Инструкция на Тепловые насосы воздух-вода General Waterstage серии High Power: WO*G112LBT, WO*G140LBT, WS*G140DB6. Руководство по сервисному обслуживанию.
Смотрите также: Руководство по монтажу →
Загружаем документ…
Текст инструкции
-
Waterstage 3 phase
Document 1394-1 ~ 29/01/2010 FR NL DE EN IT Air/Water Heat Pump Split System, Single Service 3 phase 112, 140 and 160 Maintenance Document Intended for professional use Fujitsu General (Euro) GmbH Werftstrasse 20 40549 Düsseldorf - Germany Subject to change without notice Non contractual document…
-
Technical Characteristics 1.1 Specifications WATERSTAGE 112 °C WATERSTAGE 140 -20/+35 °C °C °C Heating system operating limits Exterior temp mini/maxi Initial max heating water temperature - Floor heating system - Low temperature radiator Flow min heating water temperature 1.2 WATERSTAGE 160…
-
1.2.3 Performance Curves for Waterstage 112
1.2.4 Performance Curves for Waterstage 140 Maintenance Document 1394-1 7
-
1.2.5 Performance Curves for Waterstage 160
1.3 Hydraulic Characteristics HEAT PUMP Connection diameter Exchanger tank volume (L) Expansion vessel volume (L) Max pressure water circuit (Bar) Max flow rate (l/h) Min flow rate (l/h) Min Delta T (°C) Max Delta T (°C) 8 WATERSTAGE 112 2400 1200 WATERSTAGE WATERSTAGE 140 160 1’’ – 25.4 mm (male)…
-
Refrigeration Diagram Outdoor Unit Hydraulic Unit Expansion vessel Circulation pump THHO Pressure check valve Strainer 4- Way valve THO Accumulator Heat exchanger THHM Hot water column sensor Air bleeding valve Pressure sensor Auxiliary heater THD Injection expansion valve THC Strainer Expansion…
-
2 Installation Rules
2.1 Heat Pump 2.1.1 Outdoor Units In snowy areas: raise the outdoor unit by a height equal to the maximum height of snow cover plus 20cm. 10 Maintenance Document 1394-1
-
2.1.2 Hydraulic Unit
Minimum clearance dimensions must be provided around the appliance as shown on the drawing, to enable the machine to be serviced. The Hydraulic Unit should be installed in such a way that the distance between the module and the outdoor unit is within the authorized range. Maintenance Document 1394-1…
-
Control Terminal 2.2.1 Room Unit The room thermostat gives the user access to the following basic functions: • Adjustment of the room temperature setting by simply turning the knob • Selection of the heating mode • Switching to comfort temperatures by simply actuating the occupancy switch. In…
-
Select heating mode
Auto mode : The temperature is controlled automatically: - Heating mode according to time program - Automatic summer/winter changeover Adjust comfort setpoint temperature The comfort setpoint is adjusted directly by turning the knob, the value must be confirmed with the OK key. Adjustment of the…
-
Electrical Connections 2.3.1 Installation Precautions All machines in the ATW Split System Inverter range are designed to operate at 3x400V 50Hz. Power supplies must be compliant with NFC 15-100. The power supply contract must be able to cover not only the power of the unit but also the sum of…
-
Hydraulic Unit Connection
Outdoor Unit Connection The wiring of all Waterstage outdoor units is as follows: Maintenance Document 1394-1 15
-
2.3.3 Hydraulic Unit Connection Diagram
* If the control device does not provide a potential-free contact, the contact must be relayed to create equivalent wiring. In all cases, please refer to the instruction manuals for the external components (load limiting device, power meters) to create the wiring. If several fault inputs are…
-
3 Getting Started
3.1 Checks 3.1.1 Outdoor Unit • Unit is secured to a stable surface • Unit is raised in regions of regular snowfall • Distances to potential obstacles or hazards are maintained • A condensate drain line is connected 3.1.2 Hydraulic Unit • Unit is secured to a stable surface • There is enough space…
-
Settings Depending on their associated functions, the control settings are not accessed at the same level. There are 4 levels of access: U: end-user level I: commissioning level (installer start-up) S: engineer level (specialist) C: OEM level (manufacturer) To get to the level of access desired: •…
-
Heating Curves
70 2 Heating Flow Temperature (°C) 60 1,75 1,5 1,25 50 1 0,75 40 0,5 30 20 20,0 0,25 15,0 10,0 5,0 0,0 -5,0 -10,0 -15,0 -20,0 Outdoor Temperature (°C) Graph 1: Heating Curves The heating curves shown above refer to a 20°C room temperature setpoint. The heating curve slope (setting 720) determines…
-
3.3.2 Auto Adapt Adjustment
When this function has been activated (setting 726) the heating curve is automatically adjusted, and therefore, there is no need to change the slope or offset of the heating curve. In order for the auto adapt feature to be operational: • a room sensor must be connected • the room influence parameter…
-
3.5.1 Principle of Operation
