Service & maintenance
-
1.0 Installation
1.1 Product description Lindab’s heating and cooling panels Atrium H and Atrium C can be mounted almost anywhere in the ceiling or on the wall and primarily provide heating/cooling by radiation. The radiation share for the panels exceeds 50% to 60%, compared to approx. 5% for conventional finned…
-
1.4.1 Push-on fittings
Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a pressure test after assembly of the pipe work. Both flow and return pipe is covered by a plastic or rubber protection cover, which…
-
Push-on valve
Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. 1.4.2 Compression fitting Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a…
-
–– The copper insert should be placed inside the pipe on the beam. Always support
the copper pipe coil when inserting the copper insert into position. Mount a compression coupling and/or a valve to the pipe. Don’t stress the nut too much, since this may crush the pipe. Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes.…
-
After removing the protection cover, make sure that the pipe is intact and undamaged, especially at the pipe end. Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburring tool before installation Mount a push-on fitting to…
-
2.0 Commissioning
2.1 Product labeling Atrium H Fig.1: Label location exterior (On insulation, above water connection) Fig.2: Label location interior (Under insulation, above water connection). Atrium C Fig.1: Label location exterior (Under insulation, above water connection) On the label you’ll find: Order: Order…
-
3.0 Maintenance
The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the Atrium beams only need cleaning every 5 years. 3.1 Cleaning instructions Only use lukewarm water and a mild detergent. 4.0 Product and system specification 4.1 Material data Atrium C/H…
-
4.4 Water quality
The water preparation and maintenance for the chilled beam water circuit should be handled by a specialist To prevent corrosion, the water circuit must be airtight The water system must also be equipped with aerators to remove any build-up air in the system. The water should be oxygen free, to…
-