HANDBOOK
® P Series Automatic Dual Fuel Burner Fully Modulating Microprocessor MM Mk.6 Controller With EGA PDF MM Mk6 / EGA - Contents Page A.1
-
Contents
IMPORTANT INFORMATION A.4 SAFETY A.4 EMERGENCY INSTRUCTIONS A.4 EUROPEAN BOILER EFFICIENCY DIRECTIVE (B.E.D.) A.4 GENERAL INFORMATION B.1 INTRODUCTION B.2 FEATURES B.2 Burner Designation B.2 Burner Capacity B.2 Fuel B.2 Controls B.2 Operating Mode B.2 SITE CONDITIONS AND SERVICES B.3 Flue and…
-
COMMISSIONING THE BURNER D.3 Entering the Pass Code D.3 Options and Parameters D.3 INITIAL SETTINGS : GAS D.4 DRY RUN : GAS D.4 LIVE RUN : GAS D.5 General D.5 Gas Supply Pressure D.5 Initial Checks D.5 Establishing The Gas Flame D.6 Setting The Gas Pressure Sensor Low Limit D.8 INITIAL SETTINGS…
-
FAULT FINDING E.5 Error Checking, Fault Analysis & Identification Codes E.5 Incorrect Rotation of the Fan Motor E.5 Fan Motor Fails To Start E.5 Fan Motor Starts And Burner Goes To Lockout E.6 Start Flame Failure E.6 Main Gas Flame Is Not Established E.6 Fan Motor Only Runs Continuously E.6 SPARE…
-
GENERAL INFORMATION
P Series General Information Page B.1
-
INTRODUCTION
Fuel This handbook has been produced to enable users to install, commission and use P Series burners safely and efficiently. At each stage the conditions that should be met and the adjustments and other actions which should be carried out are detailed and the locations of the various components and…
-
Modulation By Electro-Mechanical Systems
P Series burners can be supplied with a Landis and Staefa RWF40 modulating controller. This unit is designed specifically for the control of boiler temperature or steam pressure in oil- and gas-fired heating plant. The system comprises a reversible motor that is coupled directly to the cam shaft of…
-
Gas Supply
The pipework, supplying the gas to the burner, must be appropriate to local conditions and must be constructed and installed in compliance with appropriate Codes and Standards. It shall be of sufficient size to satisfy the pressure and volume flow requirements of the burner under all firing…
-
For residual oil burners the pipework should be
insulated, trace heated and thermostatically controlled. Electrical Power Supply A three phase 50 Hz electrical supply is required. Power requirements are listed on the Burner Specification Sheet on Page C.2 Technical Specification. The power supply provided must comply with all relevant Codes and…
-
Air Supply
A floor-mounted fan provides the air supply for the system, although the fan can be suspended for the smaller sizes of burner. The flange on the rectangular outlet is drilled for bolting onto the air damper section of the burner unit. For safety, a wire mesh guards the circular inlet of the fan. The…
-
BURNER DESIGNA
TION CODE ESIGNATION P Series General Information Page B.7
-
OIL HANDLING TEMPERA
TURES AND PRESSURES EMPERATURES Fuel Handling Temperatures (°C) Fuel Class D E F G Viscosity Minimum (Seconds) From Tank 1500 3500 4200 Burner Inlet Fuel Delivery Pressures Atomising Minimum 5 Recommended BURNER MOUNTING DET AIL ETAIL Page B.8 P Series General Information 2 kg/cm psi 0.35 to 0.70 5…
-
TYPIC
AL PUMPED OIL RING MAIN YPICAL P Series General Information Page B.9
-
AMH D:\Local Work\Manuals & Data Sheets\P Series
Burners\PFinal\B_Gen\B_Gen.P65 Revision 100401A Page B.10 P Series General Information
-
TECHNICAL SPECIFICATION
-
BURNER SPECIFIC
ATION SHEET PECIFICA The information contained on this sheet describes the burner as supplied by Nu-way. If the burner is modified after delivery then this sheet should be updated as necessary. Designation : Capacity : Specification No. : Serial No. : Fuel 1 : Fuel 2 : MW Components : Modulation…
-
BURNER AND COMPONENT
IDENTIFIC ATION DENTIFICA Gas Controls The general arrangement of a PDF burner employing Mivcroprocessor MM Mk. 6 modulation is shown in the diagram Burner and Component Identification on Page C.8. An enlarged view of the burner head casing is shown in the diagram on Page C.9. These diagrams are for…
-
designed to provide automatic gas valve proving (leakage test) based on the pressure proving principle (see diagram on Page C.10). The pressure is monitored by a pressure sensor connected to the test space between the main valves. The sensor comes pre-wired as part of the gas train harness. When the…