DHW production starts when the temperature inside the tank is 7°C less than the setpoint temperature. The setpoint can be either a "reduced" or a "nominal" setpoint, depending on time program 4. During the programmed time periods it is the nominal setpoint which is active, and outside of these…
-
3.6.2 Output Test Mode
LINE 7700 OUTPUT WATERSTAGE QX23 (1) Circuit 1 heating pump or swimming pool selection valve QX21 (1) Open mixing valve 1 QX22 (1) Close mixing valve 1 QX1 QX2 DHW heating circuiting pump (if connected) QX3 Circuit 2 heating pump QX4 DHW selection valve QX5 Boiler selection valve (or heater 1) QX6…
-
4 Faults
4.1 Fault List 4.1.1 Hydraulic Unit Fault Faults which occur on the Hydraulic Unit are shown by the symbol . Press the info key for details on the cause of the fault. The following information is displayed: • Description of the error • Location of the error (sensor or contact) • Reset. Depending on…
-
stopped. For example, a safety thermostat on the
heating floor can be wired to input Ex6 (E20) to avoid excessively high temperatures in the floor. Heat pump connecting blocks … X5 X6 X7 X8 … Faults external to the heat pump Any safety device (e.g. thermostat pressure switch) wired to input Ex6 (E20) allows external problems to be reported and the…
-
4.1.2 Outdoor Unit Fault
When the system is switched back on after a power outage, the Hydraulic Unit may display fault 370 for a few tens of seconds. This is not a serious problem. It simply means that the outdoor unit is running its tests. Once the tests have been completed, the fault should disappear. If it doesn't, if a…
-
Outdoor Unit Clearing This section describes the techniques which can be used to identify the failure. 4.2.1 Failures with Error Code Clear 1: Serial reverse transfer error Hydraulic Unit LED: Green 1 flash / Red 1 flash Outdoor Unit LED: Off Probable causes: • Misconnection. • External cause. •…
-
Clear 2: Serial forward transfer error
Hydraulic Unit LED: Green 1 flash / Red 1 flash Outdoor Unit LED: 1 flash Probable causes: • Misconnection. • External cause. • Interface PCB failure. Check: 1-1. Stop the system and start it again (disconnection time 1min): Is the error still displayed? YES NO 2. Check the connections: - Check the…
-
Clear 4: Heat pump capacity signal error
Hydraulic Unit LED: Green 4 flashes / Red 1 flash Outdoor Unit LED: 22 flashes Probable causes: • Misconnection. • Sensor failure. • Interface PCB failure. Check: 1. Check connection interface PCB and Heat pump regulator PCB: - See if the connector has been disconnected. - See if the connection is…
-
Clear 5: Hydraulic Unit Heat exchanger thermistor error
Hydraulic Unit LED: Green 4 flashes / Red 2 flashes Outdoor Unit LED: 22 flashes Probable causes: • Misconnection. • Sensor failure. • Interface PCB failure. Check: 1. Check the sensor connection: - See if the connector has been removed - See if the connection is correct - Check for any damage on…
-
Clear 7: Discharge thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 1 flash Outdoor Unit LED: 2 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been disconnected. - See if the connection is correct. - Check for any damage on the…
-
Clear 8: Heat-exchange thermistor (outlet) error
Hydraulic Unit LED: Green 7 flashes / Red 3 flashes Outdoor Unit LED: 4 flashes Probable causes: • Misconnection. • Sensor fault. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been disconnected. - See if the connection is correct. - Check for any damage on the…
-
Clear 9: Outdoor temperature thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 4 flashes Outdoor Unit LED: 7 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection : - See if the connector has been disconnected. - See if the connection is correct. - Check for any damage on…
-
Clear 10: Heat Sink Thermistor (inverter) error
Hydraulic Unit LED: Green 7 flashes / Red 7 flashes Outdoor Unit LED: 9 flashes Probable causes: • Misconnection. • Sensor failure. • Inverter PCB failure. Check: 1. Check the sensor connection : - See if the connector has been disconnected. - See if the connection is correct. - Check for any damage…
-
Clear 11: Compressor thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 2 flashes Outdoor Unit LED: 8 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been removed - See if the connection is correct - Check for any damage on the…
-
Clear 12: Heat-exchange thermistor (intermediate) error
Hydraulic Unit LED: Green 7 flashes / Red 3 flashes Outdoor Unit LED: 5 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been disconnected. - See if the connection is correct. - Check for any damage on…
-
Clear 13: Heat sink thermistor (P.F.C.) error
Hydraulic Unit LED: Green 7 flashes / Red 7 flashes Outdoor Unit LED: 10 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been removed - See if the connection is correct - Check for any damage on the…
-
