB. Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Загружаем документ…
Текст инструкции
-
INSTALLATION OPERATING &
MAINTENANCE MANUAL AIR COOLED CHILLERS English/01-2005
-
TABLE OF CONTENTS
AIR COOLED CHILLERS AND SPLIT UNITS INSTALLATION OPERATION MAINTENANCE MANUAL Ref : CHILLERS_IOM-0105-E The present manual applies to the following CHILLERs versions : ECOLOGIC range : WA - WAH - RA ECOMAX range : LCH - LCB MCC range MCB range Our company is a member of the Eurovent Certification…
-
Installation - Operation - Maintenance manual (IOM) • AIR COOLED CHILLERS & SPLIT UNITS - 0105-E
-
TABLE OF CONTENTS
1- PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 PED Declaration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2- WARRANTY . . . . . . . . . . . . . . .…
-
PREFACE
1 - PREFACE You must read and be familiar with this operating manual prior to commission the chiller. Please closely follow the instructions. We would like to stress the importance of training with respect to the correct handling of the chiller. Please consult Lennox on the options available in this…
-
PED DECLARATION
All Units are compliant with the PED directive 97-23-CE. The following note must be followed carefully IMPORTANT NOTICE All work on the unit must be carried out by a qualified and authorised employee. Non-compliance with the following instructions may result in injury or serious accidents. Work on…
-
WARRANTY
2 - WARRANTY The warranty of the chillers is subject to the warranty definitions as agreed upon in the order. It is expected that the design and installation of the unit utilises good working practices. The warranty will be legally null and void if : - Service and maintenance have not been executed…
-
3. INSTALLATION
3.1 - Transport - Handling 3.1.1 - Controls and delivery checks On receipt of a new equipment please check the following points. It is the customer’s responsibility to ensure that the products are in good working order (fill the check list page 48): - The exterior has not been damaged in any way.…
-
When units are delivered on site they are not always required immediately and are sometimes put into storage. In the event of medium to long-term storage, we recommend the following procedures : - Ensure that there is no water in the hydraulic systems. - Keep the heat exchanger covers in position.…
-
3.3 - LAY-OUT AND INSTALLATION REQUIREMENTS
The following preparations are important for the installation of the chiller : - Air-cooled chillers such as Ecologic or Ecomax are designed for outdoor installation. Please consult Lennox prior to implementing other types of installation. - Locate the chiller where it is least affected by wind…
-
CLEARANCES DRAWINGS
For more details, please consult our Application Guides or the drawings supplied with the unit. ECOLOGIC range ECOMAX range OVERHEAD OBSTRUCTIONS ARE NOT PERMITTED 1m 1,5 m 1,5 m 1,5 m 1m 1m > 3 meters 1m > 2 meters 1,5 m > 2 meters Not recommended Not allowed For any air cooled unit, it is…
-
3.4.3 - Antifreeze protection
3.4.3.1 : Use glycol/water solution ADDITION OF GLYCOL IS THE ONLY EFFICIENT WAY TO PROTECT AGAINST FREEZING The glycol/water solution must be sufficiently concentrated to ensure proper protection and prevent formation of ice at the lowest outdoor air temperatures expected on an installation. Take…
-
