Service & maintenance
-
1.0 Installation
1.1 Product description Lindab’s facade system Fasadium is an efficient system designed to handle low air pressures. Typical environments where Fasadium is used include, for example, schools, hospitals and offices. The Fasadium unit is placed at the building façade, preferably under a window sill.…
-
1.5.1 Push-on fittings
Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a pressure test after assembly of the pipe work. Both flow and return pipe is covered by a plastic or rubber protection cover, which…
-
Push-on valve
Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. 1.5.2 Compression fitting Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a…
-
–– The copper insert should be placed inside the pipe on the beam. Always support
the copper pipe coil when inserting the copper insert into position. Mount a compression coupling and/or a valve to the pipe. Don’t stress the nut too much, since this may crush the pipe. Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes.…
-
After removing the protection cover, make sure that the pipe is intact and undamaged, especially at the pipe end. Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburring tool before installation Mount a push-on fitting to…
-
2.0 Commissioning
2.1 Product labeling Fig.1: Label location exterior (water connection) On the label you’ll find: Order: Order identification number. Pos: Order position. Product: Product configuration. Project: Project name. Mark: Marking noted on order. Nozzles: Number of nozzles. Plugs: Number of plugged nozzles.…
-
2.2.2 Calculating the airflow
After measuring the static nozzle pressure, calculate the air flow per nozzle: q=0.0598∙√P q = air flow per nozzle P = static nozzle pressure After finding the air flow per nozzle, find the needed number of open nozzles: q tot/q=n open q tot = total air flow n open = open nozzles Alternatively, read…
-
Changing the airflow Measure the static nozzle pressure Calculate the needed number of nozzles to be plugged, in order to reach the desired airflow at the available air pressure, as see the diagram above. Plug or unplug nozzles to reach the desired air flow. Using the Lindab Fasadium plug-tool…
-
4.0 Product and system specification
4.1 Material data Fasadium 600 Fasadium 700 Fasadium 800 Fasadium 1000 Fasadium 1200 Fasadium 1500 Weight, kg/m, Ø100 duct 9.5 10.5 12.0 14.0 17.0 21.0 Weight, kg/m, Ø160 duct 10.0 11.0 12.5 15.0 18.0 22.0 Weight, kg/m, Ø200 duct 10.5 11.5 13.0 16.0 19.0 23.0 Water content, cooling, l. 0.55 0.66…
-
–– The water should be oxygen free, to prevent corrosion
The water system must be filled with potable water that complies with the “EC directive 98/83/EC”. pH value of water must be between approximately 6-9 pH The water velocities should not exceed 1m/s, and should be kept as close to the nominal flow as possible to minimize noise and optimize the energy…
-