Инструкция на Промывные фильтры Grunbeck серии pureliQ:RX, pureliQ:RDX
Модели: pureliQ:RX, pureliQ:RDX. Руководство по эксплуатации промывных фильтров (RDX — с редуктором давления): описание, монтаж, ввод в эксплуатацию, настройка редуктора давления, промывка, техническое обслуживание, неисправности, технические данные. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
We understand water
© cliQlock Backwash filter | pureliQ:RX, pureliQ:RDX Operation manual grunbeck
-
Central Contact
-
Introduction This manual is intended for owners/operators/operating companies and qualified specialists and ensures the safe and efficient handling of the product. The manual is an integral part of the product. ● Carefully read this manual and the component instructions contained therein before you…
-
Validity of the manual This manual applies to following products: ● Backwash filter pureliQ:RX (Order no. 101000030000) ● Backwash filter pureliQ:RDX (Order no. 101000040000) 1.2 Other applicable documents In the interests of sustainability, we provide the product data sheet, checklists and these…
-
Product identification You can identify your product based on the product designation and the order number on the type plate. ► Check whether the products indicated in chapter 1.1 correspond to your product. The type plate is located on the side of the filter. Designation Designation 1 DVGW test…
-
Symbols used Symbol Meaning Danger and risk Important information or prerequisite Useful information or tip Written documentation required Reference to further documents Work that must only be carried out by qualified specialists Work that must only be carried out by qualified electricians Work that…
-
Warning sign and
signal word DANGER Personal injury Death or serious injuries WARNING Possible death or serious injuries CAUTION Possible moderate or minor injuries NOTE 1.6 Consequences if the information/instructions are ignored Damage to property Possible damage to components, the product and/or its functions or…
-
SAFETY
2 Safety 2.1 Safety measures ● Only operate your product if all components are installed properly. ● Obey the local regulations on drinking water protection, accident prevention and occupational safety. ● Do not make any changes, alterations or extensions on your product. ● Only use genuine spare…
-
SAFETY
2.2 Product-specific safety instructions WARNING Excessive contamination of the filter element ● Risk of infection due to contamination ► Comply with the intervals and recommendations for inspection and maintenance of the filter. ► Do not unlock the cliQlock module system under pressure. Ensure that…
-
Product description 3.1 Intended use ● The backwash filters pureliQ:RX and pureliQ:RDX are designed for the filtration of drinking water. ● The filters are designed according to the stipulations of DIN EN 13443-1 and DIN 19628 and are intended for installation into the drinking water system…
-
Product components BA_100263049900_en_045_pureliQ_RX-RDX.docx Designation Designation Slip-on coupling for cliQlock basic module Maintenance ring with month indicator 5 Inspection window 6 Backwash handwheel 7 Adapter for drain connection 3 Pressure reducer handwheel 8 Hose adapter 4 Pressure gauge…
-
Functional description The unfiltered drinking water flows into the filter through the inlet side and from the outside in through the filter element and to the pure water outlet. Thus, foreign particles of a size > 100 µm are retained. Depending on their size and weight, foreign particles stick to…
-
TRANSPORT AND STORAGE
4 Transport and storage 4.1 Transport ► Transport the product in its original packaging only. ► Obey the symbols and instructions on the packaging. 4.2 Storage ► Store the product protected from the following effects: • Dampness, moisture • Environmental impacts such as wind, rain, snow, etc. •…
-
Installation The installation of the product represents a major intervention into the drinking water system and must be carried out by a qualified specialist only. In accordance with DIN EN 806-2 and DIN EN 1717, the product is installed in the cold water pipe downstream of the water meter and…
-
Installation example in vertical pipe
Designation Designation 1 Inlet shut-off valve 4 Shut-off valve output 2 cliQlock basic module 5 3 Leakage protection protectliQ:B Drain connection DN 50 according to DIN EN 1717 17 | 52
-
Requirements for the installation site Observe the local installation directives, general guidelines and technical specifications. ● Protection from frost, severe heat exposure and direct sunlight ● Protection from chemicals, dyes, solvents and their vapours ● Ambient temperature and radiation…
-
Checking the scope of supply Depending on your order, you will receive the backwash filter pureliQ:RX or the pureliQ:RDX backwash filter with pressure reducer. The cliQlock basic module is not included in the scope of delivery. Designation 1 Backwash filter pureliQ:RX 2 Backwash filter pureliQ:RDX…
-
Water installation The cliQlock basic module must already be installed. The filter can be mounted in a horizontal or vertical pipe. When removing the filter, the plug-in coupling can get stuck in the cliQlock basic module. ► When removing the filter, pay attention to the plug coupling in the…
