MCAC-VTSM-2012-09 Precautions ■Be sure only trained and qualified service personnel to install, repair or service the equipment. Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment. If installation is defective, it…
-
Main units installation 2.1 Main unit combination HP Mode Qty. of indoor unit HP Mode 8 8HP×1 13 24 12HP×2 39 10 10HP×1 16 26 8HP×2+10HP 43 12 12HP×1 19 28 10HP×2+8HP 46 16 8HP×2 23 30 10HP×3 50 18 10HP+8HP 29 32 10HP×2+12HP 53 20 10HP+10HP 33 34 12HP×2+10HP 56 22 10HP+12HP 36 36 12HP×3 59 2.2…
-
MCAC-VTSM-2012-09 Hoisting main unit ■It is banned to take wooden cork base as the force bearing point of lifting up the unit during hoisting, the correct method is use the braces or lifting ropes which can bear the unit’s weight and go through the lifting holes of the front and back bottom plates…
-
■Position illustration of screw bolt (Unit: mm)
-
MCAC-VTSM-2012-09 Main units’ placement sequence & master and slave units’ settings A system, which provide with more than two main units, will be set as the followings method: The main units in this system should place sequentially from the large to the small capacity; the largest capacity main…
-
■Installation space of several main units
CAUTION: When install several main units, please reserve the top maintenance space as the single main unit installation. Installation 49
-
MCAC-VTSM-2012-09 Water system installation 3.1 Basic requirements of connection of chilled water pipes CAUTION: ·After the unit is in place, chilled water pipes can be laid. ·The relevant installation regulations should be abided with when conducting connection of water pipes. ·All water pipes must…
-
13) The rated water flow volume of different models are as follow
Model Rated water flow volume(m3/h) 8HP 5.4 10HP 6.0 12HP 7.2 WARNING: ·The water pipes network including water filters and heat exchangers should be periodically cleaned, otherwise, dreg or dirt may seriously damages the heat exchangers and water pipes. ·The installation persons or the users must…
-
Main unit chassis
Main unit chassis Main unit chassis Main unit chassis Drainage port Fig.3-3 WARNING: It is needed to block the water outlet in the side which do not need to be connected with drainage pipes with water outlet plug and seal ring (see Fig.3-3), otherwise the condensed water produced during the system…
-
Main unit side water pipelines connecting figure (Recommended)
Fig.3-4 Direction schematic diagram of water system pipes Fig.3-5 Symbols description Installation Gate valve Thermometer Pressure gage Motorized valve Water flow switch Drainage valve 53
-
As the above Fig.3-5, when horizontal installing the water system main water inlet pipe and main water return pipe, the water inlet branch pipe and water return branch pipe which connected with the unit must be separate connected from the vertically lower direction of main water inlet pipe and main…
-
Fig.3-6
3.6 Operations and maintenance of double-pipe heat exchanger 3.6.1 Operations of double-pipe heat exchanger 1) Please note that correctly install the water inlet and outlet pipes. The thread of water inlet and outlet are inner thread G1-1/4. 2) For the double-pipe heat exchanger is internal thread…
-
3.6.2.1 Preparation of cleaning liquor
1) The material of water side double-pipe is red copper, and for general corrosion situation it is suggested that use the pickle liquor with 5% oxalic acid, 1.2% buffer and 0.8%surfactant, and the temperature should be controlled in 60°C, that will has prefect cleaning effect. 2) If use hydrochloric…
-
handling the water, please make sure with the water dealing person to confirm that use any water scale inhibitor and antiseptic agent etc. will not have corrosion to the stainless steel and copper products. Table.3-1 ITEMS CONCENTRATION (mg/L) Chromaticity ≤15,and cannot display other colors…
-
4 Refrigerant Pipe Engineering
-
Fig.4-1
