Инструкция на Панель управления DeLonghi серии EVOLUTION прецизионными кондиционерами
Панель управления DeLonghi серии EVOLUTION для прецизионных кондиционеров. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
INSTRUCTION MANUAL
GB USER TERMINAL: EVOLUTION
-
CONTENTS
U I A General characteristics 2 U I A User interface 2 U I A Main screen 3 U I A Flow charts for accessing the screens 7 U I A Default values 11 U I A Diagram of ambient temperature control 12 U I A Diagram of ambient humidity control 13 U I A General information and definitions 14 U I A Most common…
-
GENERAL CHARACTERISTICS
The EVOLUTION controller allows independent control of all the unit operating parameters. The controller is made up of: • A microprocessor control board housed inside the electrical panel • A user terminal or graphic interface The program that resides on the control board can be used on all types of…
-
MAIN SCREEN
I A The following figure shows the layout of the main screen. Area 1 - GENERAL STATUS OF THE UNIT. unit off unit on Area 2 - DETAILED INDICATION OF THE UNIT STATUS. presence of an active alarm (flashing) maintenance signal (flashing) manual controls active (flashing) unit on/off from terminal…
-
Area 3 - ALARMS LIST
This area displays an icon that, in the event of alarms or maintenance signals, respectively indicates the type of alarm and the device that requires maintenance. EEPROM fault LAN disconnected Water leak (flood) 1 2 High pressure in circuit 1 High pressure in circuit 2 EVENT OF ALARM In case of…
-
Area 4 ACTIVE COMPONENTS
This area displays icons corresponding to the devices currently installed on the unit. 1 compressor 1 active 2 compressor 2 active 1 2 compressors 1 and 2 active 1 first electric heater stage active 2 second electric heater stage active 1 2 first and second heater stages active (third stage active)…
-
STATUS SCREENS
Starting from the main screen, pressing the UP/DOWN buttons accesses the other status screens, which are, in order: A WATER VALVE STATUS/OPTIONAL PROBE READINGS: screen displaying the temperature values read by the optional probes (outlet air temperature probe, chilled water temperature probe, hot…
-
FLOW CHARTS FOR ACCESSING THE SCREENS
U I A MAIN LOOP SCREENS MAIN SCREEN A Water valve status Optional probe readings B LAN status C Humidifier status D Set points E User PASSWORD Change set point Change proportional band User PASSWORD Change maintenance threshold User PASSWORD Reset operating hours Reset number of starts Operating…
-
SCREENS FOR SETTING THE PARAMETERS
SCREENS “I” Starting from the main screen, pressing the PRG button and entering the correct password accesses a menu used to set all the other parameters that are not available on the status screens, as described in the previous paragraph. Two passwords can be entered: Screen “I1” Used to modify…
-
SCREENS “N”
Screen “N1” Used for clock settings SCREENS “O” Screen “O1” & “O2” Used to activate manually the unit and also each single componenets installed on it. Screen “O3” & “O4” Used to check all contact available on board SCREENS “P” These screens are of foundamental importance for the right unit…
-
SETTING PARAMETERS SCREENS
MASCHERA PRINCIPALE PRG password (*) I SETUP I1 I2 Temp. and Humidity limits ALARMS DELAY L1 L SETUP I3 RESET MODE ALARMS OUTPUT STATUS L2 LAN SETUP L1 I5/I6 I4 L3 STANDBY UNIT SETUP SERIAL SETUP L2 M ADVANCED PARAMETERS SETUP A/B SETUP L3 SENSORS ADJUSTMENT Password N1 N CLOCK SETUP SETUP O1 O…
-
USER DEFAULT VALUES
Set points and differential band Cooling set point Cooling proportional band Heating set point Heating proportional band Dehumidification set point Dehumidification proportional band Humidification set point Humidification proportional band Maintenance operating hour threshold Fan Compressor 1…
-
AMBIENT TEMPERATURE CONTROL DIAGRAMS
-
TERMINAL EVOLUTION
30% on off differential 55% differential 50% differential 45% off compressor 5% 40% 0% off Cold water valve 5% 100% 10% DEAD ZONE dehumidification set point 3% 33% low ambient humidity alarm humidifier humidification set point 60% on on off 77% differential 3% 80% high ambient humidity ambient rH%…
-
GENERAL INFORMATION AND DEFINITIONS
U I A 1 The local network connection is used to manage the operation of a series of air-conditioners operating inside the same environment, or a series of liquid chillers connected in parallel in the same installation. 2 The max number of units that can be connected is 10. 3 The maximum extension of…
-
MOST COMMON CONFIGURATIONS
U I A 1 Up to 10 units connected in the network with just one remote share terminal In this configuration, a power failure on the first unit will cause the terminal to shutdown, and therefore the information corresponding to the units in the network can no longer be read. Nonetheless, the other…
-
ELECTRICAL CONNECTIONS
The electrical connections must be completed when the units are off and disconnected from the power supply. The network can have different configurations, according to the maximum distance of the connections between the boards and the remote terminal; for the connections between the remote terminal…
-
J11
shielded cable shield J11 The shield on the shielded cable is earthed at a single point in the network. Earthing the cable at different points in the network may cause control malfunctions. The connection must be made, where possible, by fastening the cable with a metal clamp, as shown in the figure…
-
CONNECTION TO THE REMOTE TERMINAL FROM THE BOARD
U I A EXAMPLE OF CONNECTION TO THE REMOTE TERMINAL POWERED BY THE BOARD This configuration requires: 1 the use of two 'T' shunts: one fitted on the unit and one near the remote terminal; 2 the use of the 3x2 shielded cable, so that the power to the remote terminal is also supplied by the board on…
-
CONFIGURATION OF THE TERMINAL AND THE BOARD
SETTING THE LOCAL NETWORK ADDRESS ON THE EVOLUTION TERMINAL AND THE pCO1 BOARD Before setting the addresses, first check the LAN connection between the boards, the connection to the remote or shared terminal, and the power supply connections to the unit. The terminal address can be set only after…
-
TABLE OF TERMINAL ADDRESSES AND LAN BOARD
ADDRESSES fig. 2 Terminal address (displayed automatically) LAN Board Address (set using the buttons on the terminal) Terminal address (displayed automatically) LAN Board Address (displayed automatically) 32 (remote) - Board no. 2 Board no. 3 shared user terminal no.32 Fig. 1 represents a network…
-
TROUBLESHOOTING
PROBLEM The user terminal does not switch on or does not communicate with the unit. The user terminal is on but no icons or menu items are displayed. The shared user terminal cannot communicate with the unit or the units connected in the network (LAN). CAUSE I A SOLUTION The connection cable between…
-
COD. 5787000900
Dé Longhi Group - Via L. Seitz, 47 - 31100 Treviso (Italia)