Clear 14: Expansion valve thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 8 flashes Outdoor Unit LED: 6 flashes Probable causes: • Misconnection. • Sensor failure. • Main PCB failure. Check: 1. Check the sensor connection: - See if the connector has been removed - See if the connection is correct - Check for any damage on the…
-
Clear 15: Current trip (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 4 flashes Outdoor Unit LED: 13 flashes Probable causes: • Connection failure. • Outdoor Heat Exchanger clogged. • Outdoor Fan operation failure. • Compressor failure. • Inverter PCB failure. Check: 1. Check connections condition in control unit: - Check if…
-
Clear 17: Compressor startup error (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 5 flashes Outdoor Unit LED: 15 flashes Probable causes: • Misconnection of the various electrical components. • Inverter PCB failure. • Compressor failure. Check: 1. Check connections condition in control unit: - Check if the terminal connection is loose.…
-
Clear 18: Fan motor error (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 7 flashes Outdoor Unit LED: 16 flashes (fan 1), 17 flashes (fan 2) Probable causes: • Fan motor failure. • Motor protection. • Main PCB failure. Check: 1. Check fan rotation: - Switch off the heat pump and rotate the fan manually. - If the fan or bearings…
-
Clear 20: Inverter error
Hydraulic Unit LED: Green 6 flashes / Red 3 flashes Outdoor Unit LED: 18 flashes Probable causes: • Connection failure. • Main PCB failure. • Inverter PCB failure. Check: 1. Check connections in control unit: - Check if the terminal connection is loose. - Check if connector is removed. - Check if…
-
Clear 22: Discharge temperature protection (permanent stoppage)
Hydraulic Unit LED: Green 10 flashes / Red 1 flashes Outdoor Unit LED: 11 flashes Probable causes: • Valve is close. • EEV failure. • Gas leak, less. • Discharge Thermistor failure. • Outdoor Fan operation failure. • Outdoor Heat Exchanger clogged. Check: Cooling mode Heating mode 1. Check if gas…
-
Clear 24: Pressure sensor error
Hydraulic Unit LED: Green 8 flashes / Red 6 flashes Outdoor Unit LED: 3 flashes Probable causes: • Connector connection failure. • Pressure Sensor failure. • Main PCB failure. Check: 1. Check connection of the Pressure Sensor: - Check if the terminal connection is loose. - Check if connector is…
-
Clear 25: Compressor temperature protection (permanent stoppage)
Hydraulic Unit LED: Green 10 flashes / Red 3 flashes Outdoor Unit LED: 12 flashes Probable causes: • Valve is close. • EEV failure. • Gas leak, less. • Compressor Thermistor failure. • Outdoor Fan operation failure. • Outdoor Heat Exchanger clogged. Check: Cooling mode Heating mode 1. Check if gas…
-
Clear 26: Low pressure abnormal
Hydraulic Unit LED: Green 10 flashes / Red 5 flashes Outdoor Unit LED: 20 flashes Probable causes: • Connector connection failure. • Pressure Sensor failure. • Main PCB failure. • Gas leak, less. Check: 1. Check connection of the Pressure Sensor: - Check if the terminal connection is loose. - Check…
-
Hydraulic Unit LED: Green 6 flashes / Red 4 flashes Outdoor Unit LED: 19 flashes Probable causes: • Connector connection failure. • Main PCB failure. • PFC PCB failure. Check: 1. Check connections of between Main PCB and PFC PCB: - Check if the terminal connection is loose. - Check if connector is…
-
Clear 33: Detection of compressor position error (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 5 flashes Outdoor Unit LED: 14 flashes Probable causes: • Misconnection. • Inverter PCB failure. Check: 1. Check connections condition in control unit: - Check if the terminal connection is loose. - Check if connector is removed. - Check if connector is…
-
4.2.2 Failures With No Error Code
Clear 35: No voltage on Hydraulic Unit Probable causes: • Power supply fault. • External causes. • Faulty electrical components. Check: 1. Check the installation : - Is the circuit breaker cut off? - Check the wiring. OK 2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or…
-
Clear 36: No voltage on outdoor unit
Probable causes: • Power supply fault. • External cause. • Faulty electrical components. Check: 1. Check the installation - Is the circuit breaker cut off? - Check the wiring. OK 2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop) : - Check for any other…
-
Clear 38: No heat
Probable causes: • Hydraulic Unit error. • Outdoor unit error. • Influence from the outdoor environment. • Misconnections of connectors and cables. • Refrigeration system fault (not enough gas, clogging, dirty filters). Check: 1. The unit provides heating or cooling No 2. Check the Hydraulic Unit…
-
Clear 39: Abnormal noise
Probable causes: • Abnormal installation (outdoor) • Fan failure • Compressor failure. Checks: 1. The noise comes from the outdoor unit: - Is the unit stable? - Is the protection screen properly mounted? OK - Is the propeller broken or distorted? - Has the propeller screw been lost? - Is any object…