A main isolator switch must be inserted between the end of the power supply cable and the unit to enable total isolation of the latter when necessary. Chillers are supplied as standard without a main isolator switch. This is available as an option. WARNING Wiring must conform to applicable…
-
UNITS WITH REMOTE CONDENSER
Unit with remote condenser with capacity control Unit with remote condenser without capacity control 4 A A 2 2 H1 H1 H2 H2 H3 H3 H4 H1 : 15 m. maxi H4 1 - Lower trap with single tube 2 - Clode coupled trap H2 : 5 m. maxi H3 : 0,3 m. maxi H4 : 0,15 m. maxi 3 - Lower trap with double tubes 4 - Higher…
-
CONDENSING UNITS
Condensing unit with capacity control Condensing unit without capacity control Min 0,25% gradient 4 Min 0,25% gradient H1 2 H1 2 H2 H2 H4 H1 : 15 m. maxi H4 1 - Lower trap with single tube 2 - Clode coupled trap H2 : 5 m. maxi H4 : 0,15 m. maxi 3 - Lower trap with double tubes 4 - Higher trap with…
-
Minimum refrigeration capacity in kW for oil entrainments up Suction risers
Refrigerant : R407C Table C Tubing nominal OD, mm Saturated temperature (°C) Suction gas temperature (°C) 0,39 0,71 1,20 2,04 3,88 6,88 11,11 21,31 36,85 55,86 115,24 199,30 10 0,37 0,68 1,14 1,94 3,68 6,53 10,54 20,20 34,94 52,95 109,25 189,14 10 0,47 0,86 1,45 2,47 4,69 8,33 13,44 25,77 44,58…
-
15 °C, it is often necessary to leave the pump running for 10 to 20 hours. The duration of pump operation is not a factor of efficiency. The pressure level must be checked before the unit is put into service. 3.7.5 - Refrigerant charge Chillers with R407C must be filled in the liquid phase. Never…
-
3.7.7 - Air cooled condensers
An air cooled condenser connected to a unit must have the same number of circuits as the unit. Selection of the condenser must be made carefully to enable transfer of the heat capacity of the unit even at the highest temperatures expected on an installation. It is mandatory to control the head…
-
4 - PRELIMINARY CHECKS
Check that all drain and purge plugs are in place and well tightened prior to fill the installation with water. 4.1 - LIMITS Prior to any operation, please checks the operation limits of the unit given in the «ANNEXES» at the end of the IOM, page 55 to 62. These tables will give you all necessary…
-
tightened in the various wells, if necessary add heat conducting paste to improve contact. Make sure all sensors are correctly fitted and that all capillary tubes are fastened. The technical data printed at the top of the wiring diagram should correspond with those indicated on the unit nameplate.…
-
NOTE
An under-tensioned belt will slip, heat and wear prematurely. On the other hand, if a belt is overtensioned, the pressure on the bearings will cause them to over-heat and wear prematurely. Incorrect alignment will also cause the belts to wear prematurely. 9a) PULLEYS ALIGNMENT After adjusting one or…
-
AT 18-18 FAN CURVE
Installation - Operation - Maintenance manual (IOM) • AIR COOLED CHILLERS & SPLIT UNITS - 0105-E • 21 •
-
UNIT START-UP
5 - UNIT START-UP 5.1 - CHECKS TO BE MADE DURING START UP 5.1.1 CHECKS TO BE MADE DURING START UP Before starting the unit, fill in the check list sheet on page 48 of this manual and follow the instructions below to be sure that the unit is correctly installed and ready to operate. 1) Thermometers…
-
UNIT START-UP
These verifications can only be made once the proper operation of all safety devices and unit controls has been established. 5.2 - OIL CHARGE Units have a complete operating charge of oil when they are shipped, and there is no need to add any oil before start up or afterwards. Note that unit…
