Air-condensed water chillers and
heat pumps YLCA / YLHA Installation manual Ref.: N-40287_EN 0910
-
таблицы и схемы — в просмотре
-
Installation manual Safety instructions 1.1 Safety instructions This document contains the necessary information for the safe and efficient transportation, assembly and installation of the air conditioning unit. This guarantees the condition of the unit and its operating safety. Only an authorised…
-
Instructions for storage, transport, loading and unloading of the unit
1 1.3 1.3 Instructions for storage, transport, loading and unloading of the unit CAUTION Outdoor units must be moved and stored vertically to prevent oil from leaking from the compressor. Delivery inspection The unit should be carefully inspected for visible damage or abnormalities as soon as it is…
-
Selection guide (YLCA/YLHA)
1.3.3 Disposal of the unit When removing the unit, the components must be ecologically recovered. The refrigeration circuit is full of refrigerant that must be extracted and delivered to the gas manufacturer for recycling. ATTENTION The refrigerant gas contains greenhouse-effect fluorinated gas…
-
Selection guide (YLCA/YLHA)
1 1.4 SELECTION EXAMPLE A chiller is required to chill water from 13°C to 7°C, with a cooling capacity of 119 kW. There are also other design conditions: • Ambient air entering the condensing unit 35°C • Fouling factor: 0.044 m2 °C/kW • Altitude: Sea level Taking a quick look at the table, we can…
-
Selection guide (YLCA/YLHA)
YLHA SELECTION EXAMPLE A YLHA heat pump operating at a 35°C ambient temperature should chill water from 13°C to 7°C, with a 112 kW cooling capacity. A 110 kW heating capacity is required in 5°C design ambient temperature and a hot water output tem‐ perature of 40°C. The fouling factor is 0.044 m2…
-
Selection guide (YLCA/YLHA)
1 1.4 1.4.1 Selection guide with glycol (cooling only units) Necessary information The following information is needed to select a YLCA water chiller: 1 Cooling capacity needed 2 Design cold water/glycol input and output temperatures. 3 Design water/glycol flow. 4 Design input temperature of air to…
-
Selection guide (YLCA/YLHA)
On design glycol concentration, apply the capacity correcting factors x 1.015 and power x 1.005 (see Correcting factors for other glycol concentrations, see on page 12). Applying these factors to the selection: YLCA ‑120 Capacity = 76.8 x 0.987 x 0.973 x 1.015 = 74.9 kW Comp. power = 28.8 x 0.995 x…
-
1.5 Technical data
1.5.1 Limits of use Voltage limits Model YLCA YLHA Nominal at 400 Input air temperature to the coil DB Water output temperature Operating cycle Operating cycle Minimum °C Maximum °C Minimum °C Maximum °C Mini‐ Maxi‐ mum mum Cold Cold Cold Cold 342 -18 436 Heat -10 46 Heat 20 5(1) Heat 30 15 Heat…
-
Glycol concentration and correcting tables
Recommended ethylene glycol concentrations A % in weight a Recommended concen‐ tration % in weight B Outlet liquid tempera‐ ture C b Freeze point C Glycol factor L/S °C/kW in recommended con‐ centrations c Glycol factor in recom‐ mended concentrations Ethylene glycol in other concentrations. A…
-
Propylene glycol in other concentrations
A Glycol factor B Outlet liquid temperature °C C Glycol factor Ethylene glycol pressure drop correcting factor A Correcting Factor B Average liquid temperature °C C Glycol concentration P/P Propylene glycol pressure drop correcting factor A Correcting Factor B Average liquid temperature °C C Glycol…
-
Correcting factors for other glycol concentrations
% in weight Ethylene glycol Propylene glycol Capacity Absorbed power Capacity Absorbed power 10 1,061 1,025 1,097 1,033 20 1,036 1,015 1,067 1,023 30 1,015 1,005 1,026 1,008 0,985 0,995 0,974 0,992 50 0,954 0'985 0,923 0,977 If it is necessary to select different glycol percentages, correct the…
-
Pressure drop in the YLCA/YLHA 40 ÷ 150 hydraulic circuit without pack (no filter
fitted) YLCA-YLHA model Flow l/h kPa Flow l/h kPa 4750 13 YLCA-YLHA model 9500 40 5500 19 10000 43 6250 26 11000 48 7000 33 12000 53 7750 42 13000 59 8500 50 14000 65 9250 61 15000 72 10000 71 16000 79 10750 84 17000 87 6500 25 18000 96 7000 28 19000 107 7500 31 20000 119 8000 34 21000 132 8500 37…
