Product Manual
805 B – 04/11 E Date: November 2004 Supersedes: 805 B – 04/04 D :DWHUFRROHGVFUHZFKLOOHUV :+6;(· &RROLQJFDSDFLW\IURPWRN: +]±5HIULJHUDQW+)&D McQuay is participating in the Eurovent Certification Programme. Product are as listed in the Eurovent Directory of Certified Products and on the web site…
-
New water cooled screw chillers McQuay WHS XE
McQuay International introduces their newest water cooled screw chillers equipped with new single screw compressors. McQuay water cooled WHS chillers equipped with 1 or 2 McQuay screw compressors are a new range of the unit using the Frame 4 single screw compressors. They are manufactured by McQuay…
-
Oil injection is used for these compressors in order to get
high COP at high condensing pressure. WHS units are provided with an high efficiency oil separator to maximise oil extraction. Compressors have a infinitely variable capacity control down to 25% of its total capacity. This control is made by means of capacity slides controlled by microprocessors.…
-
Q = 35,83 X 1 P (kW) X ∆T(°C) N where: Q = Minimum content of the plant expressed in litres P = Cooling capacity of the plant expressed in kW ∆T = Entering/leaving water temperature difference of the evaporator expressed in °C N = Number of compressors. For a more accurate determination of the…
-
Oil differential pressure switch
Compressor thermal Condensation fan Magneto-thermal High Discharge Temperature on the compressor Phase Monitor Star / Delta Transition Failed Low Delta Pressure between Suction and Discharge Low pressure ratio High oil pressure drop Low oil pressure System security Phase monitor Freeze protection…
-
Visualization of their graphics • Display, print-out of the actual alarms • Connection between local and remote computer via telephone line (Modem) MicroTech II C Plus remote control Compatibility with supervisory systems is becoming increasingly important in HVAC. MicroTech II C Plus allows easy…
-
Note: to realize the baseframe consider that the dimensions of the sound proof cabinet are 300 mm longer, 300 mm wider and 200 mm higher than the standard unit. Suction line shut off valve – Suction shut-off valve installed on the suction port of the compressor to facilitate maintenance operation.…
-
Table 1 – Operating limits
WHS 098.1÷272.2 Max evaporator leaving water temperature Min evaporator leaving water temperature (without glycol) Min evaporator leaving water temperature (with glycol) Min evaporator water ∆T Max evaporator water ∆T Max condenser leaving water temperature 15 4 -8 WHS XE operating range 60 Leaving…
-
Table 2 – Evaporator fouling factors
Fouling factors m2°C / kW Cooling capacity correction factor Power input corretion factor COP correction factor 0,0176 0,0440 0,0880 0,1320 1,000 0,978 0,957 0,938 1,000 0,986 0,974 0,962 1,000 0,992 0,983 0,975 Table 3 – Condenser fouling factors Fouling factors m2°C / kW Cooling capacity…
-
Nomenclature
WHS XE 235 . 2 ST 134 WHS Water cooled Screw chiller XE High Efficiency 098÷272 Unit size 1 2 N°of compressors ST Standard version 134 Refrigerant HFC 134a 805 B – 04/11 E – pag. 11/24
-
Physical data WHS XE - HFC 134a
“WHS” Unit size Cooling capacity (1) Power input (1) COP McQuay StargateTM Screw compressor Refrigerant circuits Refrigerant charge HFC 134a Oil charge Min % of capacity reduction Evaporator Evaporators / water volume Max operating pressure Condenser Condensers / water volume Max operating pressure…
-
Electrical data WHS XE - HFC 134a
WHS unit size Standard voltage (1) Nominal unit current (2) Max unit current (3) Max unit inrush current star/delta (4) Max unit current for wires sizing (5) WHS unit size Standard voltage (1) Nominal unit current (2) Max unit current (3) Max unit inrush current star/delta (4) Max unit current for…
-
Sound pressure level WHS XE
WHS Unit size 63 Hz 098.1 118.1 138.1 196.2 218.2 235.2 254.2 272.2 53,6 54,6 56,6 56,6 56,2 56,6 57,1 58,2 -5 Sound pressure level at 1 m from the in free field ( rif. 2 x 10 ) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 56,2 57,2 59,2 59,2 58,8 59,2 59,7 60,8 71,1 72,1 74,1 74,1 73,7 74,1…
-
unit
size WHS 098.1 WHS 118.1 WHS 138.1 WHS 196.2 Evaporator leaving water temp. (°C) Standard ratings WHS XE 098.1 ÷ 196.2 ENTERING CONDENSER WATER TEMPERATURE °C Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power cap. input cap. input cap. input cap. input cap. input…
-
unit
size WHS 218.2 Evaporator leaving water temp. (°C) Standard ratings WHS XE 218.2 ÷ 272.2 Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power cap. input cap. input cap. input cap. input cap. input cap. input cap. input (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)…
-
Evaporator pressure drop
Note: in case of pressure drop higher than 100 kPa, it is necessary to contact the factory. 805 B – 04/11 E – pag. 17/24
-
Condenser (2 passes) pressure drop
Note: in case of pressure drop higher than 100 kPa, it is necessary to contact the factory. Note: in case of pressure drop less than 10 kPa it is necessary install a 4 passes condenser 805 B – 04/11 E – pag. 18/24
-
Condenser (4 passes) pressure drop
Note: in case of pressure drop higher than 100 kPa, it is necessary to contact the factory. 805 B – 04/11 E – pag. 19/24
-
805 B – 04/11 E – pag. 20/24
N.B. McQuay International reserves the right to make changes in design and construction at any time without notice Dimensions WHS XE 098.1 ÷ 138.1
-
805 B – 04/11 E – pag. 21/24
N.B. McQuay International reserves the right to make changes in design and construction at any time without notice Dimensions WHS XE 196.2 ÷ 272.2
-
WHS HF Frame 4 - Technical specifications
To supply and install, where specified in the project n unit(s) water cooled chiller with cooling capacity of kW, to cool l/sec. of water from °C to , condenser entering water temperature ….°C, condenser leaving water temperature ….°C. The unit should work with electricity at V, 3ph, 50Hz. The…
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay partecipa al programma di Certificazione Eurovent. I prodotti interessati figurano nella Guida Eurovent dei Prodotti Certificati. McQuay is participating in the…