-
6 - OPERATION
6.1 - CLIMATIC CONTROL cf. See the specific CLIMATIC 50 manual cf. See the specific «Basic CLIMATIC controller» manual 6.1.1 - Menu Tree - ECOLOGIC range See «Annexes», page 70 to 78 6.1.2 - Menu Tree - ECOMAX range See «Annexes», page 79 to 90. 6.1.3 - Connection diagrams - CLIMATIC™ 30 A remote…
-
AWG24
DC 50 DC 50 DS 50 6.1.4 - Connection diagrams - CLIMATIC™ 50 Installation - Operation - Maintenance manual (IOM) • AIR COOLED CHILLERS & SPLIT UNITS - 0105-E • 25 •
-
6.2 - UNIT OPERATION
6.2.1 - Functions of refrigeration circuit components 6.2.1.1 - Thermostatic expansion valve: Very important: The thermostatic expansion valve fitted on each machine has been selected for a given operating range; it must be replaced with a model with the same reference from the same manufacturer.…
-
Note: On units fitted with CLIMATIC control, see the appropriate user manual for more specific details. 6.2.1.9 - Differential oil pressure safety switch : (only on units with semi-hermetic compressors) a) Reciprocating compressors: This pressure switch initiates unconditional unit stoppage if…
-
6.2.3 - Automatic sequences
6.2.3.1 - Starting sequence: - Press the unit start switch, the power light will come on ; The control circuit cannot be energised if there is no power supply to the main power circuit. - Depending on the demand for cooling, the control thermostat authorises start up of the compressor(s), which…
-
VENT1/C1
-
ECOMAX - Fans electrical box labelling
-
MAINTENANCE
7. MAINTENANCE The following maintenance instructions form a part of the operations required for this type of equipment. However, It is not possible to give fixed and precise rules for permanent maintenance procedures capable of keeping all units in perfect operating condition since too many factors…
-
MAINTENANCE
3) Clean any corroded surfaces and repaint them. 4) Inspect the chilled water circuit for any signs of leakage. Check operation of the water circulating pump and its ancillaries. Check the percentage of antifreeze in the chilled water circuit, top up as necessary (if antifreeze is used). 5) Carry…
-
8.1 LIST OF THE MOST COMMON PROBLEMS
PROBLEMS – SYMPTOMS A) PROBABLE CAUSE RECOMMENDED ACTION THE COMPRESSOR DOES NOT START - Motor control circuits established, the compressor does not run - No power supply - Check main power supply and switch positions - Compressor motor burnt out - Replace - Low voltage reading on voltmeter…
-
PROBLEMS – SYMPTOMS
PROBABLE CAUSE RECOMMENDED ACTION B) THE COMPRESSOR DOES NOT START - Normal operation with too frequent starts and stoppages due to action of the low pressure safety switch. Bubbles in sightglass.. - Low pressure safety switch trip out - Check low pressure safety switch differential - Low…
-
PROBLEMS – SYMPTOMS
PROBABLE CAUSE RECOMMENDED ACTION D) THE COMPRESSOR RUNS IN LONG CYCLES OR RUNS CONTINOUSLY - Faulty control thermostat - Check operation - Temperature too low in the conditioned space - Chilled water thermostat set too low - Adjust it - Bubbles in sightglass - Low refrigerant charge - Check the…
-
PROBLEMS – SYMPTOMS
PROBABLE CAUSE RECOMMENDED ACTION F) THE COMPRESSOR CUTS OUT ON ANTIFREEZE PRESSURE SWITCH - Antifreeze pressure switch tripped - Check that the pressure switch is operating properly - Low water flow in the evaporator - Check the water pump - Evaporator obstructed - Determine the degree of fouling…