-
Sensor Values 4.3.1 Outdoor Unit Temperature Sensors Outdoor Heat Exchanger (outlet), Outdoor Heat Exchanger (middle) Temperature (°C) -10 -5 20,9 16,1 12,4 9,73 7,67 27,5 Resistance value (kΩ) 25 6,1 30 3,95 Outdoor Discharge Pipe / Compressor / Expansion valve inlet Temperature (°C) Resistance…
-
Service parts information 4.4.1 Service parts information 1 : Compressor Diagnosis method of compressor (if outdoor unit LED displays error, refer to Failures and clears) Does not start up Stops soon after starting up Is there open or loose connection cable? Is there open or loose connection cable?…
-
4.4.2 Service parts information 2 : Inverter compressor
Check point 1 : Check connection Check terminal connection of compressor (Loose or incorrect wiring) Check connection of inverter PCB (Loose or incorrect wiring) Check point 2 : check winding resistance Check winding resistance on each terminal If the resistance value is 0Ω or infinite, replace…
-
4.4.3 Service parts information 3 : Outdoor unit electronic expansion
valve (EEV, EEV(INJ)) Check point 1 : Check connection Check connection of connector (Loose connector or open cable) Check point 2 : Check coil of EEV Remove connector, check each winding resistance of coil. Check point 3 : Check voltage from main PCB Remove connector and check voltage (DC12V) If it…
-
4.4.4 Service parts information 4 : Outdoor unit solenoid valve (SV)
Check point 1 : Check connections Check connection of connector (Loose connector or open cable) BLUE 2 2 CN104 BLUE 1 1 SV SOLENOID COIL (INJ) Check point 2 : Check solenoid coil Remove connector and check if coil is open (normal resistance value of each coil : 1495+/7%) If resistance value is…
-
Operating Limits WATERSTAGE 112 HEAT PUMP Min/max OT in heat mode (°C)*** Heating floor maximum water temperature (°C) LT radiator maximum water temperature (°C) Min/max OT in cooling mode(°C) Cooling floor minimum water temperature (°C) Fan coil minimum water temperature (°C) Water circuit max…
-
5 Failures
5.1 Hydraulic, Electric and Refrigeration Systems 5.1.1 Hydraulic System If the installation is fitted with a heating floor, the most common failures are those listed below: FAILURE CASES CONSEQUENCES SOLUTIONS APPLIED BY 1- Clogged filter* or sludge in system Flow pressure too high clean filter or…
-
5.1.2 Electrical System
Outdoor Unit Overvoltage Check for possible causes in the list below (this list is not exhaustive): • Problem with the compressor • PFC board • Inverter board • Main board • Faulty power relay Steps to be followed before performing any work on the Inverter module: • First switch off the system using…
-
5.1.3 Refrigeration System
Unit produces no heat The unit remains in continuous scanning mode. Initial checks: Check the settings Are the data sent by the user interface received by the heat pump? Hydraulic unit electronic circuit sending data to outdoor unit ? No Hydraulic unit electronic system faulty Yes Compressor running…
-
Outdoor unit does not defrost
• • • • Is condensation drain properly discharged (outdoor unit directly on the ground)? Are the auxiliaries powered? In boiler backup mode, is the boiler authorized? In very cold areas, a fusing resistance value is recommended. Is the installation regularly subject to microoutages of power…
-
b. Defrost ending conditions
With all models, defrosting stops if the exchanger temperature is above 10 °C or if the defrosting time is over 15 minutes). Crankcase heater When the outdoor exchanger temperature is below -5°C and the heating mode has been stopped for 30 minutes, the compressor windings are powered and maintain…
-
6 Control Settings
6.1 General The settings described below are those which can be modified by the user. We wish to remind you that changing the settings below may cause the heat pump to behave in an undesirable way. A testing period should be conducted before the permanent settings of the heat pump are confirmed.…
-
COMMAND LINE ACCESS LEVEL U U U U U 2nd phase on 2nd phase off 3rd phase on 3rd phase off Default values Time program 4 / DHW 560 U Preselection FUNCTION st SETTING RANGE 00:00…--:-00:00…--:-00:00…--:-00:00…--:-No/yes --:---:---:---:-No Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦ Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦…
-
LINE
ACCESS LEVEL S I I I I S 901 902 U U Actuator running time Floor curing function Floor curing setpoint manually Floor curing day current Floor curing days completed Optg mode changeover Cooling circuit 1 Operating mode Comfort cooling setpoint 907 U Release I I I S S S S S S S S S S S S S S S S S…
-
LINE
ACCESS LEVEL 1156 1157 1200 I I S 1610 1612 U U FUNCTION Floor curing day current Floor curing days completed Optg mode changeover Domestic hot water Nominal setpoint Reduced setpoint FACTORY SETTING SETTING RANGE 0…32 0…32 Protection mode Thc…65°C 8°C….Thc 50°C 25°C 24h/day Heating circ time pgms…
