User manual
CLIMATIC™ 200/400 - Controller Providing indoor climate comfort MUL28E-0104 09-2006
-
GENERAL DESCRIPTION
This equipment is an electronic device that controls packaged water cooling systems via air and reversible air/water heat pumps. The thermostat allows the following operations: - Unit ON/OFF. - Select system operating mode. - Set point adjustment. - Alarm signal relay. - Display temperature.…
-
THE KEYPAD INCORPORATED AT THE UNIT, MODEL Climatic® 200
READING DISPLAY This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment: - Cooling set point, cooling differential temperature. - Heating set point…
-
THE KEYPAD INCORPORATED AT THE UNIT, MODEL Climatic® 400
READING DISPLAY This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment: - Cooling set point, cooling differential temperature. - Heating set point…
-
THE KEYPAD REMOTE CONTROLLER (OPTION), MODEL RC Climatic® 200
READING DISPLAY This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment: - Cooling set point, cooling differential temperature. - Heating set point…
-
THE KEYPAD REMOTE CONTROLLER (OPTION), MODEL RC Climatic® 400
READING DISPLAY This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment: - Cooling set point, cooling differential temperature. - Heating set point…
-
FUNCTION
UNIT COMMISSIONING When all the instructions in the Operating, Service and Installation Manual have been carried out, the unit can be commissioned as follows: POWER SUPPLY TO THE UNIT - Set the general cut-off switch to ON. TURN ON/OFF THE UNIT - Pressing on off button for more than 2 seconds lets…
-
MENU MODE
Press mode and on off buttons and release within 2 seconds, to enable the user to get to the menu mode mode To move through the menu on this way : on off Press mode and buttons simultaneously and release within 2 seconds. To move through the menu on this way : Press mode and on off buttons…
-
SET POINT THERMOSTAT FUNCTION DESCRIPTION
LEVEL 1 MAIN DISPLAY It shows: Inlet water temperature Active alarms LEVEL 2 SET POINT LEVEL 3 Cooling set point Set point value Heating set point Set point value See page 7, for adjustment of set point of the system. The water temperature is thermostatically controlled via a set point and a…
-
ANALOGUE INPUTS
MAIN DISPLAY It shows: Inlet water temperature Active alarms SET POINT Press Press mode on off Probe status Probe value Probe value Probe value Probe value Probe value mode mode + + on off on off >2" <2" NOTE: When the leds on the display flash alternatively from one to the other, you are on menu…
-
OPTIONS
ON/OFF REMOTE Remove the wire between 93 and 94 terminal block on the electrical box and insert a contact. If the unit stops with ON/OFF Remote, "E00" will appear on the unit display. REMOTE CHANGEOVER SUMMER/WINTER On heat pump units, it is possible to select cooling or heating mode with a remote…
-
OPTIONS
Set point ºC DYNAMIC SET POINT Set point ºC 42ºC heating set point 12ºC 38ºC 9ºC cooling set point 25ºC 35ºC starting differential Dynamic set point -10ºC outdoor temp. ºC outdoor temp. ºC 6ºC starting differential Dynamic set point 6ºC COOLING MODE When the outdoor temperature exceeds 35ºC, the…
-
MODIFY PARAMETERS
MAIN DISPLAY Press mode on off It shows: Inlet water temperature Active alarms Press Press Press mode mode + + on off on off >2" <2" PARAMETERS NOTE: When the leds on the display flash alternatively from one to the other, you are on menu mode. Press mode on off Menu of configuration parameters of…
-
MODIFY UNIT PARAMETERS
MAX: Maximum value for the parameter. MIN: Minimum value for the parameter. DEF: The default value, factory set. UNIT: The units of measure used. VAR.: Minimum variation allowed. DESCRIPTION MIN MAX DEF UNIT VAR. 1 CIRCUIT UNIT MODEL Climatic® 200 Cooling thermal regulator hysteresis 0 25.5 1.5 ºC…
-
OPERATING HOURS
Press mode on off It shows: Inlet water temperature Active alarms Press Press Press Press Compressor 1 operating hours Press Press Compressor 2 operating hours mode Compressor 3 operating hours on off Compressor 4 operating hours OPERATING HOURS mode mode + + on off on off >2" <2" Water pump…
-
MENU STRUCTURE
MAIN DISPLAY It shows: Inlet water temperature Active alarms LEVEL 1 SET POINT Press Probe status Press Press mode on off LEVEL 2 Active alarms Codes ALARMS The unit self-protects through safety devices; when any of these safety devices detect an anomaly, this is shown in the display in order to…
-
VIS
DESCRIPTION E05 Anti-freeze alarm. It indicates the outlet water temperature is lower than +3ºC. After 1 automatic reset, it comes to be a manual reset. E06 Outlet water temperature probe alarm (St2). Outlet water temperature probe open or without connecting. E07 Refrigerant piping temperature probe…
-
VIS
E23 DESCRIPTION EFFECT RE Compressor 1 circuit 2 thermal protection alarm: Compressor 1 - Compressor thermal protection open. circuit 2 MAN - Faulty power supply. stops E24 Fan thermal protection alarm. ACTION Press the ON/OFF button until the alarm disappears; if alarm shows up again, check…
-
DESCRIPTION OF THE DEFROSTING SYSTEM
The defrosting process is activated during heating mode in heat pump units, when the outside temperature is low and the outdoor coil could become frozen. To melt the ice the defrosting function will switch the unit to cooling operation for a short period. During defrosting mode the low pressure is…
-
FAN SPEED CONTROL (only for 0091 to 0812 units)
Fan speed control: Management of the fan speed It is managed by a fan speed control printed plate located at the electrical box of the unit. The function of the fan speed control is to prevent very low condensing temperatures during cooling mode operation between 0ºC and 46ºC outside temperatures.…
-
SAFETY DEVICES
The units contain various safety devices to avoid damage to the unit due to very low water temperatures. 1.- Anti-freeze protection. This protection is activated by the control of the unit when the outlet water temperature probe (St2), located inside the water exchanger, measures +5ºC and…
-
www.lennoxeurope.com
BELGIUM, LUXEMBOURG www.lennoxbelgium.com RUSSIA www.lennoxrussia.com Due to Lennox’s ongoing commitment to quality, the Specifications, Ratings and Dimensions are subject to change without notice and without incurring liability. CZECH REPUBLIC www.lennoxczech.com SLOVAKIA www.lennoxdistribution.com…