-
PROBLEMS – SYMPTOMS
PROBABLE CAUSE RECOMMENDED ACTION - If starting on a single winding on compressors fitted with part winding start or wye-delta - Check operation of the starter contacts, the start up time delay and the condition of the windings - Compressor knocking - Broken mechanical parts inside compressor…
-
PROBLEMS – SYMPTOMS
PROBABLE CAUSE RECOMMENDED ACTION M) SUCTION PRESSURE IS TOO HIGH - The compressor runs continuously - Suction line unusually cold. - Too much cooling demand on the evaporator - Check the system a) Expansion valve opened to far a) Adjust superheat and check that the expansion valve bulb is correctly…
-
CONTROL DEVICES Operation By reacting to compressor discharge pressure, the high pressure switch monitors efficiency of the condenser. Poor efficiency, the result of an excessive condensing pressure, is usually caused by : - A dirty condenser - Low water flow - Low air flow The low pressure switch…
-
OPERATION AND START-UP CHECK SHEET Machine identifications : File number : Year of manufacture : NORMAL CONDITIONS OF USE Leaving chilled water temperature : °C Outdoor air temperature : Max : °C Power supply voltage : V/Ph/Hz Refrigerant type : Min : °C Date and time measurements were taken…
-
REGULAR CHECKS TO BE MADE - CHILLER UNIT ENVIRONMENT CHILLED WATER CIRCUIT VALUE Inlet / Outlet pressure guages for pressure drop . . . . . . . . . . . . . . . . . . . . . . . . . . DkPa Evaporator inlet temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .…
-
MANUFACTURER’S RECOMMENDED INSPECTIONS 8.5.1 - LIQUID CHILLERS WITH RECIPROCATING COMPRESSOR(S) 8.5.1.1 - Number of recommended preventive maintenance visits : NUMBER OF RECOMMENDED PREVENTIVE MAINTENANCE VISITS Year Start up 500/1000H visit Major technical inspection Inspection visit 15 000 h…
-
8.5.1.2 - Description of inspection duties - Liquid chiller with reciprocating compressor(s)
START UP - Check unit installation - Check water flow and water circuit ancillaries - Check safety devices - Check leaktightness - Configuration of the microprocessor based management system (if used) - Verification of operating parameters and unit performance - Transmission of the machine service…
-
8.5.2 - LIQUID CHILLERS WITH SCROLL COMPRESSOR(S)
8.5.2.1 - Number of recommended preventive maintenance visits : NUMBER OF RECOMMENDED PREVENTIVE MAINTENANCE VISITS Year Start up 500/1000H visit Major technical inspection Inspection visit Tube analysis (1) +10 Every year 3 times a year Every 3 years This table is published for units operating…
-
8.5.2.2 - Description of inspection duties - Liquid chiller with scroll compressor(s)
START UP - Check unit installation - Check water flow and water circuit ancillaries - Check safety devices - Check leaktightness - Configuration of the microprocessor based management system (if used) - Verification of operating parameters and unit performance - Transmission of the machine service…
-
8.5.3 - LIQUID CHILLERS WITH SCREW COMPRESSOR(S)
8.5.3.1 - Number of recommended preventive maintenance visits : NUMBER OF RECOMMENDED PREVENTIVE MAINTENANCE VISITS Year Start up 500/1000H visit Major technical inspection Inspection visit 30000 h inspection Tube analysis (1) 1 1 Every 30000 hours Every 3 years 3 +10 Every year 3 times a year This…
-