-
LINE
ACCESS LEVEL FUNCTION SETTING RANGE HC+DHW op mode change HC op mode change HC1 op mode change HC2 op mode change Error/alarm msg Dewpoint monitoring Pool release Normally closed Normally open 6046 I Function Input H2 6047 6048 6100 6120 6205 6220 I S S S S S 6711 6740 6741 6745 6746 6800 6802 6804…
-
COMMAND LINE ACCESS LEVEL 7711 I FUNCTION Voltage signal UX 7720 I Digital output test 7721 7722 7730 7820 7823 7824 7830 7831 7832 7833 7841 7846 7855 7914 7915 7916 I I I I I I I I I I I I I I I I 8000 8001 8003 8004 8006 8011 8022 8050 8052 8054 8056 8058 8060 8062 8064 8066 8068 I I I I I I I I…
-
LINE
-
Adjustment Function Details 6.3.1 Date and Time Functions The controller has an annual clock which contains the time, the day of the week and the date. LINE NO. In order for the function to operate, the time and date must be set properly on the clock. PROGRAMMING LINE Hour/minutes Day/month Year…
-
6.3.2 User Interface Functions
LINE NO. PROGRAMMING LINE Language Info Operation lock Programming lock Direct adjustment Info (22): • Temporary: After pressing the Info key, the information display returns to the basic "predefined" display after 8 minutes or when pressing the operating mode key. • Permanent: After pressing the…
-
Room unit 1 Room unit 2 Room unit P Operator unit 1 Programming line 42 Heating circuit 1 Heating circuits 1 and 2 Heating circuits 1 and P All HCs Heating circuit 1 Heating circuits 1 and 2 Heating circuits 1 and P All HCs X X X X X X X X X X X 54 X X X Operator unit 2 Operator unit P Operating…
-
6.3.3 Time Program Functions (heating circuit 1 & 2, DHW, cooling)
Several control programs are available for the heating circuits and the production of DHW. They are initiated in "Automatic" mode and control the change in temperature levels (and therefore the associated setpoints, reduced and comfort) via the adjusted changeover times. Enter changeover times…
-
Holidays
Line no. HC1 Programming line HC2 Start End Operating level The holiday program enables changing the heating circuits over to a selected operating level according to the date (calendar). Important ! The holiday program can be used only in the automatic mode. 6.3.4 Heating Circuit 1 & 2 Functions…
-
Heating Curve
Line no. HC1 Programming line HC2 1020 1021 1026 Heating curve slope Heating curve displacement Heating curve adaptation Heating curve slope: Based on the heating characteristic, the controller computes the flow temperature setpoint which will be used for controlling the flow temperature in…
-
Information
To ensure operation, the following requirements must be met: A room sensor must be connected. The "room influence" parameter must be set between 1 and 99. The reference room (where the room sensor is installed) must not contain adjusted thermostatic valves. If present in the room, these valves must…
-
24-Hour heating limit
The 24-hour heating limit is used to switch the heating on and of in the course of the day, depending on the outside temperature.This function is used mainly during intermediate seasons (spring and fall) to react rapidly in case of fluctuating temperatures. Thus, in the following example the…
-
percentage. The better the installation in the reference room (accurate room temperature, correct installation location, etc.) the higher will be the value that can be set. Example: Approx 60%: the reference room is appropriate Approx 20 %: the reference room is inappropriate Information: Activation…
-
Optimisation at switch-on and switch-off
Line no. HC1 790 791 Programming line HC2 1090 1091 Optimum start control max Optimum stop control max Optimum start control max The change in temperature levels is optimised in such a way as to reach the comfort setpoint during changeover times. Optimum stop control max The change in temperature…
-
Mixing Valve Control
Line no. HC1 830 834 Programming line HC2 1130 1134 Mixing valve boost Actuator running time Mixing valve boost The controller adds the increase set here to the current flow setpoint and uses the result as the temperature setpoint for the heat generator. Actuator running time For 3-position control…
-
Heat pump
flow temp Days Fh Bh Fh + Bh X : Starting day "Manual controlled curing" setpoint The flow temperature setpoint for the "Manual" controlled floor drying function can be adjusted separately for each heating circuit. Current controlled curing setpoint Displays the current flow temperature setpoint for…
-
6.3.5 Cooling Circuit 1 Functions
The cooling sequence is automatically started when the room temperature is higher than the comfort setpoint in cooling mode (line 902). The cooling function must be activated (command line 901 = Auto) and is triggered by the programming clock (Command line 907). The cooling sequence is interrupted…