-
YLCA-YLHA model
-
Available pressure for the YLCA/YLHA 40 ÷ 150 hydraulic circuit with pack (no
filter fitted) YLCA-YLHA TP model Flow l/h kPa Flow l/h kPa 4750 261 YLCA-YLHA TP model 12000 245 5500 218 13000 236 6250 166 14000 226 7000 105 15000 215 7500 60 16000 201 8000 13 17000 187 6500 149 18000 171 7000 142 19000 153 7500 135 20000 131 8000 127 21000 110 8500 119 22000 87 9000 110 23000…
-
Pressure drop in filters
1 1/2" filter Water flow (l/h) 3500 4000 4500 5000 5500 6000 6500 7000 7500 kPa 1,3 2,6 4 5,4 6,9 8,4 10 11,6 13.3 Water flow (l/h) 8000 8500 9000 9500 10000 10500 11000 11500 11800 kPa 15 16,8 18,7 20,7 22,8 25 27,3 29,7 32 2" filter Water flow (l/h) 6000 7000 8000 9000 10000 11000 12000 13000 kPa…
-
1.5.3 Physical data
Physical data, YLCA units Physical data YLCA (T and TP) Characteristics kW 39,6 52,1 60,5 72,6 Capacity control % 100 Power supply V/ph Cooling capacity EER/OOP Compressor 50-100 25-50-75-100 400.3.50 3 2,9 3,1 2,9 2,9 2,9 2,8 Compressor consumption kW 12,46 2 x 8.5 2 x 9.2 2 x 12.4 4 x 7.8 4 x 9.4…
-
Weights for the empty unit
(2) Static pressure available, Eurovent certified (3) Pressure with clean filter Units without pack YLCA Characteristics Start-up current (compressor) A Water circuit pressure drop kPa 27,5 17,2 23,6 24,8 33,6 50 53 67,3 Unit water content Max. unit power supply consumption kW Max. current amperage…
-
Physical data, YLHA units
Physical data YLHA (T and TP) Characteristics Cooling capacity kW 37,8 52 60,5 72,2 Heating capacity kW 38,6 52,5 59,6 74,7 104 119,6 150 Capacity control % 100 Power supply V/ph EER/OOP Compressor 40 50-100 25-50-75-100 400.3.50 2,7/2,8 2,6/3 2,8/2,8 Compressor consumption in cooling kW 12,4 2x8 2…
-
Weights for the empty unit
-
1.6 Measurements, clearances and accesses
1.6.1 Clearances When installing each unit, clearances should be left for: 1 Air inlet and discharge. 2 Maintenance servicing. 3 Power supply connections. For proper operation, all minimum clearances shown on the general dimension diagrams should be respected always with regard to possible…
-
Minimum technical clearance YLCA/YLHA 100 ÷ 150
22 A Water inlet and outlet B Air
-
1.6.2 Dimensions and hydraulic connections (models YLCA/YLHA 40)
A Air outlet C Water outlet B Water inlet D Air inlet 23
-
1.6.3 Dimensions and hydraulic connections (models YLCA/YLHA 50 and
60) 24 A Water inlet 1 2" GF (Inlet) B Water outlet 2 2" GF (Outlet)
-
1.6.4 Dimensions and hydraulic connections (models YLCA/YLHA 80)
A Water inlet 1 2" GF (Inlet) B Water outlet 2 2" GF (Outlet) 25
-
1.6.5 Dimensions and hydraulic connections (models YLCA/YLHA 100,
-
Cooling capacities YLHA
-
Installation manual Cooling capacities YLHA 1.7.2 Cooling capacities YLHA 40 ÷ 150 (35% ethylene glycol) Outdoor ambient temperature °C DB (80% RH) YLHA model Water outlet temp. °C Ca‐ pacity kW kW kW -5 26,35 7,39 25,27 -4 27,86 7,61 26,69 -2 30,58 8,03 29,42 0 33,32 8,44 2 37,19 20 25 Abs. power…
-
Cooling capacities YLHA
-
Cooling capacity YLCA
1 1.8 1.8.2 Cooling capacities YLCA 40 ÷ 150 (35% ethylene glycol) Outdoor ambient temperature °C DB (80% RH) YLCA Model Water outlet temp. °C Ca‐ pacity kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW -5 27,64 7,38 26,5 8,03 25,35 8,78 24,88 9,11 24,1 10,2 22,21 10,59 21,16 11,18 20,04 11,86 -4…
-
Installation manual Instructions for installation and connection of the unit 1.9 Instructions for installation and connection of the unit 1.9.1 Characteristics of the location Before locating the unit, make sure you have received the appropriate product by checking the specifi‐ cations described on…
-
1.9.4 Preparation and connecting to the various utilities Electricity. Power and control Wiring diagrams Electrical installation YLCA / YLHA 40 A YLCA / YLHA termi‐ nal strip B Outdoor strip C Main switch a b c Remote ON / OFF switch d Remote COOL / HEAT switch CLOSED = COOL OPEN = HEAT (YLHA units…
-
Electrical installation, YLCA 50, 60 and 80 A YLCA terminal strip b General alarm (voltage-free inverter contact max. 2A re‐ sist. at 230 Vac) B Outdoor strip c Remote ON / OFF switch C Main switch d Pump heat protectors Auxiliary contacts Pump contacts a Supply (400 ‑ 3 + N ‑ ph ‑ 50 Hz) e Pump…
