Air-condensed water chillers and
heat pumps YLCA / YLHA 40 User manual Ref.: N-40288_EN 0910
-
General description of the unit
1.1 General description of the unit The YLCA/YLHA units are high-performance air-water chillers and heat pumps using R-410A ecological refrigerant. These units are designed for air conditioning or industrial applications that require cold or hot water. They are silent and compact units, equipped…
-
General description of the unit
1 1.1 1.1.2 Technical specifications These units are supplied completely factory-assembled and with all refrigerant tubing and wiring ready for installation on site. After mounting, these units must go through an operational test with water. Re‐ frigerant leaks will also be checked during this…
-
General description of the unit
Hydro kit (pack) These units include a pack assembled with the components of a hydro kit. This assembly is located within the unit frame and does not increase the footprint of same. It includes the following components: Lined buffer tank and with an antifreeze heater, centrifugal pump, expansion…
-
General description of the unit
1 1.1 Options and accessories Units without hydro kit This includes the elements described in the previously mentioned specifications, less the hydro kit (pack). The water circuit includes an air bleed valve. Connections are ready for on-site installation. Two pumps Accessory available with models…
-
General description of the unit
Antivibratory supports Whenever necessary to reduce vibrations and noise produced by the unit to a maximum, a set of steel spring antivibratory supports can be used. These should be installed between the chassis support of the unit and the base or floor on which it is to sit. This base must be solid…
-
1.2 Operating instructions µC2 (YLCA/YLHA 40)
DESCRIPTION OF THE CONTROL UNIT This is a multipurpose controller specially programmed for use with air-water chillers and heat pumps equipped with a compressor with one single power stage. Main functions • Water temperature control (at inlet or outlet, as per parameter r6). • Defrost cycle…
-
Direct Level
Accessible without a password. Allows for reading of the values detected by the sensors, as well as other system values. Can be used by the user without affecting unit operation. General Modification of the parameters that affect basic unit configuration should be made with the controller in Standby…
-
1.2.1 General diagram, YLCA / YLHA 40
A Four-way valve B2 Water outlet temperature sensor (Antifreeze pro‐ tection) B Pump B3 Outdoor temperature sensor (Dynamic set point) C Heater B4 Radiometric pressure sensor (Fan speed and de‐ frost control) D Compressor 1 ID1 Water flow switch E Alarm ID2 Remote COOL / HEAT F 230 / 24 transformer…
-
1.2.2 Symbols on the display
The display has three figures in green, plus the sign and one decimal. It also shows the symbols of the functions selected in orange (the alarm symbol is red). Button Meaning Colour LED permanently lit -2-7Orange -8- Timing start-up Compressor on call - Water pump operating - -9- Fans operating…
-
1.2.3 Location of controls (YLCA / YLHA 40)
A Temperature sensor (B3) H Low-pressure switch (LP) B Fan I Compressor C Flow switch (FS) J high-pressure switch (HP) D NTC water outlet sensor (B2) K Four-way valve E Indoor heat exchanger L Outdoor heat exchang‐ er F NTC water inlet sensor (B1) M Pressure sensor (B4) G Pump Parameter tables The…
-
1.2.4 Parameters relating to sensors
-
1.2.6 Operating graphics
Min. operating time of a compressor A Signal B Compressor Min. stoppage time of a compressor A Signal B Compressor Min. time between compressor start-ups A Signal B Compressor 13
-
Compressor / pump stoppage delays
A Compressor B Pump Pump / compressor start-up delays A Pump B 14 Compressor
-
1.2.7 Parameters relating to fans
Parameters relating to fans Display F01 Description Fan outlet: 0= Absent (function not available Level VS F Unit Max. Min. Value 10 (R/W) U 48 (R/W) 1= Present Operating mode: 0=Always ON (function not available) F02 1= parallel to the compressor (function not available) 2=ON/OFF operation…
-
1.2.8 Parameters relating to defrost
-
1.2.9 Antifreeze control configuration parameters
Antifreeze control configuration parameters Parameters Description Level VS Unit Max. Min. Value A01 Antifreeze control set point temperature U 11 (R/W) °C - A07 3 A02 Antifreeze reset differential U 12 (R/W) °K 50 0,3 5 A03 Antifreeze alarm bypass time U 22 (R/W) Seconds A04 Antifreeze heater…
-
1.2.10 Unit configuration parameters
-
1.2.11 Alarm configuration parameters
Alarm configuration parameters Parameters Level VS Unit Max. Min. Value P01 Alarm delay by flow switch at start-up. U 63 (R/W) Seconds P02 Alarm delay by flow switch with unit in operation. U 64 (R/W) Seconds P03 Alarm delay by low-pressure switch at start-up. U 65 (R/W) Seconds P05 Alarm reset 6=…
-
1.2.12 Controller configuration parameters
-
1.2.13 Alarm table
Alarm table Display Alarm type Reset A1 Antifreeze alarm Manual Aht High temperature at start-up (if activated, P20=1) Automatic ALt Low temperature at start-up (if activated, P20=1) Automatic d1-2 Defrost operating - dF1-2 Problem in defrost Automatic E1 B1 sensor Automatic E2 B2 sensor Automatic…
-
1.2.14 Functions
Alarm reset Pressing the UP and DOWN keys for 5 seconds cancels alarms present in the memory. At the same time, the alarm message disappears from the display and the alarm relay is deactivated. Forced defrost (heat pumps) Pressing the SEL and UP keys simultaneously for 5 seconds activates forced…
-
Regular maintenance activities for which the user is responsible
1 1.3 1.3 Regular maintenance activities for which the user is respon‐ sible 1.3.1 Maintenance Schedule The air conditioning unit is designed to require as little maintenance as possible. Nevertheless, to ensure smooth operations with a minimal use of electricity, a long working life and compliance…
-
User manual Regular maintenance activities for which the user is responsible DANGER It is strictly prohibited for the user to carry out any maintenance or upkeep tasks on the HVAC unit. This appliance is not destined for use by people (including children) with limited physical, sensorial or mental…