-
► Note the nominal connection diameter (DN) of the cliQlock basic module
on the type plate. 21 | 52
-
Attaching the backwash connection If it is not possible to install a waste water pipe, the backwash water can be collected in a bucket/container. 5.4.1 Backwash water discharge with drain connection Designation 1 Drain connection DN 50 according to DIN EN 1717 Designation 2 Waste water pipe on site…
-
Backwash water discharge with hose connection 1. Mount the hose adapter on the filter. The hose is not included in the scope of supply. The hose length must not exceed 4 metres. Longer hoses can lead to pressure loss and impair backwash. NOTE Stagnated water can remain in the hose due to…
-
2. Connect an on-site hose to the hose adapter and to the installed drain
connection. 24 | 52
-
Alternative discharge of the backwash water
1. Connect an on-site hose to the hose adapter. 2. Lay the hose to the discharge point (e.g. bucket, drain or floor outlet). BA_100263049900_en_045_pureliQ_RX-RDX.docx ► Make sure that there is a free outlet for the backwash water at the discharge point. 25 | 52
-
Commissioning The initial start-up of the product must be carried out by technical service personnel only. 6.1 Checking the product 2. Open the nearest water withdrawal point downstream of the filter as far as it will go. » The filter is vented. 3. Check the filter for leaks. 4. Enter the initial…
-
Setting the month display BA_100263049900_en_045_pureliQ_RX-RDX.docx Via Grünbeck’s myProduct app, you will receive a message about the timely backwash of the filter (refer to chapter 7.1). ► Set the maintenance ring to the month of the next maintenance (alternatively, to the month of the next…
-
Setting the pressure reducer (pureliQ:RDX) The pressure reducer is factory-set to 4 bar. You can change this value as follows: 1. Set the desired downstream pressure on the pressure reducer handwheel (turn anticlockwise = pressure increase, turn clockwise = pressure reduction). 2. Open and close a…
-
Handing over the product to the owner/operator/operating company ● Explain how the product works to the owner/operator/operating company. ● Use the manual to brief the owner/operator/operating company and answer their questions. ● Inform the owner/operator/operating company regarding the need for…
-
OPERATION/HANDLING
7 Operation/handling The product is operated automatically and does not require any manual operation. CAUTION Unlock the cliQlock module system under pressure ● Bumping, hitting through filter ► Shut off the water supply before operating the cliQlock module system. ► Ensure that the cliQlock module…
-
Maintenance and repair Maintenance and repair includes the cleaning, inspection and maintenance of the product. The responsibility for inspection and maintenance is subject to local and national requirements. The owner/operator/operating company is responsible for compliance with the prescribed…
-
Intervals Regular work is necessary in order to ensure proper functioning of the product in the long term. DIN EN 806-5 recommends regular maintenance to ensure trouble-free and hygienic operation of the product. ► As owner/operator/operating company determine which components must be inspected and…
-
Inspection You as owner/operator/operating company can carry out the regular inspections yourself. ► Conduct an inspection at least every 2 months. 1. Check the installation for leaks and function. BA_100263049900_en_045_pureliQ_RX-RDX.docx 2. Read the static pressure (zero flow) of pureliQ:RDX. 3.…
-
Semi-annual maintenance 8.4.1.1 Filter backwash During the backwash process, filtered pure water is still available. We recommend repeating the backwash process 3 times. Backwash via hose connection NOTE Stagnated water can remain in the hose due to insufficient slope. ● Bacterial growth in the…
-
1. Turn the backwash handwheel to the left in the direction of the arrow as
far as it will go. 2. Hold the backwash handwheel in this position for 5 – 10 seconds. 3. Turn the backwash handwheel to the right back to its initial position. 35 | 52
-
4. Check the water pressure of the pureliQ:RDX
a Fully open a water withdrawal point and read the flow pressure on the pressure gauge. b Close the water withdrawal point and read the static pressure (zero flow) on the pressure gauge. c Adjust the holding pressure if required. 6. Confirm the backwash in the Grünbeck myProduct app, if registered.…
-
Annual maintenance The work below must be carried out by a qualified specialist only. If a leak or malfunction is detected, conduct a wear test in addition to the semi-annual maintenance: 1. Detach the drain connection from the filter. BA_100263049900_en_045_pureliQ_RX-RDX.docx 2. Check the tight…
-
4. Close the shut-off valves at the inlet and outlet
6. Dismantle the drain connection or the hose adapter (if fitted). ► If the connection point is leaking, proceed as follows. 38 | 52 BA_100263049900_en_045_pureliQ_RX-RDX.docx 5. Carry out a backwash to relieve the water pressure in the filter and in the water pipe.
