CSS EASY CSS KSR DIGITAL GB CSS EASY CSS Leister Process Technologies Galileo-Strasse 10 CH-6056 Kaegiswil/Switzerland Tel. +41-41662 74 74 Fax +41-41662 74 16 www.leister.com sales@leister.com KSR DIGITAL
-
Operating Instructions
GB Please read operating instructions carefully before use and keep for further reference. Leister CSS EASY / CSS / KSR DIGITAL Temperature controller SOFTWARE-VERSION 3.10 Issue operating instructions 05.2008 Warning Danger! When opening up the tool, live components and connections are exposed. The…
-
INSTALLATION
TECHNICAL SPECIFICATIONS Dimensions and cut-out; panel mounting Display 2 x 4 digits, 7-segment-LED display, green, height 10 and 7mm Keys 4 mechanical keys (Man/Aut, INC, DEC, F) Accuracy 0.2% full scale ± 1 digit at 25°C room temperature Main input (settable digital filter) TC, RTD, PTC, NTC…
-
CSS EASY
-
DESCRIPTION OF FACEPLATE
Function indicator Indicates modes of operation L1 L2 L3 Indication of output states OUT 1 (AL 1); OUT 2 (Main); OUT 3 (AL 2); OUT 4 MAN/AUTO = OFF (automatic control) ON (manual control) SET SETPONT1/2 = OFF (IN1 = OFF - local Setpoint 1) ON (IN1 = ON - local Setpoint 2) SELFTUNING = ON (enabled…
-
Information menu
INF Informationsmenu SoftwareVersion Default: 3.10 Error display Default: 4 0 No Error 1 Lo 2 Hi 3 ERR 4 SBR +8 error OUT2 card recognition +16 error OUT3 card recognition Configuration hrd Default: 213 CFG menu CFG Default: 0 Regelparameter Enabling self-tuning, autotuning, softstart S.tun…
-
InP Menu
InP Input settings Def. remote setpoint Default: 0 Val. Type of remote setpoint 0 Digital (from serial line) 1 Digital (from serial line) Absolute Relative Absolute Reletive to local setpoint Digital filter on input (if = 0 excludes averaging filter on sample value) 0.0 20.0 s Default: 0.1 +2 set…
-
Out Menu
Out Default: 0 Default: 0 Output settings Select reference signal for alarm 1 Select reference signal for alarm 2 AL.1.r, AL.2.r AL.x.r Variable to be compared PV (Process variable) SSP (active setpoint) PV (process variable) Reference setpoint AL AL (only absolute) AL (only relative and referred to…
-
Hrd menu
Hrd Hardware configuration Val Default: 0 Enable multiset instrument control by serial Control type Default: Val Multiset (2 SP) Reversed LED state Instrument control by serial x x x x x x x x x x x x Control type P heat P cool P heat / cool PI heat PI cool PI heat / cool PID heat PID cool PID heat…
-
U.CAL menu
U.CA User calibration Default: 0 (1) (2) Val Function Analogue output (1) Input 1 – custom 10V / 20mA Input 1 - custom 60mV Custom PT100 / J PT100 Custom PTC Custom NTC Input 2 - custom TA (2) The analog output in 20mA is calibrated with accuracy higher than 0.2 % f.s.; calibrate when converting to…
-
CONTROL ACTIONS
Proportional Action: action in which contribution to output is proportional to deviation at input (deviation = difference between controlled variable and setpoint). Derivative Action: action in which contribution to output is proportional to rate of variation input deviation. Integral Action: action…
-