SERVIC E——nrormation LE; "АИ, Lil OX industries Inc. Form No. CORP. 7916-L8 Litho U.S.A HONEYWELL SINGLE ZONE SOLID STATE CONTROL SYSTEM USED ON CHA11, CHP11 AND GCS11 UNITS | - INTRODUCTION The “‘Honeywell’’ Single Zone Solid State Control System is being incorporated into the CHA11, CHP11 and…
-
ture. The discharge sensor, located in the unit discharge air
stream, monitors the machine’s output. In simple terminology, the Honeywell control system compares the space demand to the machine's output and then logically cycles the unit to satisfy the demand with minimum energy consumption. If the unit includes the power saver option, the control system…
-
SETPOINT
ON OFF H3 ON OFF H2 ON OFF HOT WATER| ~~ H1 OPEN CLOSED | [~~~ DC VOLTS | | on oe | | |“ 1 | у о | 4F oF 2 VF + +2 | | | RAMP CHART 2F VF й , SETPOINT OFF ON сз OFF ОМ OFF ON | c1 *K23 is used on CHA and GCS applications using power OFF ON saver and switching subbase K23* or switching status panel.…
-
CONTROL OPTION CHART
START « REMOTE SETPOINT ROOM MITER ROOM THERMOSTAT Г < CONTROL > ] REMOTE SETPOINT YY ROOM TRANSMITTER THERMOSTAT 25651 25652 RETURN AIR ROOM ‘TEMPERATURE TEMPERATURE SENSOR MO SENSOR MP. | SENSOR у RETURN AIR ROOM TEMPERATURE TEMPERATURE SENSOR 27C40 SENSOR 58C92 SSP11 STANDARD SUBBASE PTUs PANE…
-
Run separate harnesses for АС and DC currents. AC voltage interferes with DC signals
CONDUIT BOX (NOT FURNISHED) STANDARD ._NON-SWITCHING А SUBBASE FIGURE 7 2-Thermostat output consists of two voltage ramp signals, one for heating and one for cooling. A change in the thermistor resistance causes the thermostat to generate a DC ramp signal which is proportional to the temperature…
-
at a central station where the set point settings will not
be subject to unauthorized adjustment. 3 - The transmitter also mounts on a 2 x 4 inch handy box as shown in Figure 8. If an optional switching subbase is used, identify the 2 tow voltage AC wires at transmitter. These wires connect to fan switch option and wire to subbase terminals 9 and 10. On…
-
SP11 STATUS PANEL SSP11 SWITCHING STATUS PANEL
© 8 AUTO (Ф) cool Mode COc00! Mode HEAT ищу COOL ‘OFF. —ЕМ HEAT @ Hest Mode В тв УМ @ Compressor 1 (О) сотриевзог 1 auto @) compressor 2 © compressor 2 FA Ny О ® № Heat O № Heat eg, men @xenwox S OLennox FIGURE 12 FIGURE 13 2 - The “Cool Mode” LED is green when lit. It indicates Power 8 - The ‘After…
-
LOGIC PANEL
1 - DIRECTION OF MOTOR TRAVEL AS VIEWED FROM POWER END. 2-WHEN MOTOR IS POWERED, BRAKE HOLDS MOTOR POSI- TION AGAINST SPRING RETURN ACTION [ ‘TR TR) wees © TRIAC SWITCHING | OPEN LIMIT SA! = NJ <) > ЕН MAX. @ be {ay} ё # is (8) fer) Iman EB = ‘CCW WINDING О MINIMUM POSITIONER a Aw N.C. N.O. Е (5)…
-
MINIMUM POSITION
ADJUSTMENT MINIMUM POSITIONER ROTATE SCREW CLOCKWISE TO OPEN OUTSIDE DAMPER OR COUNTERCLOCKWISE TO CLOSE DAMPERS ~~ FIGURE 16 D - Enthalpy Control The enthalpy control senses the heat content of the air. If heat content rises above control setpoint, the Power saver dampers drive to minimum position.…
-
The outdoor dampers are held closed during cooling setup
The blower cycles with demand from “C1” on logic panel. Mechanical cooling is used to satisfy the demand. If cooling lockout is chosen, the equipment is shut down and the outdoor air dampers are held closed. The degree of heating setback or cooling setup is determined by separate resistors at the…
-
MINIMUM POSITION
@HEATING. @ COOLING DEMAND AND OUTSIDE AIR TEMPERATURE ABOVE ENTHALPY CONTROL SETTING. @ COOLING DEMAND WITH DISCHARGE TEMPERATURE BELOW 50°F. a OuTSIDE| | \ DAMPER | |\ 5-5-2 POWER SAVER $ MOTOR RETURN AIR DAMPER OPEN POSITION @ COOLING DEMAND AND OUTSIDE AIR TEMPERATURE BELOW ENTHALPY CONTROL…
-
Vill - TROUBLESHOOTING
Before checking out this solid state control system, make sure that all other components affecting system operation are working properly. Refer to the troubleshooting section in the unit service manual. Be extremely careful when making checks on a solid state control system. Do not mix the different…
-
4 - Meter reading depends on the temperature at the sensor
Discharge sensor resistance should be betweem 1500 to 4500 ohms. For resistance readings at different temperatures, see Figure 23. [sy = DISCHARGE SENSOR [ony HEAT tommy CHECKOUT ны Dae teed amet эк CHECK RESISTANCE FROM “‘T” Jared ae bed TERMINAL TO “Ti” LEAD pm coat py (ede! нЕ OHM METER a ВЕЛИ ig…
-
LOGIC PANEL RELAY SEQUENCE
FOR HEATING CHECK LOGIC PANEL OHM ~ ie) METER pe ee Г | 1+1 lap | нат 3600.5 REMOVE LEADS AT SWITCHES Dard ed Melaed AND USE AN OHM METER TO CHECK CONTINUITY ACROSS гро 1—1 СОМТАСТ$ ie saletall НН] ао тт THERMOSTAT ВЕС... 0, 0 SIMULATOR | pun 5 BLUE || у ВЕБ APPLY 24\ AC BLACK TO “TR” WHITE…
-
5 - If wiring is correct and motor does not operate, check the
unit service manual for valve motor checkout. 6 - Slowly turn heat/cool knob counter-clockwise to simulate a decreasing heating demand. The motor should close. Power Saver Checkout (Voltmeter) 1 - Disconnect the power saver lead to terminal W on the logic panel and connect simulator as shown in…
-
Е - Power Saver Motor
1 - Remove wires from terminals В, W and В on motor. 2 - Apply 24 VAC to “TR” terminals at motor. 3 - Connect jumper wire to terminals В and W as shown in Figure 31. Outside dampers should drive closed. 4 - Now connect jumper wire to terminals В and В. Outside dampers should open. CONNECT JUMPER…