-
Cooling Characteristic
Line no. Programming line 908 909 Flow temp setp at OT 25°C Flow temp setp at OT 35°C The controller computes the flow temperature required for a given averaged outdoor temperature based on the cooling characteristic. This is defined by two reference points (flow setpoint at 25°C and at 35°C). Flow…
-
Summer Compensation
Line no. Programming line Summer comp start at OT Summer comp end at OT Summer comp setp increase In summer the "cooling comfort setpoint" (902) is gradually increased according to the outdoor temperature. This saves on cooling power and prevents the differences between the ambient temperature of…
-
Flow Setpoint Limitation
Line no. Programming line 923 924 Flow temp setp min at OT 25°C Flow temp setp min at OT 35°C It is possible to assign a lower limit to the cooling flow temperature. The limitation line will be defined by two reference points. In addition the resulting flow setpoint will have a lower limit and may…
-
Control according to outdoor conditions with
room influence The difference between the room temperature and the setpoint value is measured and taken into account for temperature control. This enables taking into account possible heat inputs and ensures a more even room temperature. Thus the differences with the room temperature are taken into…
-
Mixing Valve Control
Line no. Programming line Mixing valve cooling offset Actuator running time Mixing valve in heating mode Mixing valve cooling offset The cooling demand issued by cooling circuit 1 to production is reduced by the adjusted value. If there is a second zone, this reduction should enable the second zone…
-
Dewpoint Monitoring
Line no. Programming line Lock time dewpoint limiter Flow temp setp incr hygro Flow setp incr start at r.h. Flow temp diff. dewpoint These settings are useful only when a dewpoint sensor (hygrostat). is used. Lock time dewpoint limiter As soon as the dewpoint sensor detects condensation, it closes…
-
With prim controller/system pump
Line no. Programming line 963 With prim contr/system pump (no / yes) This setting specifies whether the cooling circuit is supplied from the primary controller or from the primary pump (depending on the installation). It can also be used to provide cooling to the second zone. Warning: In the case of…
-
Release
Line no. Programming line 1620 Release (24h/day / Heating circ time pgm / Time program 4/DHW / Low-tariff/ Time pgm 4/DHW or Low-tariff) 24h/day (Not recommended) Regardless of the time programs, the temperature of the domestic hot water is continuously maintained at the DHW nominal setpoint…
-
DHW mode
Off On On On On On On On On x = indifferent Holiday status Release (settings 1620) Time pgm status (Pgm 4) x x x x x Yes No No No No No No No … Low tariff (OPK) Low tariff (OPK) Time pgm 4 or OPK Time pgm 4 or OPK Time pgm 4 or OPK Time pgm 4 or OPK Information: Release by low tariff input always…
-
Circulation Pump
Line no. Programming line 1660 Circulation pump release Circulation pump release The "DHW release" setting switches on the circulation pump when DHW production is released. 6.3.7 Swimming Pool Functions Line no. Programming line 2056 Setpoint source heating The controller enables a swimming pool to…
-
6.3.9 DHW Tank Functions
DHW charging at the nominal setpoint temperature (1610) always takes place in two stages. In the first stage, only the heating pump heats the DHW tank. The power supplied during this time is at its peak. Then, when the heat pump is no longer able to supply enough heat to reach the setpoint value, it…
-
Heater
Line no. Programming line 5060 5061 El imm heater optg mode Electric immersion heater release El imm heater optg mode • Substitution The heater performs DHW charging as soon as the heat pump is stopped or becomes inoperative, or if the heat pump has finished charging without reaching the setpoint.…
-
• Time program 4/DHW
Time program 4/DHW of the local controller is taken into account for the heater. Information: Switch-on will actually be in effect only if the heater is able to operate according to the "heater operating mode" setting. 6.3.10 Configuration Functions When an installation is started up, the hydraulic…
-
Input H2 Function
Input H2 is available only on the control extension module. No more than two extension modules can be fitted into an installation. In this case the settings on Line no. Programming line 6046 6047 6048 contact H2 will be assigned to the module with address 1. Only one function can be assigned to…
-
Installation Frost Protection
Line no. Programming line 6120 Frost protection for the plant According to the outdoor temperature, the heating circuit pump and the condenser pump are switched on although there is no demand for heat Outdoor temperature Pump Diagram Continuously ON Set to ON for 10 min, approx. every 6 hours.…
-
Fault Indication Function