8.5.3.2 - Description of inspection duties - Liquid chiller with screw compressor(s)
START UP - Check unit installation - Check water flow and water circuit ancillaries - Check safety devices - Check leaktightness - Configuration of the microprocessor based management system - Verification of operating parameters and unit performance - Transmission of the machine service log 500 H /…
-
CHECK LIST
This check list should be filled in by the contractor to make sure that unit installation takes place according to appropriate industry practices. WARNING : Disconnect the power supply before carrying out any inspections on the unit. If the unit must be left powered up, proceed with precaution to…
-
ANNEXES
AIR COOLED CHILLERS AND SPLIT UNITS INSTALLATION OPERATION MAINTENANCE MANUAL Ref : CHILLERS_IOM-0105-E ANNEXES HYDRAULIC CIRCUIT DRAWINGS ECOLOGIC range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 ECOMAX range . . . .…
-
wa
UNIT WITHOUT HYDRAULIC OR HYDRONIC MODULE 150 std/ln 75/100/110 he/sln 04b 15a ˚C 16 04a D 17b 22 15b ˚C 17a 18 200 -> 370 std/ln/he/sln 90/130/150 HE/SLN wA 15a 16 04b ˚C 22 19 04a D 17b ˚C 15b 17a 18 19 ITEMS SUPPLIED LOOSE ITEMS MOUNTED INSIDE THE UNIT 01 19 Groove lock coupling 15a 15b…
-
UNIT WITH HYDRONIC MODULE
08 11b 07 04b 11a 13b °C 15a 14 04a Or 12 13a 09 16 °C 17b 15b 17a 18 19 ITEMS SUPPLIED LOOSE ITEMS MOUNTED INSIDE THE UNIT 01 19 Groove lock coupling 05 Paddle flow switch 11b Single 50L expansion vessel (WA <= 150D) 02 18 Unit isolation valve 06 Water tank 200L or 500L 12 Pump suction isolation…
-
UNIT WITH HYDRAULIC MODULE
11b °C 04b 11a 10 15a 14 04a 13b 17b °C Or 15b 18 17a 19 13a ITEMS SUPPLIED LOOSE ITEMS MOUNTED INSIDE THE UNIT 01 19 Groove lock coupling 05 Paddle flow switch 13a Single pump 02 18 Unit isolation valve 10 25L expansion vessel 13b Double pump 03 Water inlet filter 11a Second 25L expansion vessel…
-
ECOLOGIC - HYDRAULIC DRAWING
wa - ek - dk std/ln/he/sln UNIT WITH FREE COOLING OPTION WA 150 STD/LN 04b C 15a °C 16 04a D 02 B 22 15b B A 17b D °C 17a 18 19 WA 150 HE/SLN and 200/230/270/300/370 STD/LN/HE/SLN 15a 16 04b C °C B 04a D A A 17b B °C 15b 17a 18 D ITEMS SUPPLIED LOOSE ITEMS MOUNTED INSIDE THE UNIT 01 19 Groove lock…
-
ECOMAX - HYDRAULIC DRAWING
all units standard high ambient low noise 04b 07a °C D 04a 09b °C 12 07b 09a 10 11 ITEMS SUPPLIED LOOSE ITEMS MOUNTED INSIDE THE UNIT 01 19 Groove lock coupling 06 Heat exchanger 02 10 Unit isolation valve 07a 07b Temperature sensors 03 Water inlet filter 04a 09a 08 Differential Flow switch In/Out…
-
wa - ek - dk
STANDard ECOLOGIC WA WA Minimum outlet water temperature °C 5 Maximum inlet water temperature °C 20 Minimum difference water inlet/outlet °C 3 Maximum difference water inlet/outlet °C 8 Minimum outside air temperature °C 6 Minimum outside air temperature with low ambient kit °C -10 Maximum outside…
-
wa - ek - dk
HIGH EFFICIENCY ECOLOGIC WA WA Minimum outlet water temperature °C 5 Maximum inlet water temperature °C 20 Minimum difference water inlet/outlet °C 3 Maximum difference water inlet/outlet °C 8 Minimum outside air temperature °C 6 Minimum outside air temperature with low ambient kit °C -10 Maximum…
-
waH
STANDARD ECOLOGIC WAH - COOLING MODE WAH 150 200 Minimum outlet water temperature °C 5 Maximum inlet water temperature °C 20 Minimum difference water inlet/outlet °C 3 Maximum difference water inlet/outlet °C 8 Minimum outside air temperature °C 6 230 Maximum outside air temperature : • Normal…