-
oil valve (normally-closed; for distillate fuel oil) inner gun assembly housing the oil nozzle oil solenoid valve (tip shut-off) motorised spill control valve non-return valve Pumping Set For Class D Fuel The pump unit is free standing and comprises : oil pump motor oil filter(s) air bottle The unit…
-
Oil Nozzle
P Series pressure jet burners use a Fluidics atomizing nozzle as shown in diagram Fluidics Oil Nozzle on Page C.7. The primary function of the nozzle is to spray oil in a suitable pattern into the combustion air stream at a rate commensurate with the appliance’s thermal rating. Oil Solenoid Valve…
-
Data Transfer Interface (DTI)
A further option is the DTI which is a data acquisition system that can collect the operational data from up to 10 MM modules on one site. The data can be transmitted via an RS 232/422 link to a local computer or building management system using the MODBUS protocol. Alternative DTI firmware allows…
-
BURNER AND COMPONENT IDENTIFIC
ATION DENTIFICA Page C.8 P Series MM Mk6 Technical Specification
-
Page C.9
-
GAS CONTROL TRAIN SCHEMA
TIC CHEMATIC Page C.10 P Series MM Mk6 Technical Specification
-
OIL PUMPS
-
DISTILL
ATE OIL CONTROL TRAIN SCHEMA TIC ISTILLA CHEMATIC Page C.12 P Series MM Mk6 Technical Specification
-
RESIDU
AL OIL CONTROL TRAIN SCHEMA TIC ESIDUAL CHEMATIC P Series MM Mk6 Technical Specification Page C.13
-
DISTILL
ATE OIL PUMPING SET ISTILLA Page C.14 P Series MM Mk6 Technical Specification
-
RESIDU
AL OIL PUMPING/HEA TING SET ESIDUAL EATING P Series MM Mk6 Technical Specification Page C.15
-
MK.6 M.M./E.G.A. System Pt. No. MM60001 Combustion Management Systems M.M. STATUS ENTER MEMORY INTER (CHANNEL + ANGULAR POSITION) OUTSIDE TEMP ch. No. POS'N 0.0° CH.1 0.0° CH.2 CH.3 CH.4 CH.5 CH.6 COMPENSATION HIGH FUEL METERING START IBS SEQUENCING OPEN AC DRIVE CLOSE FLAME SCANNER DISPLAY STATUS…
-
TEMPERA
TURE AND PRESSURE DETECTOR EMPERATURE P Series MM Mk6 Technical Specification Page C.17
-
BURNER HEAD
-
ELECTRODE SETTING DET
AIL ETAIL P Series MM Mk6 Technical Specification Page C.19
-
AMH D:\Local Work\Manuals & Data Sheets\P Series
Burners\PFinal\C_Tech\PDF\MMMk6\EGA\C_Tech.P65 Revision 100401A Page C.20 P Series MM Mk6 Technical Specification
-
COMMISSIONING
-
INDIVIDUAL S ETTING R ECORD
- This manual contains commissioning sheets (Pages D.14 and D.15) of essential information that should be completed by the commissioning engineer with individual details of the burner. These details should be verified periodically and changed as adjustments occur. - - S AFETY It is essential that…
-
- - - - Commissioning, operating, emergency shutdown and maintenance instructions for the plant. Establish that the operation of plant other than that being commissioned will not have an adverse effect on the operation of the plant to be commissioned, and similarly, that the operation of the plant…
-
Enter Parameter Mode by pressing the OPEN and CLOSE buttons simultaneously. The Set Parameters screen will appear on the LCD display. On the right of the display is the parameter number and below it the numeric value assigned to that parameter. Initially the value for parameter 1 is displayed. Using…
-
2. 3. 4. 5. 6. 7. 8. 10. 11. 12. 13. Check that the electrical supply to the control panel and burner are turned off. Switch the burner On/Off switch to ‘OFF’ position. Set the Fuel Selector to ‘Gas’. Ensure that the gas manual isolation valve is closed. Check that the gas pipework between the plant…
-
4. 5. 6. 7. 8. 9. Wait for the valve proving cycle to complete. Warning - During this period fuel gas will be admitted to the region between the two shut-off valves, so the system is pressurised. The fan will start. IMMEDIATELY CLOSE the gas isolation valve. Observe that the rotation of the…
-
Press ENTER - the start flame settings are now memorised and the HIGH light will begin to flash. NOTE : The maximum value of the start gas flow rate will be found in the appropriate standard 13. With the burner running at start rate, prepare the controller for transition to high flame by pressing…
-
31. Press ENTER. Wait until the RUN light