Line no. Programming line 6740 6741 6745 6746 Flow temp 1 alarm Flow temp 2 alarm DHW charging alarm Flow temp cooling 1 alarm The difference between the setpoint value and the current temperature value is monitored. Any difference which continues after the set time period has elapsed will trigger…
-
Table of error messages which can be displayed
-
Reset
360: no process reversing valve Y22 364: Heat pump cooling system error 369: External fault 370: Outdoor unit fault Number* If such statuses or events occur for the first time, they will not directly generate a fault message, but only a status message. 100 No No Yes 3 No No Yes 3 No No Only if the…
-
Maintenance / Special Operating Mode Functions Maintenance Maintenance functions can be used as a preventive step for periodically monitoring the installation. All maintenance functions can be individually activated / deactivated. Line no. Programming line 7070 7071 7072 7073 7076 7077 7078 7079…
-
DHW stor tank since maint (7091)
The time elapsed (in months) since the last maintenance. If the value is greater than the setting "DHW tank interval" (Line 7090), this symbol will be displayed and a maintenance message will appear in the Info section: 11: TWW DHW tank period (Priority 6) Emergency mode If the heat pump is not…
-
Input / Output Testing Functions Input/output testing is used to ensure that the connected components are in working order. Relay Output Testing Selection of a setting from relay testing closes the corresponding relay and therefore switches on the connected component. This makes it possible to Line…
-
Input Testing
Line no. Programming line 7914 7915 7916 Input EX4 Input EX5 Input EX6 If a test setting is selected, the associated input is displayed and can thus be checked. The "0 V" display means that there is no voltage and that the respective input is currently inactive. The 6.3.14 "230 V" display indicates…
-
State heating circuit
End user (Info level) Thermostat response Manual action active Controlled drying active Heating mode restriction Startup, heating engineer Thermostat response Manual action active Controlled drying active Overeating protection active Restriction, Boiler protection Restriction, DHW priority…
-
State DHW (8003)
End user (Info level) Thermostat response Manual action active Draw-off mode Adiabatic cooling active Charging lock active Forced charging active Charging by heater Accelerated charging active Charging active Frost protection active Switch-off delay active Charging on standby Charged Off Ready 106…
-
State cooling circuit (8004)
End user (Info level) Dewpoint sensor activated Manual action active Fault Frost protection active Cooling mode locked Cooling mode restricted Comfort cooling mode Cooling protection mode Frost protection active OT cooling limit activated Off Cooling mode off Maintenance Document 1394-1 Startup…
-
State heat pump (8006)
End user (Info level) Emergency mode Fault Locked Lim. time active Frost protection active Defrosting activated Cooling mode active Heating Frost protection active Off Startup, heating engineer Emergency mode Fault Locked, outdoor temperature Locked, external Locked, economy mode Consumer flow rate…
-
State supplementary source (8022)
End user (Info level) Locked In operation for HC, DHW Released for HC, DHW In operation for DHW Released for DHW In operation for heating circuit In operation for HC, DHW Released for HC, DHW In operation for DHW Released for DHW In operation for heating circuit Released for HC Overrun active Off.…
-
Setpoints and Measured Values
Line no. Programming line 8410 8412 8413 8425 Return temp HP Flow temp HP Compressor modulation Temp diff condenser These lines allow the various setpoints and measured values for the heat pump to be viewed. Hour / Startup Counter Line no. Programming line 8454 8455 8456 8457 Locking time HP Counter…
-
Cooling Circuit
Line no. Programming line 8756 Flow temperature cooling 1 The actual values of the cooling mode are displayed. The cooling mode room setpoint is displayed on programming line 8741. Domestic Hot Water Line no. Programming line 8820 8821 8830 8840 8841 8842 8843 DHW pump Electric immersion heater DHW…
-
Status of Relays for Extension Modules 1 and 2
Line no. Programming line 9050 9051 9052 9053 9054 9055 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 The switching status of the relays connected to extension modules 1 and 2 can be…
-
7 Annual Maintenance Services
7.1 • • • • clean filter (if any) inspect heating system (system pressure, purging, leak test) inspect expansion vessel (preload with nitrogen at 1 bar) fix any leaks 7.2 • • • • Hydraulic Circuit Outdoor unit clean heat exchanger clean refrigeration and ventilation compartment check for correct…
-
8 Connection Diagrams
8.1 114 Connection Diagram of Hydraulic Unit Maintenance Document 1394-1
-