-
7. Detach the filter from the cliQlock basic module
a Pull out the cliQlock clip. b Carefully pull the filter out. 8. Check the O-rings on the plug-in coupling for wear. BA_100263049900_en_045_pureliQ_RX-RDX.docx 9. Check the cliQlock clip and the cliQlock basic module for cracks and warping. Designation 1 2 Flat seals for the water meter screw…
-
10. If necessary, dismantle the cliQlock basic module and check the seals
on the water meter screw connections for wear. 11. Check the non-return valve for wear. 12. Check the blind plug with O-ring for wear. Designation Designation 1 Filter bell cover 5 Backwash valve incl. seal 2 Backwash handwheel 6 Filter cylinder 3 Fastening nut incl. seal 7 Filter element 4 Spring…
-
15. Unscrew the filter cylinder
16. Check the O-rings and flat seals for wear and tear. 17. Check the spring assembly and backwash valve for smooth running and damage. 18. Check the filter element for damage and dirt deposits. 19. Replace worn components (refer to chapter 8.7). 20. Mount the filter and put the installation into…
-
Service Kits 8.7.1 Service kits for pureliQ:RX 4 Backwash valve incl. seals 2 O-ring filter cylinder 5 Spring assembly 3 Filter cylinder 6 Fastening nut incl. seal Designation Consisting of Order no. Service kit I • Filter element 100 µm incl. seal • O-ring filter cylinder • Backwash valve incl.…
-
Service kits for pureliQ:RDX BA_100263049900_en_045_pureliQ_RX-RDX.docx Designation Designation 1 Filter element 5 Spring assembly 2 O-ring filter cylinder 6 Fastening nut incl. seal 3 Filter cylinder 7 Pressure reducer 4 Backwash valve incl. seals 8 Pressure gauge Designation Consisting of Order…
-
ERROR
9 Error WARNING Contaminated drinking water due to stagnation ● Infection ► Have faults remedied immediately. 44 | 52 Observations Observation Explanation Remedy Water pressure at the withdrawal point too low (pressure loss too high) The shut-off valves are not fully open ► Fully open the shut-off…
-
ERROR
Observation Explanation Remedy Water loss in the system (leakage) Faulty joint ► Check O-rings and seals for deformations or wear and tear ► Check filter head for damage ► Check cliQlock basic module checked for damage ► Have leaky components replaced by a qualified specialist If an error cannot be…
-
DECOMMISSIONING
10 Decommissioning It is not necessary to take your product out of operation. In case of longer absences, e.g. holidays, precautionary hygiene measures according to VDI 3810-2 and VDI 6023-2 must be taken in order to maintain drinking water hygiene after downtimes. 10.1 Temporary standstill ►…
-
Dismantling and disposal 11.1 Dismantling The work described herein represents an intervention into your drinking water system. ► Have this work performed by qualified specialists only. 1. Close the shut-off valves upstream from the filter. 2. Open a water withdrawal point and wait for a few…
-
1. Pull the plug-in coupling out of the cliQlock basic module by hand - do
not use any tools. BA_100263049900_en_045_pureliQ_RX-RDX.docx 2. Insert the plug-in coupling into the filter connection as far as it will go. 48 | 52
-
11.2 Disposal
► Comply with the applicable national regulations. Packaging ► Dispose of the packaging in an environmentally sound manner. NOTE Danger to the environment due to incorrect disposal ● Packaging materials are valuable raw materials that can be reused in many cases. ● Incorrect disposal can cause…
-
Publisher's information
Technical documentation If you have any questions or suggestions regarding this operation manual, please contact the Technical Documentation Department at Grünbeck AG Email: dokumentation@gruenbeck.de
-
Grünbeck AG
Josef-Grünbeck-Str. 1 89420 Hoechstaedt Germany +49 9074 41-0 info@gruenbeck.com For more information, go to www.gruenbeck.com
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.