Service & maintenance
-
1.0 Installation
1.1 Product description Lindab’s natural convection beam Capella is the lightest chilled beam available on the market. Capella is mounted on the ceiling and supplies cooling through natural convection and radiation, which results in a draught-free climate. 35% of the cooling supplied by Capella…
-
1.4.1 Push-on fittings
Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a pressure test after assembly of the pipe work. Both flow and return pipe is covered by a plastic or rubber protection cover, which…
-
Push-on valve
Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. 1.4.2 Compression fitting Please ensure that all pipes and fittings are undamaged, as even small dents and scratches potentially pose a risk of leakage in the system. Always remember to do a…
-
–– The copper insert should be placed inside the pipe on the beam. Always support
the copper pipe coil when inserting the copper insert into position. Mount a compression coupling and/or a valve to the pipe. Don’t stress the nut too much, since this may crush the pipe. Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes.…
-
After removing the protection cover, make sure that the pipe is intact and undamaged, especially at the pipe end. Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburring tool before installation Mount a push-on fitting to…
-
2.0 Commissioning
2.1 Product labeling Fig.1: Label location exterior (Above water connection). On the label you’ll find: Order: Order identification number. Pos: Order position. Product: Product configuration. Project: Project name. Mark: Marking noted on order. Nozzles: Number of nozzles. Plugs: Number of plugged…
-
3.0 Maintenance
The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the Capella beams only need cleaning every 5 years. 3.1 Cleaning instructions Only use lukewarm water and a mild detergent. 8 We reserve the right to make changes
-
4.0 Product and system specification
4.1 Material data Capella 17 Capella 17 Capella 53 Weight, kg/m 1.6 3.2 4.8 Water content, l/m 0.25 0.50 0.75 Copper pipes, quality EN 12735-2 EN 12735-2 EN 12735-2 CU-DHP CU-DHP CU-DHP PN10 PN10 PN10 Pressure class 4.2 Environmental declaration Please visit www.lindqst.com 4.3 • Select…
-
The water velocities should not exceed 1m/s, and should be kept as close to the nominal flow as possible to minimize noise and optimize the energy yield There should be used in-line strainers to remove dirt particles from the water. If the water contains any additive inhibitor this must be…
-