Connection Diagram of Outdoor Unit Heat exchanger MID Maintenance Document 1394-1 115
-
Disassembly Process of Outdoor Unit > Warning ! < Before servicing the unit, turn the power supply switch OFF, then, do not touch electric parts for 10 minutes due to the risk of electric shock. Appearance 9.2 Service panel removal 9.3 Insulation sheet removal 116 9.1 Maintenance Document 1394-1
-
Main PCB removal 9.5 INVERTER, PFC, FILTER, and CAPACITOR PCB removal Maintenance Document 1394-1 117
-
9.5.1 INVERTER PCB removal
9.5.2 PFC PCB removal 9.5.3 FILTER PCB removal 118 Maintenance Document 1394-1
-
9.5.4 CAPACITOR PCB removal
Maintenance Document 1394-1 119
-
FAN MOTOR removal
9.7 TOP PANEL removal 9.8 PIPE COVER FRONT removal 120 9.6 Maintenance Document 1394-1
-
RIGHT PANEL removal 9.10 REACTOR removal 9.11 THERMISTOR removal 9.11.1 HEAT EXCHANGER (OUT) THERMISTOR 9.11.2 EXPANSION VALVE THERMISTOR Maintenance Document 1394-1 121
-
9.12 SOLENOID COIL removal
9.12.1 4WAY VALVE 9.12.2 INJECTION 9.13 EEV COIL removal 9.13.1 MAIN 9.13.2 INJECTION 9.14 PRESSURE SENSOR removal > Warning ! < Wear gloves to prevent the frostbite, because a small amount of refrigerant leaks during work. 122 Maintenance Document 1394-1
-
9.15 COMPRESSOR removal
Precautions for exchange of compressor. Do not allow moisture or debris to get inside refrigerant pipes during work. Procedure for compressor removal. 1 Turn off the power 2 Remove the service panel 3 Fully close the 3Way valve (gas) and 3Way valve (liquid) 4 Collect the refrigerant from the 3Way…
-
Procedure for compressor installation
Reverse procedure to removing the compressor. Precautions for installation of compressor. 1 When brazing, do not apply the flame on the terminal. 2 When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale. 124 Maintenance Document 1394-1
-
9.16 Precautions for exchange of refrigerant-cycle-parts
Maintenance Document 1394-1 125
-
Spare Parts The data is being prepared. 126 Maintenance Document 1394-1
-
Accessories 11.1 DHW kit See installation instructions "DHW kit" no. 1316. 11.2 Swimming pool kit See installation instructions "Swimming Pool Kit" no. 1341. 11.3 2nd circuit kit Management of 2 heating circuits requires installation of the 2nd zone kit, which includes a controller extension module…
-
2284Z35a
2284Z34a 2284Z33a Heat Pump, Split System, Single Service, 3 phase Connection: The room thermostat must be connected to one of the terminals b (CL+, CL-) of the heat pump controller board. To do this, you can use a 0.5mm² cable of the two-pair telephone cable type. If the cable is shielded, the…
-
Remote control The remote control includes the functions of the room unit together with those of the user interface mounted in series on the Hydraulic Unit. It can be used, therefore, not only to measure the room temperature, but also to view the operating status of the heat pump, to enter the pump…
-
Connections
The room central unit must be connected to terminal b (CL+, CL-, G+) of the heat pump controller board. To do this, you can use a 0.5mm² cable of the twopair telephone cable type. Terminal T75 If the cable is shielded, the shielding can be connected to the controller CL- terminal. It may under no…
-
12 Related Documents
12.1 Quick-Start Procedure Before switching on the Hydraulic Unit: 1. Check the electric wiring 2. Check the refrigeration circuit and make sure the gas supply has been performed 3. Check the hydraulic circuit, with 1-2 bar pressure, check that the heat pump is purged, as well as the rest of the…
-
12.2 Startup Checklist
Date: After Sales Service identification: Unit reference number: Installation identification: Installer identification: Serial number: BEFORE STARTING UP Sight Checks Outdoor unit: (See "Outdoor unit Installation" section of "Installation" instructions) OK NON COMPLIANT OK NON COMPLIANT OK NON…
-
STARTING UP
Switching On (See "Starting up" section of "Installation" instructions) OK NON COMPLIANT OK NON COMPLIANT VALUE OK NON COMPLIANT VALUE OK NON COMPLIANT Switching on Initialisation for a few seconds Operation of the pumps Outdoor unit starts after 3mins Checks on Outdoor Unit Operation of fan(s)…
-
12.3 Settings Sheet
Setting Description set to Menus Setting Description Preliminary settings 20 language 5700 set to Menus Boiler backup Op. section 3700 Release below out. temp Suppl. source. hour / minutes time and date 3705 Overrun time Suppl. source. day / month time and date year time and date 6046 Function Input…
-
12.4 Startup Data Sheet
Site: Installer: Outdoor unit Serial no.: Hydraulic Unit Serial no.: Model: Model: Refrigerant type: Refrigerant charge: Checks kg Operating voltage and current on Outdoor Unit Compliance with positioning distances L1/N, L2/N, L3/N : V Condensate evacuation correct L1/E, L2/E, L3/E : V Electric…
-
Fujitsu General (Euro) GmbH
Werftstrasse 20 40549 Düsseldorf - Germany 136 Maintenance Document 1394-1