Инструкция на Бытовые кондиционеры Roda серии X-SPACE
Бытовые сплит-системы Roda серии X-SPACE RS/RU-V09A, RS/RU-V12A, RS/RU-V18A, RS/RU-V24A. Инструкция по сервисному обслуживанию.
Смотрите также: Инструкция по установке и эксплуатации →
Загружаем документ…
Текст инструкции
-
AIR CONDITIONER
-
CONTENTS
OPERATION RANGE SPECIFICATION INSTALLATION REFRIGERANT FLOW DIAGRAM ELECTRICAL DATA CONTROL MODE TROUBLE SHOOTING PAGE NOTE: The figure, size and parameter of the product may not be identical with the service manual, please take the actual product as the standard.
-
1. OPERATING RANGE
-
2. SPECIFICATIONS
2-1. Unit specifications Model No. Type Ratings Cooling Capacity W Heating Capacity W Rated Input-Cooling W Rated Input-Heating W Moisture Removal L/H.r Air Circulation m3/h EER for Cooling W/W COP for Heating W/W Energy Class Cooling Energy Class Heatling Refrigerant Refrigerant charge volume g…
-
3. INSTALLATION
1. How to choose an air conditioner: a. Choice for reference: 150-170W/㎡ for average rooms; b. Choice for reference: 160-200W/㎡ for small size offices; c. Choice for reference: 220-350W/㎡ for restaurants; d. Choice for reference: 200-300W/㎡ for entertaining venues; e. Choice for reference…
-
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant flow diagram : OUTDOOR INDOOR COMPRESSOR CONDENSER EVAPORATOR CHECK VALVE ASS'Y 2 CAPILLARY CAPILLARY .6.
-
4. REFRIGERANT FLOW DIAGRAM
4-2. Evacuation procedures: Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will not work in its initial Connect the gage manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit. Run the…
-
5-1.Electrical wiring diagrams
-
a. The indoor unit has one control board
-
b. The indoor unit has one control board and one power board
-
OUTDOOR
-
5-2. Sensor parameter
-
2. THE PARAMETER OF THE OUTD OOR COIL AND OUTDOOR SENSOR :
-
3.THE PARAMETER OF THE INDOOR COIL AND INDOOR ROOM SENSOR
(R0=15K;B=3450) .18. :
-
6-1. Major general technical parameters
6-1-1 Conditionings for operation: Ambient temperatures: (-15 - +45 ℃), relative humidity (45 - 85%). 6-1-2 Remote receiver distance: 8 m. 6-1-3 Remote receiver angle: Less than 80 degrees. 6-1-4 Temperature control accuracy: ±1℃. 6-1-5 Time error: Less than 1%. 6-1-6 The power supply for the air…
-
forced cooling with the indoor fan speed being set at high speeds, the
flaps sweeping and the air conditioner’s operation is irrelevant with room temperatures. 6-3-1-3 If a remote signal has been received during the emergency run, the machine will operate upon the command of such a remote signal. 6-3-2 Operator-machine communication 6-3-2-1 The air conditioner has a…
-
has not received a signal from the remote controller when the set time is
up, it will automatically start and operate in the preset conditions. 6-3-3-2 Timer off: When set to stop in a set time by the remote controller, the air conditioner will start in the timer off condition. When the set time is up, the air conditioner will turn off after receiving a signal from the…
-
6-3-6 Automatic run (SMART) mode
If there is no man-machine communication function after the unit is started, the indoor fan operates at the ultra-low flowrate for 20 seconds before selecting a run mode; the room temperatures are detected during this period for the selection of a run mode. In the first operation: a. When Troom…
-
6-3-6-2 Cooling→heating turnover operation
Cooling→heating: the compressor stops; 50 s later the 4-way valve is activated and 3 minutes more the compressor turns on. Heating→cooling: the compressor stops, 50 s later the 4-way valve is interrupted and 3 minutes more the compressor turns on. 6-3-6-3 There is temperature compensation during the…
-
6-3-8 Heating-run mode
6-3-8-1 Temperature compensation Principle for compensation: The compensation is available only if the proper sensor is used and it is not available when it is subject to the sensor on the remote controller or line controller. 6-3-8-2 Indoor fan The fan speed is set at the high, medium or low fan…
-
6-3-9 Dehumidifying mode
The dehumidifying mode is illustrated as follows: Indoor Ambient Temperature Tset I II III 160C Time Dehumidifying area I: Operation at the frequency in the range (30–80 Hz) according to Δt (Tindoor ambient-T set). f(Hz) Δt(℃) 0 0.5 1 1.5 ≥2 Efficient Dehumidifying area II: The compressor stops for…
-
When being auto, the fan speed is determined in the cooling mode (with
the temperature setting of 240C in default). The high, medium and low fan speeds are same with that in the cooling mode. 6-3-11 Compressor operating state indication When the compressor is in operation, The 3 LED indicator lights on the control panel of the outdoor unit indicates the causes of the…
-
system cannot be started. Normally, when the indoor unit receives a
control signal from the remote controller and emergency button, the system will be started and the beeper will ring two times, and in other cases, the beeper will ring one time. 6-3-12-2 This model can achieve the power interruption restoration function by the selection of the EEPROM data. The power…
-
7-1. Trouble alarm
Indication on the outdoor unit When the compressor is interrupted, the outdoor LEDs are used to indicate the troubles listed below: NOTE:★:ON Sr 0 1 Ο:FLASHING ×:OFF Outdoor Failure Description Normal Outdoor coil temperature sensor in trouble Compressor exhaust temperature sensor in trouble…
-
7-2. Service flow chart
Switch on the power supply Does it receive the Does DLED Yes screen remote display normally? function No Is the Start up self-test signal? No Is Yes controller fuse(F01, Ye s the Check the result remote controller in good No 3.15A/250V) blown? Replace the battery press condition ACL button. Yes…
-
Error code 33
Take out from Indoor temperature CN6 ,Measure the sensor resistance of thermistor Does the resistance of thermistor have the Yes Replace the characteristics indoor pcb board Error code 34 on part 6-3 Take out from CN3 ,Meaure the Indoor Coil sensor trouble No resistance of thermistor Replace Does…
-
Error code 39
Indoor fan motor trouble Set the air conditioner operate in fan mode Is indoor fan motor running? yes no Does the socket CN1(1-3) of indoor control board have power input Does fan motor stop with the remote controller yes no no Indoor control board faulty and replace it yes Replace the indoor fan…
-
Error code 36
Communication trouble Are all the lead wires connected between indoor and outdoor unit? no Connect the indoor and outdoor unit again according to the wiring diagram Display board fault, replace it yes no Is there power output between indoor T/B 1 and 2 AC220V? And "S" of indoor terminal block DC24V?…