-
Electrical installation YLHA 50, 60 and 80 A YLHA terminal strip terminal c Remote ON / OFF switch d Remote COOL / HEAT switch CLOSED = COOL OPEN = HEAT (YLHA units only) B Outdoor strip C Main switch e Pump heat protectors Auxiliary contacts Pump contactors a Supply (400 ‑ 3 + N ‑ ph ‑ 50 Hz) f…
-
Electrical installation YLCA/YLHA 100, 120 and 150 A YLCA / YLHA termi‐ nal strip c General alarm (voltage-free inverter contact max. 2A re‐ sist. at 230 Vac) B Outdoor strip d Remote ON / OFF switch C Main switch a Supply (400 ‑ 3 + N ‑ ph ‑ 50 Hz) e Remote COOL / HEAT switch CLOSED = COOL OPEN =…
-
Instructions for starting up the unit 1.10
1.10 Instructions for starting up the unit 1.10.1 Start-up About 45 seconds after powering the unit, the start-up display is activated. Default language: English. 1st Display. START-UP (information on water temperature/unit status) • Water inlet temperature • Water outlet temperature • Unit status…
-
1.11 Unit sound power spectrum data
1.10.2 Rotational direction of Scroll compressors The Scroll compressors and the fans only operate correctly if they rotate in the correct direction. All of the motors and compressors in the unit are connected so that they rotate correctly. If the compressors are not connected correctly and are…
-
Unit installation data 1.12
1.12.1 List of tests for unit start-up Please complete the following forms to register the full details of the installation and the start-up inspec‐ tion. Complete the blank fields or mark the appropriate box, as applicable. Company performing installation Company performing installation Installing…
-
1.12 Unit installation data
1.12.2 Start-up Data Electrical data Rating plate Actual Power supply Control voltage Fan consumption (A) Consumption of condenser fan 1 (A) Consumption of condenser fan 2 (A) Consumption of compressor 1 (A) Consumption of compressor 2 (A) Check specifica‐ tions in the Installa‐ tion Manual…
-
Unit installation data 1.12
Air temperature Mode (cool or heat) Temperature (C) Outdoor air Supply air Return air Indoor air mix (if economiser is fitted) Options Heating mode (hot water coil) Air temperature Capacity (kW) Temperature (C) Supply air (at 100 %) Return air Hydraulic circuit Temperature (C) Pressure (bar) Water…
-
1.12 Unit installation data
Notes and observations Notes and observations Installed by Name Date and signature 42
-
Wiring diagrams 1.13
1.13 Wiring diagrams 1.13.1 Unit wiring diagrams Wiring diagram, YLCA/YLHA 40, 400.3.50 43
-
1.13 Wiring diagrams
(*) On units with hydro kit only 1* Alarm HTP Heater thermal protection A Electronic control K1 Compressor contactor B The components in the box are standard accessories supplied by the manufacturer K2 Auxiliary heater contactor C The components in the box are not supplied by the manufacturer K3…
-
Wiring diagrams 1.13
-
1.13 Wiring diagrams
46 (*) On units with hydro kit only (**) On units with hydro kit and two pumps only (***) On 50 and 60 units only A The components in the box are not supplied by the manufacturer FS Water flow switch B The components in the box are standard accessories supplied by the manufacturer FSC Fan speed…
-
Wiring diagrams 1.13
-
1.13 Wiring diagrams
-
Wiring diagrams 1.13
(*) On units with hydro kit only (**) On units with hydro kit and two pumps only (***) On 50 and 60 units only (1) Units without pump A The components in the box are not supplied by the manufacturer FS Water flow switch B The components in the box are standard accessories supplied by the…
-
1.13 Wiring diagrams
-
Wiring diagrams 1.13
-
1.13 Wiring diagrams
52 (**) Pm YLHA units only N10 ‑ C10 = Voltage-free contact (-A- general protection alarm) a White b Black c Green
-
Wiring diagrams 1.13
A Keyboard-display terminal B Terminal connection FSC1, FSC2 Circuit 1 and 2 fan speed controllers F10 (FSC1, FSC2) C Programmable key connection Fuses of the fan speed controllers D Control module E Identification of the connectors and their terminals F Control box G Distribution of motors and…