-
WA
Operating limits for evaporator Water Test pressure bar 10 Refrigerant Test pressure bar 29 Water Max. operating pressure bar 6 Refrigerant Max. operating pressure bar 29 Water Minimum flow rate 3 m /h 8°C ∆T Water Maximum flow rate m3/h 3°C ∆T Safety Low pressure cut out bar 0,7 Safety Interlocking…
-
LCH - VK
standard all units LCH Operating limits Min. outlet water temperature Max. inlet water temperature Min. difference water inlet/outlet Max. difference water inlet/outlet Min. outside air temperature Min. outside air temperature (1) Max. outside air temperature (2) °C °C °C °C °C °C °C LCH Operating…
-
LCH - VK - PK
all units high ambient LCH Operating limits Min. outlet water temperature Max. inlet water temperature Min. difference water inlet/outlet Max. difference water inlet/outlet Min. outside air temperature Min. outside air temperature (1) Max. outside air temperature (2) °C °C °C °C °C °C °C LCH…
-
LCH - VK
low noise all units LCH Operating limits Min. outlet water temperature Max. inlet water temperature Min. difference water inlet/outlet Max. difference water inlet/outlet Min. outside air temperature Min. outside air temperature (1) Max. outside air temperature (2) °C °C °C °C °C °C °C LCH Operating…
-
LCH
Operating limits for Evaporator Water Test pressure Bar Refrigerant Test pressure Bar Water Max. operating pressure Bar Refrigerant Max. operating pressure Bar Water Min. flow m3/h Water Max. flow m3/h Operating limits for Pressure gauge control Safety Cut of low pressure Bar Safety Interlocking of…
-
RISK ANALYSIS AND HAZARDOUS SITUATIONS ACCORDING TO 97/23/CE DIRECTIVE
N° Event Effect Risk 1A Violent Chocks, Static or Dynamic Loads applied Appearance of cracks, distortions, Leaks, liquid or gas projections, possibility of rupture Metal parts projections. 2A Unit not installed properly or leveled to the ground Unusual stress in the frame leading to possible and…
-
RISK ANALYSIS AND HAZARDOUS SITUATIONS ACCORDING TO 97/23/CE DIRECTIVE
Event Effect Risk Actions to Eliminate the Risk Information to minimise the Occurrence of a risk Unit exposed to extremely corrosive materials. Modification of the mechanical and chemical properties of certain materials with a risk or corrosion rupture, pipe bursting, leaks and cracks. Partial or…
-
ECOLOGIC - REFRIGERATION CIRCUIT
REFRIGERANT DRAWING wa - ek - dk std/ln/he/sln 370 STD/LN/HE/SLN 02 19 S 08 07b Text Airflow S UDT T P P 01 HP P P S CE M 18 17 06b 05b 03 04b 04a 05a 07a 06a 09 14 Airflow REFRIGERATION CIRCUIT COMPONENTS 01 1st & 2nd scroll compressors 08 Air cooled condenser 15 Expansion valve bypass for low…
-
ECOLOGIC - REFRIGERATION CIRCUIT
REFRIGERANT DRAWING waH 150/200D/230D 04a 03 P HP 19 04b S Text P Airflow 08 01 07b C1 05a S P P 06a 05b 06b M YV 99 07a Airflow REFRIGERATION CIRCUIT COMPONENTS 01 1st & 2nd scroll compressors 08 Air cooled condenser/Evaporator 19 External temperature sensor 03 High pressure switch 09 Fan motor 20…
-
RA - REFRIGERATION CIRCUIT
-
ECOMAX - REFRIGERANT DRAWING (SCREW COMPRESSOR)
standard high ambient low noise all units 08 07b T AIRFLOW 18 01 M 20 P P D UDT 03 P HP P V 04b 16 06b 17 CE 04a 05a 05b M 07a 06a 75% T 09 50% 18 25% ON AIRFLOW eco Tex HA Refrigeration Circuit Component 01 Screw compressor 03 High pressure switch 04a 04b Pressure transducers HP & BP 05a 05b Low…
-