flashes. This will take a few minutes as the system carries out the ‘Auto Commission’ routine. 32. Press RUN. 33. Switch off the burner and the electrical power supply to the control panel. Setting The Gas Pressure Sensor Low Limit Carry out this procedure when the appliance controls are calling for…
-
LIVE RUN : OIL
4. General The instructions in this section are presented as a sequence. No separate set of actions (for example, checking the flame signal) should be followed in isolation without paying particular attention to any safety precautions such as isolating the electrical supply to the burner which must…
-
9. 10. 11. 12. 13. Press ENTER. The START light will begin to flash. Set up the positioning motors to the initial ignition positions as follows: Press START. The START light will become steady and the ENTER light will begin to flash. Enter a start position in the CH1 and CH2 windows by using the UP…
-
23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. Check that the combustion is clean. If the CO2 is too low, press MM and slowly increase the fuel valve position by using the CH1 UP button to give the correct CO2. If the CO2 is too high, press MM and slowly increase the air valve position by adjusting the…
-
Remove the pressure measuring equipment. Set-Point Adjustment To enter or edit the controller set-point, which is also known as the ‘Required Value’ (Re), follow the procedure below : 1. Establish the electrical power supply to the control panel. 2. Select the either fuel with the fuel selector…
-
N OTES
-
COMMISSIONING SHEET : GAS
The details below are to to be completed by the Commissioning Engineer. The completed sheet must then be photocopied and a copy forwarded to the appliance manufacturer. Installer's Name : Address : Site Address : Appliance Type : Size : Serial No. : Type : Size : Serial No. : Burner Commissioning…
-
COMMISSIONING SHEET : OIL
The details below are to to be completed by the Commissioning Engineer. The completed sheet must then be photocopied and a copy forwarded to the appliance manufacturer. Installer's Name : Address : Site Address : Appliance Type : Size : Serial No. : Type : Size : Serial No. : Burner Commissioning…
-
AMH D:\Local Work\Manuals & Data Sheets\P Series Burners\P Final
-
OPERATION AND MAINTENANCE
PDF MM Mk6 - Operation And Maintenance Page E.1
-
NORMAL OPERA
TION PERATION Exhaust Gas Analyser End User Operation 1. 2. 3. 4. 5. Establish the electrical power supply to the control panel. Select the required fuel with the fuel selector switch on the control panel. If oil is the selected fuel : Close the manual gas isolation valve Ensure that the oil supply…
-
Establish the electrical supply to the burner and switch on the burner. Allow the burner to proceed through its operating sequence until it is operating on high fire. If the burner has been operating on oil for a prolonged period it may be necessary to purge the gas line of air. ROUTINE SAFETY…
-
ROUTINE MAINTENANCE
ALWAYS SWITCH OFF THE ELECTRICAL POWER AND FUEL SUPPLIES TO THE BURNER BEFORE CARRYING OUT MAINTENANCE. Combustion Air Fan Access the fan blades as follows: 1 Remove the ring of nuts on the air inlet side of the fan unit 2 Remove the plate containing the air inlet. Clean the fan blades with a stiff…
-
Gas Ignition Electrodes
Clean and check the electrodes are not cracked or worn. Renew if necessary. Check the settings of the ignition electrodes and reset if necessary, details are shown on page C.19. Gas Nozzles Carefully clean any deposits from the gas spikes and nozzle inserts. Check nozzle inserts for tightness.…
-
- The gas supply is available The gas supply pressure is high enough to satisfy the low gas pressure switch There are no gas leaks in the control train causing a failure of the valve proving check The appliance controls are calling for heat The fuel selector switch is correctly set If a gas booster…
-
BURNER SERVICE RECORD
PDF MM Mk6 - Operation And Maintenance Page E.7
-
Page E.8
PDF MM Mk6 - Operation And Maintenance
-
NOTES
PDF MM Mk6 - Operation And Maintenance Page E.9
-
AMH D:\Local Work\Manuals & Data Sheets\P Series Burners
\PFinal\E_Oper\PDF\MMMk6\E_Oper.p65 Revision 100401A Page E.10 PDF MM Mk6 - Operation And Maintenance
-
AMH D:\Local Work\Manuals & Data Sheets\P