Fig.4-2 CAUTION: 1. All branch pipes must apply the branch pipes specified by Midea, otherwise, that will cause serious error of the system! 2. Indoor units should be placed as equally as possible at the both sides of the U-shape branch pipe. 3. When the main unit is over 20m from the above places…
-
4.2 Select the Refrigerant Piping Type
Fig.4-3 Table.4-3 Pipe name Code (As per the Fig. 4-2) Main pipe L1 Indoor unit main pipe L2~L9 Indoor unit aux. pipe a, b, c, d, e, f, g, h, i, j Indoor unit branching pipe assembly A, B, C, D, E, F, G, H, I Main unit branching pipe assembly L, M Main unit connective pipe g1, g2, g3, G1 4.3 Size of…
-
final confirm the main pipe diameter isΦ38.1/Φ22.2
-
Table.4-9 Main unit multi-connective pipe assembly
Main unit Qty. Main unit connective pipe diameter Parallel connect with the branching pipes Main pipe 2 units g1, g2: 8, 10HP: Φ25.4/Φ12.7; 12HP: Φ31.8/Φ15.9 L: FQZHW-02N1C 3 units g1, g2, g3: 8, 10HP: Φ25.4/Φ12.7; 12HP: Φ31.8/Φ15.9; G1: Φ38.1/Φ19.1 L+M: FQZHW-03N1C Refer to Table 6-5 for main pipe…
-
pipe diameter areΦ31.8/Φ19.1, take the large one for
your selection, final confirm the main pipe diameter is: gas/liquid pipeΦ38.1/Φ22.2. D Parallel connect the main units 1) The main unit linked by Pipe g1 is 8HP, parallel connects with main unit. the connective pipe diameter to be selected according to its connector size isΦ25.4/Φ12.7;The main unit…
-
CAUTION
1. Pressurized nitrogen(3.9MPa)is used for air tightness test. 2. It is not allow to use oxygen, combustible gas or toxic gas to conduct the air tightness test. 3. When welding, please use wet cloth insulating the low pressure valve for protection. 4. For avoid the equipment be damaged, the pressure…
-
CAUTION
1.Don’t mix up the different refrigerants or abuse the tools and measurements which directly contact with refrigerants 2.Don’t adopt refrigerant gas for air vacuuming. 3. If vacuum level could not get to -0.1MPa, please check whether resulted by leakage and confirm the leakage site. If no leakage…
-
× Wrong Way
MCAC-VTSM-2012-09 Fig.5-9 × Wrong Way Fig.5-10 3) The branching pipe must be installed horizontally, error angle of it should not large than 10°. Otherwise, malfunction will be caused. Fig.5-11 66 Installation
-
5. TRIAL RUN
5.1 Inspection and confirmation before commissioning 1) Check and confirm that refrigeration pipe line and communication wire with indoor and main unit have been connected to the same refrigeration system. Otherwise, operation troubles shall happen. 2) Power voltage is within ±10% of rated voltage.…
-
Fig.6-1
5.4 Caution on refrigerant leakage 1) This air conditioner adopts R410A as refrigerant, which is safe and noncombustible. 2) The room for air conditioner should be big enough that refrigerant leakage can not reach the critical thickness. Besides this, you can take some action on time. 3) Critical…
-
Fig.6-3
Installation 69
-
Commissioning Report for Midea MDV Pro System
Date:dd mm yy Item name: Address: Tel: Supplier: Delivery date: Installation section: Principal: Commissioning section: Principal: dd mm yy Remark: recharged refrigeration quantity to system: kg Name of refrigerant: (R22, R407C, R410A) Installing section: (seal) Commissioning name: (seal) Signature…
-
Test Data for Test Run of __________System
Model of main unit Production series no. Operation data of main unit (Cooling) Unit Run Voltage No.1 No.2 No.3 V Total current of run A Operation current of compressor High-pressure pressure Kg/cm Low-pressure pressure Kg/cm A 2 2 Inlet air temperature C Outlet air temperatureC Operation data of…
-
System parameter
SW1: (CHECK)――Used to query main unit data. Check point sequence and corresponding actuality is as follows: No. Display content Note No. 1 Main unit address 0,1,2,3 14 2 Capacity of main unit 8,10,12 15 3 Qty. of modular main unit 4. Total capacity of main unit 5 Total capacity requirement of indoor…