ECOMAX - REFRIGERANT DRAWING (PISTON COMPRESSOR)
-
Description
1-Alarm 1000 1-(date).(time) Code Description Code Description Code Unit 2100 1-Temperature 2110 1-Outside 2111 °C 2-Inlet 2112 °C 3-Outlet 2113 °C 1-SuperHeat 2121 °C 2-T°. Condensing 2122 °C 3-T°- Saturated 2123 °C 4-T°. Suction 2124 °C 5-P. Condensing 2125 b 6-P. Saturated 2126 b 1-SuperHeat 2131…
-
Description
2-Control Code 2200 Description Code Description Code Unit 7-In. % Custom 2170 1-Temp. 1 2171 °C 2-Temp. 2 2172 °C 3-Temp. 3 2173 °C 4-Temp. 4 2174 °C 1-Sp Cool 2211 °C 2-Sp Heat 2212 °C 3-Cap.Cool 2213 % 4-Cap.Heat 2214 % 5-Sw 2°Sp 2215 On/Off 6-Offset 2216 °C 1-SetPoint 2221 b 2-Capa. V1 2222 %…
-
Description
Code Description Code Description Code Unit 2-Comp.2 - Circ.1 2420 1-Config. 2421 Liste 2-State 2422 Liste 3-Sw State 2423 On/Off 4-Sw High P. 2424 On/Off 5-Sw Low P. 2425 On/Off 6-Relay 2426 On/Off 7-H.Pump 2427 On/Off 8-Bypass 2428 On/Off 9-Run Time 2429 h 1-Config. 2431 Liste 2-State 2432 Liste…
-
Description
5-EEV Code 2500 Description 6-Comp.3 - Circ.2 1-Circuit 1 2-Circuit 2 6-Ventilation 2600 1-Fan 1 - Circuit 1 2-Fan 2 - Circuit 1 3-Fan 3 - Circuit 1 Code 2460 2510 2520 2610 2620 2630 Description 1-Config. Code Unit 2461 Liste 2-State 2462 Liste 3-Sw State 2463 On/Off 4-Sw High P. 2464 On/Off 5-Sw…
-
Description
Code Description 4-Fan 4 - Circuit 1 5-Fan 1 - Circuit 2 6-Fan 2 - Circuit 2 7-Fan 3 - Circuit 2 Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 8-Fan 4 - Circuit 2 7-Option 2700 1-Recovery Code 2640 2650 2660 2670 2680 2710 Description 1-Config. Code 2641 Unit Liste…
-
Description
Code 3-Setting 3000 1-General 3100 Description 1-Order 2-Clock 1-Time 2-Schedule 3120 3210 Description 1-On/Off Code 3111 Unit On/Off Min Factory Max 2-Pompe 3112 Liste ~ Off ~ *[On / Off] Unit pump operation mode set up (see Pump operation description page 11 – IOM Climatic 50) 3-Reset Al. 3114…
-
Description
Code Description 3-Water Heat 4-Safety 4Compressor Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 5-EEV 6Ventilation 7-Option 3400 3500 3600 3700 Code 3330 3340 Description Code Unit 3-Sp Out.1 3323 °C 4-Sp Out.2 3324 °C 5-Reactiv. 3325 %/°C 1-Sp Wat.1 3331 °C 2-Sp Wat.2…
-
Description
Code 8-Config. 3800 Description 1-Unit 2-Out. Custom. 3-In. Custom. 4-In.% Custom. Code 3810 3820 3830 3840 Description 1-Range Code 3811 Unit Liste Min Factory Max 0 ~ 8 2-Size 3812 Liste 0 ~ 61 3-Pump 3813 Liste 0 ~ 2 4- gaz 3814 Liste 0 ~ 1 5-EEV 3815 Yes/No ~ ~ ~ 6-Modul. Fan 3816 Yes/No ~ ~ ~…
-
Description
Code Description 1-Display 9-Com. Code 3910 Description 1-Standard Sp Code 3911 Unit 3-BMS 3920 3930 Factory Max 1-ID 3921 ~ 1-Number 3922 ~ 2-Type 3923 Liste 1-ID 3931 ~ 2-Type 3932 Liste 3-Baud 3933 Liste Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 4-Watchdog 3934 ~…
-
таблицы и схемы — в просмотре
-
Description
Code Description Code Description Code Unit 6-Other 2160 1-Sw On/Off 2161 On/Off 2-Sw Flow 2162 On/Off 3-Sw Dis. C1 2163 On/Off 4-Sw Dis. C2 2164 On/Off 5- Sw Dis. C3 2165 On/Off 6- Sw Dis. C4. 2166 On/Off 7-Sw Reset 2167 On/Off 8-Sw Unoc. 2168 On/Off 1-Relay 1 2171 On/Off 2-Relay 2 2172 On/Off…
-
Description
Code Description Code Description Code Unit 2-Control 2200 1-Water 2210 1-Sp Cool 2211 °C 2-Cap.Cool 2212 % 3-Sw 2°Sp 2213 On/Off 4-Offset 2214 °C 1-SetPoint 2221 b 2-Capa. V1 2222 % 3-Capa. V2 2223 % 4-Capa. V3 2224 % 5-Capa. V4 2225 % 1-Config. 2311 Liste 2-State 2312 Liste 3-Sw Flow 2313 On/Off…
