Инструкция на Наружные водоохлаждаемые блоки VRF-системы V4+ (сервис мануалы)
Наружные блоки системы VRF V4+ с жидкостным охлаждением конденсатора (R410a DC Inverter V4 Plus W 50Hz). Часть 5. Устранение неисправностей. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
Part 5
Troubleshooting 1. Normal Air Conditioner Phenomenon 74 2. Air Conditioner Protection in Common 74 3. Malfunction Code and Troubleshooting 75 Troubleshooting 73
-
1. Normal Air Conditioner Phenomenon
1.1 When main unit appears white vapor or water, the reasons is as follows: 1) The fan of main unit stops to begin defrosting. 2) The electromagnet valve sends out the noise when the defrosting begins and ends. 3) There is sound like water flowing when running or off; and the noise enlarges after…
-
supply switch to cut it off. Before restarting machines, please press the on/off key again as above
3. Malfunction Code and Troubleshooting If there is phenomenon as follows, please stop air conditioner running and cut power supply and refer to the following. However, if the problem insists, please contact the customer service center of Midea commercial air conditioner company, and offer machine’s…
-
MCAC-VTSM-2012-09 40 L9 The setting speed minus the actual speed>15 protection 41 C0 TSJ sensor fault 42 C1 TSC1 sensor fault 43 C2 TSC2 sensor fault 44 C3 Low pressure sensor fault Low pressure Ps≤0.2MPa 45 C4 TSC tem. too high, too low protection C4 protection occur 3 times within 46 C5 TSJ tem.…
-
3.1 "E0": Main unit communication malfunction
Main unit Display E0(Slave unit displays only) Error Explanation If some main units compose a combination, we need to connect the H1,H2,E terminals of main unit correctly. Moreover we should switch master unit to address 0, slave 1 unit to 1, slave 2 unit to 2, slave 3 unit to 3. Address 4 and the…
-
3.2 "E1":Phase sequence malfunction
Main unit Display E1 Error Explanation A, B, C terminal of three-phase power supply correspond with U,V,W of the compressor. The compressor could work normally only when they make good matches. Supposed Causes 1. Phase sequence of the electricity supply does not match. 2. In most circumstance, the…
-
3.3 "E2": Communication failure between master
main unit and IDU Main unit Display E2(Master unit displays only) Error Explanation 1. Timer LED of indoor unit flashes quickly. 2. The number of indoor unit that displayed on main unit changes . 3. Some of the indoor unit do not work, etc. Supposed Causes 1. IDU have the same address or the net…
-
Remarks
1. Press indoor unit’s receiver button for 5 seconds, the indoor unit’s communication address code is displayed; press it for 10 seconds, power code is displayed. Check every unit's address code. Codes are as follows: 80 Director light Running Timer Fan/defend cold fan Warning Code Address Capacity…
-
2. If the signal is weak, a 120Ω resistor should be installed at the end of P and Q line of indoor units, and another 120Ω resistor should be installed at the end of P and Q of main units. Installation refers to the picture following: Troubleshooting 81
-
3.4"E8": Main unit address is wrong
Main unit Display E8 Error Explanation Main unit displays E8. Supposed Causes Main unit is assigned a wrong address. Troubleshooting E8: 82 Main unit address is wrong. Check the main unit's address, which should be less than 3 and not be the same. Chip is defective or installed incorrectly.…
-
3.5"E9": Voltage malfunction
Main unit Display E9 Error Explanation Main unit displays E9. All the main units standby. Supposed Causes 1.The voltage of power supply is too high or too low. 2.The voltage of power supply fluctuates. 3.The IC is loose or main board fails. Troubleshooting Troubleshooting 83
-
3.6"H0": Communication malfunction between
DSP and 780034 Main unit Display H0 Error Explanation DSP IC is used for providing running parameter to compressor. IC780034 send the system's parameter such as T3, T4, main unit power need, exhaust temp. etc. From which DSP IC calculates the compressor's frequency. Supposed Causes 1. The power…
-
3.7H1: Communication malfunction between IC
0537 and IC 780034 Main unit Display H1 Error Explanation For V4 and V3 series, error happens between IC 9177and IC 780034. For V4+W series, error happens between IC 0537 and IC 780034. Supposed Causes 1. IC 9177 or IC 0537 or IC 780034 is defective. 2. Disconnection of the pins of IC 780034. 3.…
-
3.8"H2":Main
MCAC-VTSM-2012-09 unit quantities decreasing malfunction Main unit Display H2(Master unit displays only) Error Explanation Main unit displays H2. All main units are standby. Supposed Causes 1. Main units’ communication lines loose. 2. Some of the main units in combination power off. Troubleshooting…
-
R410a DC Inverter V4 Plus W Series 50Hz "H3": Main unit quantities increasing malfunction Main unit Display H3(Master unit displays only) Error Explanation Main unit displays H3. All main units are standby. Supposed Causes 1. Main unit communication lines loose. 2. Some of the main units in…
-
