Инструкция на Наружные водоохлаждаемые блоки VRF-системы V4+ (сервис мануалы)
Наружные блоки системы VRF V4+ с жидкостным охлаждением конденсатора (R410a V4 Plus W 50Hz). Часть 3. Спецификация и производительность. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
Power supply
-
Max. drop between
indoor units MCAC-VTSM-2012-09 m Power wiring mm2 4×10+10(L≤20m); 4×16+10(L≤50m) 4×10+10(L≤20m); 4×16+10(L≤50m) 4×10+10(L≤20m); 4×16+10(L≤50m) Signal wiring mm2 3 core shielded wiring; wiring dia.≥0.75 3 core shielded wiring; wiring dia.≥0.75 3 core shielded wiring; wiring dia.≥0.75 Main unit water…
-
2. Dimensions
2.1 Units Dimension 8HP/10HP/12HP Dimensions (Combinable): (Unit: mm) 3. Piping Diagrams Symbol Description TSC1 Electronic expansion valve Electromagnetic valve TSC2 Pressure relief valve EXVA TSJ Way valve EXVB Filter Pressure sensor ST Pressure Switch Temperature probe SV3 Oil separator T7 SV2…
-
Key Components
Oil Separator: used to separate oil from high pressure & temperature gas refrigerant, which is pumped out from compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon. Low pressure receiver: It is used to store the liquid refrigerant and oil, it…
-
4. Electric Characteristics
Main unit Model Power Supply Compressor OFM Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA MDV-252(8)W/D2RN1(B) 16.2 32 - - / / MDV-280(10)W/D2RN1(B) 16.2 32 - - / / MDV-335(12)W/ D2RN1(B) 18.3 32 - - / / Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps.…
-
5. Electric wiring
5.1 Wiring Diagram For 8,10,12HP 26 Specification & Performance
-
5.2 Terminal base function
Electric control box diagram *Never apply line voltage to communication switching plate and XT2 water flow switch ON/OFF signal input terminal. A XT2 Water flow switch ON/OFF signal input terminal (Must be connected to weak current control circuit !) B C N XT1 Powerline terminal 380-415V 3N~…
-
MCAC-VTSM-2012-09 Signal wire of indoor/main units Signal wire of indoor/main unit adopts 3-core shielded wire (≥0.75mm2) which has polarity, please connect it correctly. Fig.3-1 5.4 Electric wiring of water pipelines 5.4.1 Water flow ON/OFF signal wiring 1) Water flow switch should be wired during…
-
be connected to power terminal of the water pump directly, only should be connected to the control terminal of the water pump stater. 2)When the water pump ON/OFF signal wire has been connected to strong current, it shoud be wired the signal wires along with other strong current wires; when it has…
-
5.5 Example for power wire connection
5.5.1 A water circuit for single system wiring 30 Specification & Performance
-
5.4.2 A water circuit for several systems wiring
Note: 1. The signal connecting line between main units, indoor and main units and indoor units has polarity. When connecting, be careful to prevent error connection. 2 2. Signal line shall adopt three-core shielded wire with an area above 0.75 mm . 3. Do not bind signal line and copper pipe together…
-
5.5 Main unit power wiring
5.3.1 Separate Power Supply (without power facility) 2 Item Model Power supply Minimum Power wire diameter (mm ) Wiring of mental and synthetic resin Size Ground wire Capacity Fuse 1×10 mm 1×10 mm 1×10 mm 4×10 mm (<20 m) 2 4×16 mm (<50 m) MDVS-252(8)W/DRN1 2 MDVS-280(10)W/DRN 380V~415V, 3N, 4×10 mm…
-
facilities. Please select the wire diameter according to the following requirement
4. Diameter of main wire (a) Depends on the total horsepower of main unit and following table. E.g. In system:(8Hp×1unit+8Hp×1unit+10Hp×1unit) Total Hp=26Hp→(Table5.3.3)→size of wire=35mm2(within 50m) 5. Wiring(b):between branch box and power equipment. Depends on the number of combined main unit.…
-
6 Operation Limits
Outdoor temp. Indoor temp. Main unit ambient humidity Cooling mode 0°C ~ 40°C 17°C ~ 32°C below 80% Heating mode 0°C ~ 40°C 15°C ~ 30°C below 80% Notes: 1. If the unit is not running in the above condition, protective device will start and even then the units will produce abnormality running. 2.…
-
6 Capacity Tables
-
8HP heating mode
-
10HP cooling mode
-
10HP heating mode
-
12HP cooling mode
-
12HP heating mode
-
9 Accessories
9.1 Standard accessories No Name Quantity Purpose / 1 Main unit installation manual 1 2 Main unit owner’s manual 1 Be sure to deliver it to the customer 3 Indoor unit owner’s manual 1 Be sure to deliver it to the customer 4 User’s guideline 1 Be sure to deliver it to the customer 5 Bolts bag 1 Stone…
-
10 Functional parts and safety devices
Item Compressor Temperature sensor Symbol Name MDVS-252(8)W/DRN1 MDVS-280(10)W/DRN1 MDVS-335(12)W/DRN1 Inverter Inverter compressor E655DHD-65D2YG E655DHD-65D2YG E655DHD-65D2YG Safety OLP Current protection board MDV-POWER-50A(IR341)-1 CCH Crank case heater DJRD-520A-1500-27.6W TSJ Water inlet temp.…