Инструкция на Контроллеры смесительных контуров Baxi серии RVA 46
Контроллеры смесительных контуров Baxi серии RVA 46.531/109 для конденсационных котлов. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
Heating Circuit
ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER
-
1 Electrical connections of RVA 46 controller
L N Mix valve H1 N Y2 Y1 F2 M B1 Pump N H1 – Input signal QAD21 MD A6 MB DB Q2 F6 L QAA50 N OCI420 Figure 1 DB 6 pins connector WHITE colour * MB H1 : Input signal (thermostat contact, if present)) M :Ground sensors B1 : Flow sensor mixing valve SIEMENS QAD21 2 pins connector LIGHT BLUE colour MD…
-
2. Wall installation of RVA 46
2.1 Regulations for installation Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it. A clearance of at least 10 mm must be provided for the controller's cooling slots which are situated a the top and bottom of the housing. The space should not be…
-
Slide the controller into the panel cut-out without
applying any force Note: do not use any tools when inserting the unit into the cutout. If it does not fit, check the size of the cutout and the position of the fixing levers. Tighten the 2 screws on the front of the controller Note: tighten the screws only slightly, applying a torque of maximum 20…
-
MR
MR : FLOW TEMPERATURE RR : RETURN TEMPERATURE SE : OUTSIDE SENSOR VZ : ZONE VALVE LEGEND HIGH temperature zone LOW temperature zone Q2 : HEATING CIRCUIT PUMP SM: FLOW TEMPERATURE SENSOR (QAD21) TA : ROOM THERMOSTAT VM: MIXING VALVE LOW temperature zone LOW temperature zone Hydraulic system example…
-
N : MAINS CONNECTION NEUTRAL CONDUCTOR VM : MIXING VALVE MOTOR Q2 : HEATING CIRCUIT PUMP QAD21 : FLOW TEMPERATURE SENSOR QAA50 : ROOM UNIT LEGEND Terminal board cap COPERCHIO M2 MORSETTIERA Terminal board M2 MORSETTIERA QAC 34 Outside sensor: connect directly to gas boiler terminal block M2 (pin…
-
MR
MR: FLOW TEMPERATURE RR: RETURN TEMPERATURE VM : MIXING VALVE Q2 : HEATING CIRCUIT PUMP VZ : VALVE ZONE SM : FLOW TEMPERATURE SENSOR (QAD21) TA : ROOM THERMOSTAT BP : BYPASS RE : RELAY L : MAINS CONNECTION LIVE AC 230 V N : MAINS CONNECTION NEUTRAL CONDUCTOR TA : ROOM THERMOSTAT LEGEND Heating low…
-
3. Description of the RVA 46
The RVA 46 Temperature Regulator is an electronic device designed to control low-temperature zone-type heating systems. The following components are necessary for operation of the RVA 46 Temperature Regulator. SIEMENS OCI 420 communications interface (see instructions supplied with the accessory…
-
4. Setting the parameters
4.1 Parameter setting level a) End user b) Installer 1…….50 51……98 To access one of these parameters, follow the instructions provided below: a) Parameter settings for the end-user Buttons Explanation 1 Line Press one of the line selection buttons. This will take you to the programming mode "End…
-
Function
16 Summer / winter changeover temperature 8...30 °C 0,5 Slope of heating curve 2,5...40 0...50 °C °C 0,5 0,5 15 - 19 Actual value of outside temperature -50…+50 °C 0,5 - 0/1 – 1 0 0...255 – 1 – Actual value of room temperature (QAA50) To reset the attenuated outside temperature to, press the + and…
-
Parameters
Function Range Unit Resolution Factory setting Service values Attenuated outside temperature Composite outside temperature Flow temperature setpoint -50…+50 -50…+50 0…140 °C °C °C – – – -4,5...+4,5 0/1 °C (K) – 0,5 1 0,0 1 --.-…4,0 °C (K) 0,5 --:- Heating circuit 64 65 Parallel displacement of…
-
Unit
Factory setting Parameters Function Range Resolution 90 91 Winter- / summertime changeover Summer- / wintertime changeover 01.01..31.12 01.01..31.12 Day, month Day, month 1 1 25.03 25.10 0...2 – 1 0 8…95 °C 1 70 0/1 – 1 1 Input signal H1 96 Input H1 97 Minimum flow temperature setpoint contact H1…
-
N.B.: if the heating system has a RVA47 regulator for control of a system with cascade-connected
boilers, set the clock of the RVA47 as MASTER clock (see instructions supplied with the regulator itself). The time, day and year must only be set on the MASTER regulator. All the RVA 46 devices connected to the MASTER are updated automatically. 6. Setting the RVA46 parameters for the type of room…
-
To set the heating curve, proceed as follows
Select program line n° 17. Press the +/- keys to set the curve required (factory setting = 15). For low temperature heating systems (e.g. underfloor systems), set a low gradient curve. N.B.: if the QAA50 digital room unit is connected to the system, the RVA 46 regulator will adapt the curve…
-
8. System delivery temperature minimum and maximum threshold
The minimum and maximum thresholds set the range within which the delivery temperature is permitted to vary, in order to prevent excessively high or low delivery temperatures. To set the thresholds, proceed as follows: Select program line n° 68. Press the +/- keys to set the delivery temperature…
-
10.2 Setting the system type
The electronic circuit board must be set up for the type of system present. Select program line n° 552 as described in the previous point; Press the +/- keys to set the boiler's water system type (see table). Level Parameter N. Description H 552 System setting Factory setting single purpose dual…
-
The test sequence is as follows
0 = displays the instantaneous delivery temperature of the delivery sensor SM; 1 = not covered; 2 = displays the instantaneous temperature measured by the QAA 50 digital room unit (if connected); 3 = displays the input status of the contact of the room temperature thermostat TA: • • 000 : thermostat…
-
14. Troubleshooting
In case of malfunctions, the message "Er" (Error - Figure 11) appears on the display. Malfunctions can be displayed as follows: Select program line n° 50. Press the +/- keys to display the malfunctions. N.B.: the RVA 46 regulator is able to save up to 2 malfunctions, which can be called onto the…
-
15. Technical data
Nominal voltage Nominal frequency Power consumption Safety class Degree of protection Electromagnetic immunity Electromagnetic emissions Maximum temperature admitted: Storage Transport Operation Output relays voltage range nominal current switch-on peak fusing Bus extenction - terminals MD-A6 (2…