"H7": Main MCAC-VTSM-2012-09 unit quantities decreasing malfunction Main unit Display H7 Error Explanation Main unit displays H7. All the main units standby. Supposed Causes 1. The communication terminal of IDU is loose. 2. The voltage transformer of IDU is defective. 3. IDU installation is not…
-
3.11"H8": Air discharge sensor error
Main unit Display H8 Error Explanation Discharge sensor broken or wire connection loose. Supposed Causes 1. Discharge sensor broken. 2. Discharge temperature Pc≤0.3MPa Troubleshooting H8 Pc≤0.3MPa Yes Check whether the wire connection is loose Fasten wire connection No Check whether sensor is broken…
-
3.12"P0": The sensor protection on the top of inv
Compressor Main Display unit P0 Error Explanation One MAIN UNIT displays P0 and changes to protecting standby state. Supposed Causes 1. 2. 3. 4. Refrigerant is not enough. Efficiency of outdoor heat exchange is low. Refrigerant does not loops smoothly Control board is defective Troubleshooting 90…
-
P0
System's refrigerant is not enough or system leaks refrigerant. System's refrigerant is not enough. Heat exchanger of IDU is inefficient. Refrigerant evaporates incompletely and flow into compressor at liquid state. Clean the heat exchanger and the filter. Make sure that the air flows through…
-
3.13"P1": High pressure protection
Main Display unit P1 Error Explanation One main unit displays P1 and changes to protecting standby state. Supposed Causes 1. 2. 3. 4. Refrigerant is excess. Refrigerant does not loop smoothly. The refrigerant loop contains air. Control board is defective. Troubleshooting 92 Troubleshooting
-
3.14"P2": Low pressure protection
Main Display unit P2 Error Explanation One main unit displays P2 and changes to protecting standby state. Supposed Causes 1. 2. 3. 4. Refrigerant is not enough. Refrigerant does not loop smoothly. Efficiency of indoor heat exchange is low. Control board is not defective. Troubleshooting Remarks…
-
promptly treated to avoid further damage
3.15"P3": Inv. compressor over current protection Main unit Display P3 Error Explanation Main unit displays P3. Supposed Causes 1. 2. 3. 4. 5. Load on main unit is excess. Main unit heat exchanging is not efficient. Refrigerant is excess. Compressor or its circuit is defective. Control board is…
-
3.16"P4": Discharge temp. sensor protection
Main unit Display P4 Error Explanation One main unit displays P4 and changes to protecting standby state. Supposed Causes 1. Refrigerant is not enough. 2. Refrigerant does not loop smoothly. 3. Compressor needs more oil. 4. Control board is defective Troubleshooting Troubleshooting 95
-
3.17 "P6": Module protection
Main unit Display P6 Error Explanation MAIN UNIT displays P6. Supposed Causes 1. 2. 3. 4. DC generatrix is not lined correctly. DC generatrix low or high voltage protection. MCE malfunction. Compressor’s frequency changes incorrectly. Troubleshooting 96 Troubleshooting
-
1. DC generatrix detection
1.1 Voltage check of DC generatrix 1.2 Check the voltage of DC generatrix, which is normal between 510V and 580V. If less , go to next step. 1.3 Check the rectification circuit. Find out any loose in the circuit. Moreover check the filter board, rectifier stacks. Mind DC and AC switch on the meter…
-
2.1 The voltage between N and P should be 1.41times to local power supply
2.2 The voltage between 1 and 2 should range from 510V to 580V 2.3 The resistance between 1,2,3,4,5 should be infinite. If any of them is about 0, which means the module has already been broken down, we need to replace the module. 3 Compressor's characteristics 3.1 Measure the resistance among the…
-
In normal situation
LED 1: Flash in 1Hz (slowly flash) when standby LED 1: On when running LED 2: Off Phenomenon A LED 2 red ON LED 1 green Flashes 8 times and stops for 1S, then repeat. Error: Inverter module failure Phenomenon B LED 2 red ON LED 1 green Flashes 9 times and stops for 1S, then repeat. Error: Low…
-
3.18"C4" : TSC tem. too high, too low
protection C4 Main unit Display Error Explanation C4 protection occur 3 times within 60 minutes Supposed Causes 1. TSC1 or TSC2 sensor fault. 2. Chip fault. 3. Main board damp. Troubleshooting C4: (Max(Tsc1,Tsc2)>52 or Min(Tsc1,Tsc2)<4℃) Yes The maximum outlet water temperature too high or minimum…
-
3.19"C5": TSJ
Main unit Display tem. too high, too low protection C5 Error Explanation TSJ>50℃ or TSJ<5℃ Supposed Causes 1. TSJ sensor fault. 2. Chip fault. 4. Main board damp. Troubleshooting Troubleshooting 101
-
3.20C7": T5
Main unit Display inverter module tem. high protection C7 Error Explanation T5 inverter module tem. high protection Supposed Causes 1. T5 sensor fault. 2. Chip fault. 5. Main board damp. Troubleshooting 102 Troubleshooting
-
3.21C8": Flow switch break protection
Main unit Display C8 Error Explanation Flow switch break protection Supposed Causes 1. Water flow volume is not enough. 2. Chip fault. 3. Flow switch break Troubleshooting C8:Flow switch break protection Yes Lack of water flow of half the rated flow Check the pump and pipeline whether are blocked…