-
Description
Code Description Code Description Code Unit 2-Comp.2 - Circ.1 2420 1-Config. 2421 Liste 2-State 2422 Liste 3-Sw State 2423 On/Off 4-Sw High P. 2424 On/Off 5-Sw Low P. 2425 On/Off 6-Relay 2426 On/Off 7-Valve 2427 On/Off 8-Run Time 2428 h 1-Config. 2431 Liste 2-State 2432 Liste 3-Sw State 2433 On/Off…
-
Description
5-EEV Code 2500 Description 6-Comp.4 1-Circuit 1 2-Circuit 2 3-Circuit 1 4-Circuit 2 6-Ventilation 2600 1-Fan - Circuit 1 1-Fan - Circuit 2 Code 2460 2510 2520 2530 2540 2610 2620 • 83 • Description 1-Config. Code Unit 2461 Liste 2-State 2462 Liste 3-Sw State 2463 On/Off 4-Sw High P. 2464 On/Off…
-
Description
Code Description 2-Fan 2 - Cicuit 3 1-Fan - Circuit 4 Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 7-Option 2700 1-Recovery Code 2630 2640 2710 Description 1-Config. Code 2631 Unit Liste 2-State 2632 Liste 3-Sw State 2633 On/Off 4-Relay 1 2634 On/Off 5-Relay 2. 2635…
-
Description
4Compressor 5-EEV 6Ventilation Code 3400 3500 Description Code Description Code Unit 1-Circuit 3410 1-Rotat. 3411 Liste 2-Safety 3420 1-Frost 3421 °C 2-Time limit 3422 °C 1-SuperHeat 3511 2-Dead zone 1-Cooling 3510 3600 7-Option 3700 8-Config. 3800 1-Unit 2Compressor 3810 3820 Min Factory Max…
-
Description
Code 3-Setting 3000 1-General 3100 Description 1-Order 2-Clock 1-Time Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 2-Schedule 3120 3210 Description 1-On/Off Code 3111 Unit On/Off Min Factory Max 2-Pompe 3112 Liste ~ Off ~ *[On / Off] Unit pump operation mode set up…
-
Description
4Compressor 5-EEV 6Ventilation Code 3400 3500 Description Code Description Code Unit 1-Circuit 3410 1-Rotat. 3411 Liste 2-Safety 3420 1-Frost 3421 °C 2-Time limit 3422 °C 1-SuperHeat 3511 2-Dead zone 1-Cooling 3510 3600 7-Option 3700 8-Config. 3800 1-Unit 2Compressor 3810 3820 Min Factory Max…
-
Description
Code Description Code Description Code Unit Min Factory Max Comments *[ Configuration ] Fan configuration 3Ventilation 3830 1-Circuit 1 3831 Liste No = No fans Stages + = Single speed stage fans Modulation = 1 fan with speed control, others with single speed Low Speed = 1 fan with 2 speed others…
-
Description
Code Description 4-Option. 5-Out. Custom. 6-In. Custom. 7-In.% Custom. Code 3840 3850 3860 3870 Description 1-Pump Code 3841 Unit Liste Min Factory Max 0 ~ 2 2-Glycol 3842 % 0 ~ 50 3-Recovery 3843 Yes/No ~ ~ ~ 1-BE50.1 3851 Liste 2-BE50.2 3852 Liste 3-BE50.3 3853 Liste 4-BE50.4 3854 Liste 1-BE50.1…
-
Description
Code Description 1-Display 9-Com. Code 3910 Description 1-Standard Sp Code 3911 Unit 3-BMS 3920 3930 Factory Max 1-ID 3921 ~ 1-Number 3922 ~ 2-Type 3923 Liste 1-ID 3931 ~ 2-Type 3932 Liste 3-Baud 3933 Liste Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E 4-Watchdog 3934 ~…
-
CERTIFICATES
Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E • 91 •
-
CERTIFICATES - PED
• 92 • Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E
-
CERTIFICATES - DECLARATION OD CONFORMITY CE
Installation - Operation - Maintenance manual • CHILLERS • ANNEXES - 0105-E • 93 •
-
BELGIUM
CZECH REPUBLIC : FRANCE : GERMANY : LENNOX BENELUX N.V./S.A. tél. : + fax : + e-mail : info.be@lennoxbenelux.com LENNOX JANKA tél. : + fax : + e-mail : janka@janka.cz LENNOX FRANCE tél. : + fax : + e-mail : marketing.france@lennoxfrance.com LENNOX DEUTSCHLAND GmbH tél. : + fax : + e-mail…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.